5 Application guidelines
Installer reference guide
9
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1D – 2016.02
▪ Setting up an auxiliary heat source for space heating
▪ Setting up the domestic hot water tank
▪ Setting up the energy metering
▪ Setting up the power consumption
▪ Setting up an external temperature sensor
5.2
Setting up the space heating
system
The Daikin heat pump system supplies leaving water to heat
emitters in one or more rooms.
Because the system offers a wide flexibility to control the
temperature in each room, you need to answer the following
questions first:
▪ How many rooms are heated by the Daikin heat pump system?
▪ Which heat emitter types are used in each room and what is their
design leaving water temperature?
Once the space heating requirements are clear, Daikin recommends
to follow the setup guidelines below.
NOTICE
If an external room thermostat is used, the external room
thermostat will control the room frost protection. However,
the room frost protection is only possible if the leaving
water temperature control on the unit's user interface is
turned ON.
INFORMATION
In case an external room thermostat is used and room frost
protection needs to be guaranteed in all conditions, then
you have to set auto emergency [A.5.1.2] to 1.
5.2.1
Single room
Under floor heating or radiators – Wired room
thermostat
Setup
B
A
a
A
Main leaving water temperature zone
B
One single room
a
User interface used as room thermostat
▪ The under floor heating or radiators are directly connected to the
indoor unit.
▪ The room temperature is controlled by the user interface, which is
used as room thermostat. Possible installations:
▪ User interface (standard equipment) installed in the room and
used as room thermostat
▪ User interface (standard equipment) installed at the indoor unit
and used for control close to the indoor unit + user interface
(optional equipment EKRUCBL*) installed in the room and used
as room thermostat
Configuration
Setting
Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
Benefits
▪
Cost effective.
You do NOT need an additional external room
thermostat.
▪
Highest comfort and efficiency
. The smart room thermostat
functionality can decrease or increase the desired leaving water
temperature based on the actual room temperature (modulation).
This results in:
▪ Stable room temperature matching the desired temperature
(higher comfort)
▪ Less ON/OFF cycles (more quiet, higher comfort and higher
efficiency)
▪ Lowest possible leaving water temperature (higher efficiency)
▪
Easy
. You can easily set the desired room temperature via the
user interface:
▪ For your daily needs, you can use preset values and schedules.
▪ To deviate from your daily needs, you can temporarily overrule
the preset values and schedules, use the holiday mode…
Under floor heating or radiators – Wireless room
thermostat
Setup
B
A
b
a
A
Main leaving water temperature zone
B
One single room
a
Receiver for wireless external room thermostat
b
Wireless external room thermostat