5 Application guidelines
Installer reference guide
12
EGSQH10S18AA9W
Daikin Altherma ground source heat pump
4P351748-1D – 2016.02
▪
Comfort.
You can set the desired room temperature, including
schedules, for each room via the remote controller of the
heat pump convectors.
Combination: Under floor h Heat pump
convectors
Setup
b
B
C
A
a
M1
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
External room thermostat
b
Remote controller of the heat pump convectors
▪ For each room with heat pump convectors: The heat pump
convectors are directly connected to the indoor unit.
▪ For each room with under floor heating: A shut-off valve (field
supply) is installed before the under floor heating. It prevents hot
water supply when the room has no heating demand.
▪ For each room with heat pump convectors: The desired room
temperature is set via the remote controller of the heat pump
convectors.
▪ For each room with under floor heating: The desired room
temperature is set via the external room thermostat (wired or
wireless).
INFORMATION
To increase comfort and performance, Daikin recommends
to install the valve kit option EKVKHPC on each heat pump
convector.
Configuration
Setting
Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
0 (LWT control): Unit operation is
decided based on the leaving
water temperature.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
5.2.3
Multiple rooms – Two LWT zones
If the heat emitters selected for each room are designed for different
leaving water temperatures, you can use different leaving water
temperature zones (maximum 2).
In this document:
▪ Main zone = Zone with the lowest design temperature
▪ Additional zone = The other zone
CAUTION
When there is more than one leaving water zone, you must
ALWAYS install a mixing valve station in the main zone to
decrease (in heating) the leaving water temperature when
the additional zone has demand.
Typical example:
Room (zone)
Heat emitters: Design
temperature
Living room (main zone)
Under floor heating: 35°C
Bed rooms (additional zone)
Heat pump convectors: 45°C
Setup
B
A
a
a
C
E
D
b
c
d
A
Additional leaving water temperature zone
B
Room 1
C
Room 2
D
Main leaving water temperature zone
E
Room 3
a
Remote controller of the heat pump convectors
b
User interface
c
Mixing valve station
d
Pressure regulating valve
INFORMATION
A pressure regulating valve should be implemented before
the mixing valve station. This is to guarantee the correct
water flow balance between the main leaving water
temperature zone and the additional leaving water
temperature zone in relation to the required capacity of
both water temperature zones.
▪ For the main zone:
▪ A mixing valve station is installed before the under floor heating.
▪ The pump of the mixing valve station is controlled by the ON/
OFF signal on the indoor unit (X2M/5 and X2M/7; normal closed
shut-off valve output).
▪ The room temperature is controlled by the user interface, which
is used as room thermostat.