5 Application guidelines
Installer reference guide
10
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1D – 2016.02
▪ The under floor heating or radiators are directly connected to the
indoor unit.
▪ The room temperature is controlled by the wireless external room
thermostat (optional equipment EKRTR1).
Configuration
Setting
Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main
zone:
▪ #: [A.2.2.4]
▪ Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition.
Benefits
▪
Wireless.
The Daikin external room thermostat is available in a
wireless version.
▪
Efficiency.
Although the external room thermostat only sends ON/
OFF signals, it is specifically designed for the heat pump system.
Heat pump convectors
Setup
B
A
a
A
Main leaving water temperature zone
B
One single room
a
Remote controller of the heat pump convectors
▪ The under floor heating or radiators are directly connected to the
indoor unit.
▪ The desired room temperature is set via the remote controller of
the heat pump convectors.
▪ The space heating demand signal is sent to one digital input on
the indoor unit (X2M/1 and X2M/4).
INFORMATION
When using multiple heat pump convectors, make sure
each one receives the infrared signal from the remote
controller of the heat pump convectors.
Configuration
Setting
Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main
zone:
▪ #: [A.2.2.4]
▪ Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heat pump convector can only
send a thermo ON/OFF
condition.
Benefits
▪
Efficiency.
Optimal energy efficiency because of the interlink
function.
▪
Stylish.
5.2.2
Multiple rooms – One LWT zone
If only one leaving water temperature zone is needed because the
design leaving water temperature of all heat emitters is the same,
you do NOT need a mixing valve station (cost effective).
Example:
If the heat pump system is used to heat up one floor
where all the rooms have the same heat emitters.
Under floor heating or radiators – Thermostatic
valves
If you are heating up rooms with under floor heating or radiators, a
very common way is to control the temperature of the main room by
using a thermostat (this can either be the user interface or an
external room thermostat), while the other rooms are controlled by
so-called thermostatic valves, which open or close depending on the
room temperature.
Setup
T
B
C
A
a
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
User interface
▪ The under floor heating of the main room is directly connected to
the indoor unit.
▪ The room temperature of the main room is controlled by the user
interface used as thermostat.