CONNECTING
5.1
Connecting CH installation
1.
Rinse the CH installation carefully.
2.
Fit the supply pipe (A) and return pipe (B) to the connection set.
3.
All pipes must be assembled with no electrical current, in order to prevent shocks
from the pipes.
4.
Existing connections may not be rotated, in order to prevent leakages.
The CH installation must be fitted with:
•
A filling/draining tap (A) in the return pipe, immediately underneath the unit.
•
A draining tap at the lowest point of the installation.
•
An overflow valve (B) of 3 bar in the input pipe at a distance of no more than 500 mm
from the unit.
Between the unit and the overflow valve there may be no valve or constriction.
•
An expansion vessel in the return pipe (in the B-pack or in the installation).
•
A check valve, if there are pipes running up, within close distance of the unit. This
prevents a thermosiphon effect from occurring during tap water operation (a non
spring-operated return valve, must be assembled vertically).
5.1.1
Thermostatic radiator taps
If all radiators are fitted with thermostatic or cable radiator taps, a minimum water
circulation must be safeguarded. See par. 7.3.
5.1.2
Underfloor heating
Underfloor heating with pump
If an underfloor heating system is not hydraulically neutral, the underfloor heating pump
may generate unwanted circulation over the CH boiler. For a good functioning of the
domestic hot water provision, unwanted circulation over the CH boiler must be
prevented.
Connect an underfloor heating system indirectly hydraulically neutrally or provide the
CH installation with a two-way valve set 230 V ~ (E). If the underfloor heating pump
absorbs heat via the return of the boiler, unwanted circulation can be prevented by
means of a check valve (D).
Make sure there is a minimal water circulation. See par. 7.3.
Connection diagram underfloor heating
A.
CH boiler
B.
CH pump
C.
Thermostatic control valve
D.
Spring-operated check valve
E.
Electrical valve 230 V ~
F.
Radiators
G.
Space/clock thermostat
H.
Maximum thermostat
Summary of Contents for EKOMBG22ABV1
Page 29: ...Daikin Europe NV 31...
Page 82: ...Daikin Europe NV 31...
Page 136: ...Daikin Europe NV 32...
Page 189: ...Daikin Europe NV 31...
Page 242: ...Daikin Europe NV 32...
Page 295: ...Daikin Europe NVs GmbH 31...
Page 347: ...Daikin Europe NV 31...
Page 372: ...Daikin Europe NV 4 Daikin EKOMBG22ABV1 EKOMBG28ABV1 EKOMBG33ABV1 CH DHW O...
Page 377: ...Daikin Europe NV 9 3 A CH L B C M D S1 N X4 E S2 O F P S3 G Q H R I 230 V S J T K U...
Page 381: ...Daikin Europe NV 13 4 2 1 2 cm O 4 2 1 50 cm2 4 2 2 A 1 2 70 C a b DHW c d e...
Page 382: ...Daikin Europe NV 14 4 3 EKVK4AA B 4 3 1 4 3 2...
Page 387: ...Daikin Europe NV 19 5 3 1 3 mm 1 2 A 3 1 4 2 5 6 10 2 7 8 5 3 1 X4 6 7 11 12 8 9 6 7...
Page 389: ...Daikin Europe NV 21 RF CH 5 RF CH 2 C rF L RF RF 1 5 4 4 10 1 7 5 5 5 1 1 2 2 3 4 50 mbar 5...
Page 391: ...Daikin Europe NV 23 5 2 CE B23 B33 C13 C33 C43 CLV C53 C63 CE...
Page 398: ...Daikin Europe NV 30 5 5 5 O 1 5 3 250 mm 2000 mm 1000 mm 1 500 mm...
Page 399: ...Daikin Europe NV 31...
Page 405: ...Daikin Europe NV 37 6 3 1 2 3 4 5 6 6 3 1 10 2...
Page 406: ...Daikin Europe NV 38 7 7 1 LED CH bar q 0 Su Et q LED Eco LED LED 8 2 LED 2 LED LED LED 30...
Page 414: ...Daikin Europe NV 46 8 3 8 3 1 7 7 7 8 8 3 2 20 mbar 7 7 7 8 8 3 3 CH 10 1 OpenTherm CH RF 80...
Page 417: ...Daikin Europe NV 49 9 9 1 1 1 2 3 4 5 6 7 1 2 3 8 4 5 6 9 10 11 Allen 12 9 1 2 1 2 3 4 5...
Page 418: ...Daikin Europe NV 50 9 1 3 1 2 O 10 12 Nm 3 4 5 6 1 2 3 A 7 8 9 10 CH 11 12 13 14 7 7 7 8 15 16...
Page 423: ...Daikin Europe NV 55 11 Daikin Europe NV CH...
Page 424: ...008 1548499_04 05 2022 88550712...