14 Technical data
Installer reference guide
83
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1D – 2016.02
Domestic hot water
25
20
15
5
10
0
–5
–10
0
10
20
30
40
4D083082-1B
A (°C)
B (°C)
60
70
50
A
Entering brine temperature
B
Leaving condenser water temperature
Only backup heater operation.
Heat pump operation
Protect against freezing by adding anti-freeze to brine side. See also remark.
Remark:
By default settings, the unit will allow operation with
entering brine temperatures to –5°C. As a result, the brine freezing
temperature may not be higher than –15°C! For water – ethanol
mixtures this corresponds to 29% ethanol (by mass), for water –
propylene glycol mixtures this corresponds to 40% propylene glycol
(by volume).
If the freezing temperature of the medium is higher than –15°C, then
protection level of unit MUST be increased by field setting.
Refer to the installation manual and/or installer reference guide for
instructions how to set a different freeze temperature of the medium
(Tf) in the controller.
The unit will NOT operate at an entering brine temperature lower
than Tf+10K.
Tf = changeable between 0°C and –15°C.