Space heating operation ( )

Space heating operation can be controlled on two different ways:

-

based on room temperature,

-

based on leaving water temperature.

The purpose of each operation and how the configuration is done, is
explained below.

Room temperature control

In this mode, heating will be activated as required by the room
temperature set point. The set point can be set manually or through
the schedule timer.

Selecting space heating operation

1

Use the 

 button to switch ON/OFF space heating ( ).

Icon 

 appears on the display as well as the corresponding

actual room temperature set point.

The operation LED   lights up.

2

Use the 

 and 

 buttons to set the desired room

temperature.

Temperature range for heating: 16°C~32°C (room temperature)

In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (see operation range).

Refer to 

"Programming and consulting the schedule timer" on

page 12

 for setup of the schedule timer function.

3

Use the 

 and 

 buttons to select the leaving

water temperature which you want to be used to heat up your
system (for detailed information see 

"Leaving water temperature

control" on page 5

).

Automatic setback function

Setback function provides the possibility to lower the room
temperature. The setback function can for instance be activated
during the night because the temperature demands during night and
day are not the same.

The setback function is configured through field settings. Refer to the
chapter 

"Field settings" on page 16

 for a detailed description how to

set one or more field settings.

[2-00] Status: defines whether the setback function is turned ON
(1) or OFF (0)

[2-01] Start time: time at which setback is started

[2-02] Stop time: time at which setback is stopped

[5-03] Room setback temperature

Leaving water temperature control

In this mode, heating will be activated as required by the water
temperature set point. The set point can be set manually, through the
schedule timer or weather dependent (automatic).

Selecting space heating operation

1

Use the 

 button to switch ON/OFF space heating ( ).

Icon 

 appears on the display as well as the corresponding

water temperature set point.

The operation LED   lights up.

2

Use the 

 and 

 buttons to set the desired leaving

water temperature.

Temperature range for heating: 25°C~80°C (leaving water
temperature)

In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (see operation range).

Refer to "Remote controller schedule timer" for setup of the schedule
timer function.

NOTE

When using room temperature control, space heating
operation based on room temperature will have priority
over leaving water control.

Note that it is possible that the leaving water
temperature becomes higher than the set point if the
unit is controlled by room temperature.

NOTE

Remark that the   icon will be flashing during
setback operation.

By default the setback function is enabled.

The setback function can be combined with the
automatic weather dependent set point operation.

Setback function is an automatic daily scheduled
function.

A

Normal room temperature set point

t

Time

T

Temperature

NOTE

While room temperature setback function is active,
leaving water setback operation is also performed (see

"Leaving water temperature control" on page 5

).

Pay attention not to set the setback value too low,
especially during colder periods (e.g. winter time). It is
possible that the room temperature can not be reached (or
it will take a much longer time) because of the big
temperature difference.

NOTE

When an external room thermostat is installed,
the thermo ON/OFF is determined by the external
room thermostat. The remote controller is than
operated in the leaving control mode and is not
functioning as a room thermostat.

The remote controller ON/OFF status always has
priority over the external room thermostat!

[2-01]

[2-02]

A

T

t

21

°

C

[5-03] 18

°

C

Summary of Contents for EKHBRD011ADV1

Page 1: ...OPERATION MANUAL EKHBRD011ADV1 EKHBRD014ADV1 EKHBRD016ADV1 EKHBRD011ADY1 EKHBRD014ADY1 EKHBRD016ADY1 Indoor unit for air to water heat pump system and options...

Page 2: ...y or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children sh...

Page 3: ...sh the button See Automatic storage on page 7 The icon will display Hot water will be produced at next scheduled action When water heat up starts the icon will be blinking 1 second interval Manual sto...

Page 4: ...installation purposes only 13 NOT AVAILABLE This icon is displayed whenever a non installed option is addressed or a function is not available A function not available can mean insufficient permissio...

Page 5: ...on as well as the shift value in case not zero will display 31 ROOM TEMPERATURE ADJUST BUTTONS and These multi purpose buttons are used to adjust the current room temperature set point in normal opera...

Page 6: ...ater temperature control In this mode heating will be activated as required by the water temperature set point The set point can be set manually through the schedule timer or weather dependent automat...

Page 7: ...ings 3 00 Low ambient temperature Lo_A low outdoor temperature 3 01 High ambient temperature Hi_A high outdoor temperature 3 02 Set point at low ambient temperature Lo_Ti the target outgoing water tem...

Page 8: ...atus defines whether the weather dependent domestic water heating is turned ON 1 or OFF 0 If enabled the storage set point will be set weather dependent In case of a higher ambient temperature e g dur...

Page 9: ...point for the domestic hot water storage temperature is reached It can also be stopped at any time by pushing the button NOTE If weather dependent domestic water heating is enabled b 02 the storage t...

Page 10: ...lf is done by the heater kit If there are no error conditions in leaving or returning water thermistors the heater kit can start to follow emergency operation Other operation modes Start up operation...

Page 11: ...lation is controlled by the schedule timer The actions programmed in the schedule timer will be executed automatically The schedule timer is enabled icon displayed or disabled icon not displayed by pr...

Page 12: ...ommand 13 00 and will remain active until the next programmed command 19 00 occurs So in order to know the actual setting one should consult the last programmed command It is clear that the last progr...

Page 13: ...water heating and quiet mode program depending on remote controller model 4 or 5 actions can be programmed per mode The same actions are repeated on a daily basis Take your time to enter all data accu...

Page 14: ...emperature 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the remote controller off to select automatic temperature calculation for leaving water...

Page 15: ...tions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted By pressing the button several times you return to previous steps in this procedur...

Page 16: ...actions except those with a higher action number than the one that is displayed E g when the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted D...

Page 17: ...ceed as follows 1 Press the button for a minimum of 5 seconds to enter FIELD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed t...

Page 18: ...A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1...

Page 19: ...storage temperature 70 45 75 1 C 04 Automatic maximum hot water tank storage temperature 70 55 75 1 C C Leaving water temperature limits 00 Installation related setting 80 37 80 1 C 01 Installation r...

Page 20: ...the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance with relevant local and national legislation...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P402192 1A 2015 04 Copyright 2015 Daikin...

Reviews: