The Controller for the EUWA/Y15-30HC(Z) Chillers
ESIE98–06A
2–32
Part 2 – Functional Description
3
1
2
4
5
3.8
z
Set Points Menu
Glycol application
Follow the next steps when you want to start the glycol application.
Two temperature
set points
This menu provides the ability to set the inlet water temperature. You can adjust two sets of
temperature set points. Each set contains a cooling and a heating set point. These set points will only
be active in automatic control mode.
The actual active set point can be consulted in the read-out menu (refer to page 2-31).
There is no outlet water control available in these units.
Selection between
set point 1 and 2
You can select set point 1 or 2 by the remote dual set point switch (if installed), refer ‘Field Wiring’ on
page 1-45.
To adjust the inlet water temperature set points, use the programming procedure on page 2-30.
step
Action
1
Push the read-out & user setting buttons at the same time for 5 seconds.
2
Release the push buttons, the C led is on.
3
Put in the password 1914.
Line n°
Display
Description
Default value
Limit value
Step
value
1
SETP. COOL 1
cooling set point 1
+12.0˚ C
+7.0
to
+25.0˚ C
0.1˚ C
2
SETP. COOL 2
cooling set point 2
+12.0˚ C
+7.0
to
+25.0˚ C
0.1˚ C
3
SETP. HEAT 1
heating set point 1
+30.0˚ C
+25.0
to
+55.0˚ C
0.1˚ C
4
SETP. HEAT 2
heating set point 2
+30.0˚ C
+25.0
to
+55.0˚ C
0.1˚ C
Summary of Contents for EUWA/Y5-30HB/C(Z)
Page 2: ......
Page 8: ...Introduction ESIE98 06A vi 3 1 4 5...
Page 10: ...ESIE98 06A 1 2 Part 1 System Outline 3 1 1 4 5...
Page 28: ...General Outline ESIE98 06A 1 20 Part 1 System Outline 3 1 1 4 5...
Page 36: ...Piping Layout ESIE98 06A 1 28 Part 1 System Outline 3 1 1 4 5...
Page 52: ...ESIE98 06A Wiring Layout Part 1 System Outline 1 44...
Page 58: ...ESIE98 06A 2 2 Part 2 Functional Description 3 1 2 4 5...
Page 100: ...ESIE98 06A 3 2 Part 3 Troubleshooting 3 1 3 4 5...
Page 134: ...Troubleshooting ESIE98 06A 3 36 Part 3 Troubleshooting 3 1 3 4 5...
Page 136: ...ESIE98 06A 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 142: ...Pre Test Run Checks ESIE98 06A 4 8 Part 4 Commissioning and Test Run 3 1 4 5...