ESIE98–06A
The Controller for the EUWA/Y15-30HC(Z) Chillers
Part 2 – Functional Description
2–37
3
2
4
5
1
3.11
t
History Menu
Reading safety info
after shutdown
Using this menu you can at all times read the information of the latest shutdowns:
■
The number of times a unit safety or circuit safety occurred
■
The unit status at the moment of the last shutdown.
Screen 1
This screen shows the unit history:
Screens 2-4
These screens show the circuit history:
Line n°
Display
Description
1
UNIT HISTORY: XXX
x = the total number of unit shutdowns
2
REVERSE PHASE PROT.
FLOW HAS STOPPED
the unit safety: reverse phase protection or flow switch
3
INLET WATER
inlet water temperature
4
AMB.
ambient temperature
4
COOLING/HEATING
operation mode: cooling or heating
Line n°
Display
Description
1
C1/C2/C3 HISTORY: XXX
x = the total number of circuit shutdowns
2
OUTL. WATER
outlet water temperature
3
INLET WATER
inlet water temperature
4
AMB.
ambient temperature
4
COOLING/HEATING/
DEFROST
operation mode: cooling, heating or defrost
Summary of Contents for EUWA/Y5-30HB/C(Z)
Page 2: ......
Page 8: ...Introduction ESIE98 06A vi 3 1 4 5...
Page 10: ...ESIE98 06A 1 2 Part 1 System Outline 3 1 1 4 5...
Page 28: ...General Outline ESIE98 06A 1 20 Part 1 System Outline 3 1 1 4 5...
Page 36: ...Piping Layout ESIE98 06A 1 28 Part 1 System Outline 3 1 1 4 5...
Page 52: ...ESIE98 06A Wiring Layout Part 1 System Outline 1 44...
Page 58: ...ESIE98 06A 2 2 Part 2 Functional Description 3 1 2 4 5...
Page 100: ...ESIE98 06A 3 2 Part 3 Troubleshooting 3 1 3 4 5...
Page 134: ...Troubleshooting ESIE98 06A 3 36 Part 3 Troubleshooting 3 1 3 4 5...
Page 136: ...ESIE98 06A 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 142: ...Pre Test Run Checks ESIE98 06A 4 8 Part 4 Commissioning and Test Run 3 1 4 5...