2.3 Connection Method
19
ED721208
Fundamental of DIII-NET
2
2.3.2 Incorrect Wiring Example
Caution:
Communication problems could occur.
[Incorrect Wiring 1]
Series wiring method only should be used.
Caution:
As shown above, the centralized control equipment should be connected to the wiring between the outdoor units,
wherever possible. (If connected to the control wiring between indoor unit and the outdoor unit, it may not be able to
control the units even on the normal circuit if the circuit connected to the centralized control equipment is out of order.)
Centralized
Control
Equipment
Summary of Contents for DCM601A51
Page 5: ...1 ED721208 1 Part 1 intelligent Touch Manager ...
Page 6: ...2 intelligent Touch Manager ED721208 ...
Page 7: ...3 ED721208 intelligent Touch Manager 1 ...
Page 8: ...4 intelligent Touch Manager ED721208 ...
Page 9: ...5 ED721208 intelligent Touch Manager 1 ...
Page 10: ...6 intelligent Touch Manager ED721208 ...
Page 11: ...7 ED721208 intelligent Touch Manager 1 ...
Page 12: ...8 intelligent Touch Manager ED721208 ...
Page 13: ...9 ED721208 intelligent Touch Manager 1 ...
Page 14: ...10 intelligent Touch Manager ED721208 ...
Page 15: ...11 ED721208 intelligent Touch Manager 1 ...
Page 16: ...12 intelligent Touch Manager ED721208 ...
Page 17: ...13 ED721208 intelligent Touch Manager 1 ...
Page 18: ...14 intelligent Touch Manager ED721208 ...
Page 40: ...36 7 2 Error Code on Initial Setting and Wiring Troubles Fundamental of DIII NET ED721208 ...
Page 403: ......