68
1.2 Wiring Adaptor for Electrical Appendices (2) <KRP4AA51 / KRP4AA52 / KRP4AA53 / KRP4A54>
Adaptor
ED721208
5. Temperature setting input
Temperature setting corresponds to resistance values in the range of 0 to 135
Ω
.
Their relationship is as shown below.
Relation between the setting temperature and the resistance are as follows.
Note:
The value of resistance includes the resistance of wiring.
The setting temperature is limited within the setting range of indoor unit. If you set the temperature outside of the
range by the adaptor, it controls at the nearest setting range.
6. Setting of control mode selector switch (RS1)
Setting
temperature (°C)
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
Resistance (
Ω
)
0.0
~
3.4
5.0
~
11.6
13.8
~
20.0
22.4
~
28.4
31.0
~
36.4
39.4
~
44.8
48.2
~
52.8
56.6
~
61.2
65.2
~
69.4
73.8
~
77.8
82.4
~
85.8
91.0
~
94.0
99.4
~
102.2
108.6
~
110.4
117.2
~
119.2
125.8
~
127.4
134.2
~
140.0
CONTROL
MODE
Position
RS1
Function
Input A close
Input A open
Input B close
(Input A is ignored)
Operation
or not of
indoor
unit
From Remote
controller
Operation
or not of
indoor
unit
From Remote
controller
Operation
or not of
indoor
unit
From
Remote
controller
0
Input Ignored
—
—
1
Remote Control Rejection
ON
Rejection
OFF
Rejection
Forced
OFF
Rejection
2
Central Priority
ON
Acceptable
3
Remote controller Acceptable/
Rejection
ON
Only Stop
acceptable
4
Remote controller acceptance /
rejection, OFF
Permit
Acceptable
Position
Function
Input A close/open
(pulse input)
Constant Input B close
( Constant input) (Input A is ignored)
Operation
or not of
indoor
unit
From Remote controller
Operation or not of
indoor unit
From Remote
controller
5
Remote Control Rejection
ON /
OFF
Rejection
Forced OFF at close
Rejection
6
Last command Priority
ON /
OFF
Acceptable
KRP4A54
C: 1PA59890F
1
Summary of Contents for DCM601A51
Page 5: ...1 ED721208 1 Part 1 intelligent Touch Manager ...
Page 6: ...2 intelligent Touch Manager ED721208 ...
Page 7: ...3 ED721208 intelligent Touch Manager 1 ...
Page 8: ...4 intelligent Touch Manager ED721208 ...
Page 9: ...5 ED721208 intelligent Touch Manager 1 ...
Page 10: ...6 intelligent Touch Manager ED721208 ...
Page 11: ...7 ED721208 intelligent Touch Manager 1 ...
Page 12: ...8 intelligent Touch Manager ED721208 ...
Page 13: ...9 ED721208 intelligent Touch Manager 1 ...
Page 14: ...10 intelligent Touch Manager ED721208 ...
Page 15: ...11 ED721208 intelligent Touch Manager 1 ...
Page 16: ...12 intelligent Touch Manager ED721208 ...
Page 17: ...13 ED721208 intelligent Touch Manager 1 ...
Page 18: ...14 intelligent Touch Manager ED721208 ...
Page 40: ...36 7 2 Error Code on Initial Setting and Wiring Troubles Fundamental of DIII NET ED721208 ...
Page 403: ......