7.8
Setting gas/air regulation
The CO
2
setting has been set at the factory and does not require any adjustments, in principle.
The setting can be checked by measuring the CO
2
percentage in the combustion gases. In case
of any disturbance of the setting, the replacement of the gas valve or the conversion to a
different type of gas must be checked, and if necessary set in accordance with the following
instructions. Always check the CO
2
percentage when the lid is open.
Checking the carbon dioxide setting
1
Switch off the heat pump module with the user interface.
2
Switch off the gas boiler with the button.
-
appears on the service display.
3
Remove the front panel from the gas boiler.
4
Remove the sample point (a) and enter an appropriate chimney analysis probe.
IMPORTANT
Ensure the start-up procedure of the analysis machine has been
completed before inserting the probe in the sample point.
IMPORTANT
Wait for the gas boiler to run stable. Faulty measurements may occur if the
measuring probe is connected before the boiler is running stable.
5
Switch on the gas boiler with the button and create a request for space heating.
6
Select the High setting by twice pressing the
and buttons simultaneously. A
capital letter "H" will appear on the service display. The user display will show a Busy
symbol. Do NOT carry out a test when a small letter "h" is shown. If this is the case,
press
and again.
7
Allow the display values to stabilize. Wait at least 3 minutes and compare the CO
2
percentage to the values in the following table.
CO
2
value at
maximum power
Natural gas G20
Propane G31 (30/37/50 mbar)
Maximum value
9.6
10.8
Minimum value
8.4
9.8
8
Note the CO
2
percentage at maximum power. This is important in relation to the following
steps.
IMPORTANT
It is NOT possible to adjust the CO
2
percentage when the test program is being
carried out. If the CO
2
percentage deviates from the values in the above table,
contact your local service department.
9
Select the Low setting by once pressing the
and buttons simultaneously.
"L" appears on the service display. The user display will show a Busy symbol.
10
Allow the display values to stabilize. Wait at least 3 minutes and compare the CO
2
percentage to the values in the following table.
CO
2
value at
minimum power
Natural gas G20
Propane G31 (30/37/50 mbar)
Maximum value
(a)
Minimum value
8.4
9.4
(a)
CO
2
value at maximum power registered at setting High.
Summary of Contents for EKOMBG22ABV1
Page 29: ...Daikin Europe NV 31...
Page 82: ...Daikin Europe NV 31...
Page 136: ...Daikin Europe NV 32...
Page 189: ...Daikin Europe NV 31...
Page 242: ...Daikin Europe NV 32...
Page 295: ...Daikin Europe NVs GmbH 31...
Page 347: ...Daikin Europe NV 31...
Page 372: ...Daikin Europe NV 4 Daikin EKOMBG22ABV1 EKOMBG28ABV1 EKOMBG33ABV1 CH DHW O...
Page 377: ...Daikin Europe NV 9 3 A CH L B C M D S1 N X4 E S2 O F P S3 G Q H R I 230 V S J T K U...
Page 381: ...Daikin Europe NV 13 4 2 1 2 cm O 4 2 1 50 cm2 4 2 2 A 1 2 70 C a b DHW c d e...
Page 382: ...Daikin Europe NV 14 4 3 EKVK4AA B 4 3 1 4 3 2...
Page 387: ...Daikin Europe NV 19 5 3 1 3 mm 1 2 A 3 1 4 2 5 6 10 2 7 8 5 3 1 X4 6 7 11 12 8 9 6 7...
Page 389: ...Daikin Europe NV 21 RF CH 5 RF CH 2 C rF L RF RF 1 5 4 4 10 1 7 5 5 5 1 1 2 2 3 4 50 mbar 5...
Page 391: ...Daikin Europe NV 23 5 2 CE B23 B33 C13 C33 C43 CLV C53 C63 CE...
Page 398: ...Daikin Europe NV 30 5 5 5 O 1 5 3 250 mm 2000 mm 1000 mm 1 500 mm...
Page 399: ...Daikin Europe NV 31...
Page 405: ...Daikin Europe NV 37 6 3 1 2 3 4 5 6 6 3 1 10 2...
Page 406: ...Daikin Europe NV 38 7 7 1 LED CH bar q 0 Su Et q LED Eco LED LED 8 2 LED 2 LED LED LED 30...
Page 414: ...Daikin Europe NV 46 8 3 8 3 1 7 7 7 8 8 3 2 20 mbar 7 7 7 8 8 3 3 CH 10 1 OpenTherm CH RF 80...
Page 417: ...Daikin Europe NV 49 9 9 1 1 1 2 3 4 5 6 7 1 2 3 8 4 5 6 9 10 11 Allen 12 9 1 2 1 2 3 4 5...
Page 418: ...Daikin Europe NV 50 9 1 3 1 2 O 10 12 Nm 3 4 5 6 1 2 3 A 7 8 9 10 CH 11 12 13 14 7 7 7 8 15 16...
Page 423: ...Daikin Europe NV 55 11 Daikin Europe NV CH...
Page 424: ...008 1548499_04 05 2022 88550712...