EKHBRD011~Y1

Indoor unit for air to water heat pump system and options

4P402192-1A – 2015.04

Operation manual

4

24. DOMESTIC WATER HEATING BUTTON 

This button enables or disables the different domestic hot water
modes in combination with the schedule timer button.

This button is not used when the domestic hot water tank is not
installed.

25. WEATHER DEPENDENT SET POINT BUTTON 

This button enables or disables the weather dependent set point
function which is available in space heating operation.

If the controller is set to permission level 3 (refer to "Field
settings" in the installation manual), the weather dependent set
point button will not be operable.

26. INSPECTION/TEST OPERATION BUTTON 

This button is used for installation purposes and changing field
settings. Refer to 

"Field settings" on page 16

.

27. PROGRAMMING BUTTON 

This multi-purpose button is used to program the controller. The
function of the button depends on the actual status of the
controller or on previous actions carried out by the operator.

28. SCHEDULE TIMER BUTTON  /

The main function of this multi-purpose button is to
enable/disable the schedule timer.

The button is also used to set the clock and to program the
controller. The function of the button depends on the actual
status of the controller or on previous actions carried out by the
operator.

29. TIME ADJUST BUTTONS 

 and 

These multi-purpose buttons are used to adjust the clock, to
toggle between temperatures (water inlet/outlet temperature of
the indoor unit, outdoor ambient temperature, actual room
temperature and domestic hot water temperature) and in
schedule timer programming mode.

30. LEAVING WATER TEMPERATURE ADJUST BUTTONS

 and 

These buttons are used to adjust the leaving water temperature
set point in normal operation mode or in schedule timer
programming mode.

If the controller is set to permission level 3 (refer to "Field
settings" in the installation manual), the leaving water
temperature adjust button will not be operable.

In case the weather dependent set point operation is selected,
the unit has a floating set point. In this case, the 

 icon as well

as the shift value (in case not zero) will display.

31. ROOM TEMPERATURE ADJUST BUTTONS 

 and 

These multi-purpose buttons are used to adjust the current room
temperature set point in normal operation mode or in schedule
timer programming mode.

When changing the room temperature set point, the set point
value on the display will be flashing. After 5 seconds the display
will show to the actual room temperature.

32. QUIET MODE BUTTON 

This button enables or disables quiet mode.

If the controller is set to permission level 2 or 3 (refer to "Field
settings" in the installation manual), the quiet mode button will
not be operable.

33. The 

 button has no function.

Setting the clock

After initial installation, the user can set the clock and day of the week.

The remote controller is equipped with a schedule timer that enables
the user to schedule operations. Setting the clock and day of the
week is required to be able to use the schedule timer.

1

Hold down the 

 button for 5 seconds.

The clock read-out and the day of week indicator start flashing.

2

Use the 

 and 

 buttons to adjust the clock.

Each time the 

 or 

 button is pressed, the time will

increase/decrease by 1 minute. Keeping the 

 or 

button pressed will increase/decrease the time by 10 minutes.

3

Use the 

 or 

 button to adjust the day of the week.

Each time the 

 or 

 button is pressed the next or

previous day is displayed.

4

Press the   button to confirm the current set time and day of the
week.

To leave this procedure without saving, press the 

 button.

If no button is pressed for 5 minutes the clock and day of the
week will return to their previous setting.

NOTE

Remark that pushing the 

 button has no

influence on the domestic water heating.
Domestic water heating is only switched on or off
by means of the 

 button and/or disabling the

storage schedule timer.

NOTE

The clock needs to be set manually. Adjust the
setting when switching from summertime to
wintertime and vice versa.

If the controller is set to permission level 2 or 3
(refer to "Field settings" in the installation
manual), setting the clock will not be possible.

A power failure exceeding 1 hour will reset the
clock and the day of the week. The schedule timer
will continue operation, but with a disordered
clock. Therefor it will be needed to correct the
clock and the day of the week.

Summary of Contents for EKHBRD011ADV1

Page 1: ...OPERATION MANUAL EKHBRD011ADV1 EKHBRD014ADV1 EKHBRD016ADV1 EKHBRD011ADY1 EKHBRD014ADY1 EKHBRD016ADY1 Indoor unit for air to water heat pump system and options...

Page 2: ...y or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children sh...

Page 3: ...sh the button See Automatic storage on page 7 The icon will display Hot water will be produced at next scheduled action When water heat up starts the icon will be blinking 1 second interval Manual sto...

Page 4: ...installation purposes only 13 NOT AVAILABLE This icon is displayed whenever a non installed option is addressed or a function is not available A function not available can mean insufficient permissio...

Page 5: ...on as well as the shift value in case not zero will display 31 ROOM TEMPERATURE ADJUST BUTTONS and These multi purpose buttons are used to adjust the current room temperature set point in normal opera...

Page 6: ...ater temperature control In this mode heating will be activated as required by the water temperature set point The set point can be set manually through the schedule timer or weather dependent automat...

Page 7: ...ings 3 00 Low ambient temperature Lo_A low outdoor temperature 3 01 High ambient temperature Hi_A high outdoor temperature 3 02 Set point at low ambient temperature Lo_Ti the target outgoing water tem...

Page 8: ...atus defines whether the weather dependent domestic water heating is turned ON 1 or OFF 0 If enabled the storage set point will be set weather dependent In case of a higher ambient temperature e g dur...

Page 9: ...point for the domestic hot water storage temperature is reached It can also be stopped at any time by pushing the button NOTE If weather dependent domestic water heating is enabled b 02 the storage t...

Page 10: ...lf is done by the heater kit If there are no error conditions in leaving or returning water thermistors the heater kit can start to follow emergency operation Other operation modes Start up operation...

Page 11: ...lation is controlled by the schedule timer The actions programmed in the schedule timer will be executed automatically The schedule timer is enabled icon displayed or disabled icon not displayed by pr...

Page 12: ...ommand 13 00 and will remain active until the next programmed command 19 00 occurs So in order to know the actual setting one should consult the last programmed command It is clear that the last progr...

Page 13: ...water heating and quiet mode program depending on remote controller model 4 or 5 actions can be programmed per mode The same actions are repeated on a daily basis Take your time to enter all data accu...

Page 14: ...emperature 10 Use the and buttons to set the room temperature 11 Use the button to select to switch heating and the remote controller off to select automatic temperature calculation for leaving water...

Page 15: ...tions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted By pressing the button several times you return to previous steps in this procedur...

Page 16: ...actions except those with a higher action number than the one that is displayed E g when the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted D...

Page 17: ...ceed as follows 1 Press the button for a minimum of 5 seconds to enter FIELD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed t...

Page 18: ...A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1...

Page 19: ...storage temperature 70 45 75 1 C 04 Automatic maximum hot water tank storage temperature 70 55 75 1 C C Leaving water temperature limits 00 Installation related setting 80 37 80 1 C 01 Installation r...

Page 20: ...the system yourself the dismantling of the system treatment of the refrigerant of oil and other parts must be done by a qualified installer in accordance with relevant local and national legislation...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P402192 1A 2015 04 Copyright 2015 Daikin...