background image

Operation manual

11

EKHBRD011~Y1

Indoor unit for air to water heat pump system and options

4P402192-1A – 2015.04

Operation example: Schedule timer based on temperature set
points.

When setback function is enabled, the setback operation will have
priority over the scheduled action in the schedule timer.

Operation example: Schedule timer based on ON/OFF instruction.

When setback function is enabled, the setback operation will have
priority over the scheduled action in the schedule timer if ON
instruction is active. If OFF instruction is active this will have priority
over the setback function. At any time the OFF instruction will have
the highest priority.

1

Schedule timer

2

Setback function

3

When both setback function and schedule timer are enabled

A

Setback function

t

Time

T

Temperature set point

Room temperature

Leaving water temperature

Method 2
[0-03]=0

Space heating based on ON/OFF instruction

During operation

When the schedule timer switches space heating OFF, 
the controller will be switched off (operation LED will stop 
working). Note that this has no influence on the domestic 
water heating.

When pushing 
the 

 button

The schedule timer for space heating will stop (when 
active at that moment) and will start again at the next 
scheduled ON function.
The "last" programmed command overrules the 
"preceding" programmed command and will remain 
active until the "next" programmed command occurs.

Example: imagine the actual time is 17:30 and actions 
are programmed at 13:00, 16:00 and 19:00. The "last" 
programmed command (16:00) overruled the 
"previous" programmed command (13:00) and will 
remain active until the "next" programmed command 
(19:00) occurs.

So in order to know the actual setting, one should consult 
the last programmed command. It is clear that the "last" 
programmed command may date from the day before. 
Refer to 

"Consulting programmed actions" on page 14

.

The controller will be switched off (operation LED will 
stop working).

However the schedule timer icon will stay displayed 
which means that the domestic heating stays enabled.

When pushing 
the  /  button

The schedule timer for space heating and domestic 
water heating along with the quiet mode will be stopped 
and will not start again.

The schedule timer icon will not be displayed anymore.

T

t

6:30

9:00

16:00

0:30

19

19

°

C

19

19

°

C

19

19

°

C

22

22

°

C

21

21

°

C

62

62

°

C

62

62

°

C

62

62

°

C

65

65

°

C

64

64

°

C

62

°

C

19

°

C

19

°

C

19

°

C

22

°

C

21

°

C

62

°

C

62

°

C

65

°

C

64

°

C

0:30

1

T

t

18

18

°

C

57

57

°

C

57

°

C

18

°

C

A

5:00

5:00

23:00

23:00

5:00

23:00

2

T

t

5:00

9:00

16:00

23:00

19

19

°

C

18

18

°

C

19

19

°

C

22

22

°

C

21

21

°

C

62

62

°

C

60

60

°

C

62

62

°

C

65

65

°

C

64

64

°

C

60

°

C

19

°

C

18

°

C

19

°

C

22

°

C

21

°

C

62

°

C

62

°

C

19

19

°

C

62

62

°

C

19

°

C

62

°

C

19

19

°

C

62

62

°

C

19

°

C

62

°

C

19

19

°

C

62

62

°

C

19

°

C

62

°

C

65

°

C

64

°

C

6:30

3

57

57

°

C

57

°

C

60

60

°

C

60

°

C

1

Schedule timer

2

Setback function

3

When both setback function and schedule timer are enabled

A

Setback function

B

ON/OFF instruction

t

Time

T

Temperature set point

Room temperature

Leaving water temperature

t

18

18

°

C

60

60

°

C

60

°

C

18

°

C

A

5:00

5:00

23:00

23:00

5:00

23:00

2

B

t

9:00

16:00

19

19

°

C

19

19

°

C

22

22

°

C

21

21

°

C

62

62

°

C

62

62

°

C

65

65

°

C

64

64

°

C

19

°

C

19

°

C

22

°

C

21

°

C

62

°

C

62

°

C

65

°

C

64

°

C

1

OFF

ON

ON

6:30

0:30

B

t

6:30

9:00

16:00

23:00

19

19

°

C

19

19

°

C

22

22

°

C

21

21

°

C

62

62

°

C

62

62

°

C

65

65

°

C

64

64

°

C

19

°

C

19

°

C

22

°

C

21

°

C

62

°

C

62

°

C

65

°

C

64

°

C

3

OFF

ON

ON

18

18

°

C

60

60

°

C

60

°

C

18

°

C

Summary of Contents for EKHBRD011ADV1

Page 1: ...OPERATION MANUAL EKHBRD011ADV1 EKHBRD014ADV1 EKHBRD016ADV1 EKHBRD011ADY1 EKHBRD014ADY1 EKHBRD016ADY1 Indoor unit for air to water heat pump system and options...

Page 2: ...y or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children sh...

Page 3: ...sh the button See Automatic storage on page 7 The icon will display Hot water will be produced at next scheduled action When water heat up starts the icon will be blinking 1 second interval Manual sto...

Page 4: ...installation purposes only 13 NOT AVAILABLE This icon is displayed whenever a non installed option is addressed or a function is not available A function not available can mean insufficient permissio...

Page 5: ...on as well as the shift value in case not zero will display 31 ROOM TEMPERATURE ADJUST BUTTONS and These multi purpose buttons are used to adjust the current room temperature set point in normal opera...

Page 6: ...ater temperature control In this mode heating will be activated as required by the water temperature set point The set point can be set manually through the schedule timer or weather dependent automat...

Page 7: ...ings 3 00 Low ambient temperature Lo_A low outdoor temperature 3 01 High ambient temperature Hi_A high outdoor temperature 3 02 Set point at low ambient temperature Lo_Ti the target outgoing water tem...

Page 8: ...atus defines whether the weather dependent domestic water heating is turned ON 1 or OFF 0 If enabled the storage set point will be set weather dependent In case of a higher ambient temperature e g dur...

Page 9: ...point for the domestic hot water storage temperature is reached It can also be stopped at any time by pushing the button NOTE If weather dependent domestic water heating is enabled b 02 the storage t...

Page 10: ...lf is done by the heater kit If there are no error conditions in leaving or returning water thermistors the heater kit can start to follow emergency operation Other operation modes Start up operation...

Page 11: ...lation is controlled by the schedule timer The actions programmed in the schedule timer will be executed automatically The schedule timer is enabled icon displayed or disabled icon not displayed by pr...

Page 12: ...ommand 13 00 and will remain active until the next programmed command 19 00 occurs So in order to know the actual setting one should consult the last programmed command It is clear that the last progr...

Page 13: ...water heating and quiet mode program depending on remote controller model 4 or 5 actions can be programmed per mode The same actions are repeated on a daily basis Take your time to enter all data accu...

Page 14: ...emperature 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the remote controller off to select automatic temperature calculation for leaving water...

Page 15: ...tions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted By pressing the button several times you return to previous steps in this procedur...

Page 16: ...actions except those with a higher action number than the one that is displayed E g when the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted D...

Page 17: ...ceed as follows 1 Press the button for a minimum of 5 seconds to enter FIELD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed t...

Page 18: ...A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1...

Page 19: ...storage temperature 70 45 75 1 C 04 Automatic maximum hot water tank storage temperature 70 55 75 1 C C Leaving water temperature limits 00 Installation related setting 80 37 80 1 C 01 Installation r...

Page 20: ...the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance with relevant local and national legislation...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P402192 1A 2015 04 Copyright 2015 Daikin...

Reviews: