22
2.4 Wiring Example
Fundamental of DIII-NET
ED721208
2.4
Wiring Example
Example of Control Wiring
Be sure to connect the wiring of the centralized control equipment to control wiring between outdoor units.
When wiring connections are made between indoor and outdoor units, there may be cases where control over normal
systems may become impossible if one of the connected systems should happen to fail.
Be sure to prevent the connection of three wires on the same terminal.
<Pattern 1>
The advantages when the centralized control equipment are connected to A.
If the centralized control equipment are connected to A, it is still possible to have a centralized control, even if the
power supply of other circuit connected to the centralized control equipment is shut off. (even if the power is shut off
due to long vacation etc.)
Caution:
+
1. It is not recommended to connect the centralized control equipment on (
α
1), (
α
2), (
α
3), as there is a risk to loose
control over all systems.
Ex.; If intelligent Touch Manager (iTM) is connected on (
α
1), and System1 shut down, control over System2 and
System3 units is lost.
Control wiring between indoor unit
and outdoor unit
Transmission wiring for
remote controller
Control wiring
between outdoor
units
Outdoor unit
Outdoor unit
Outdoor unit
It is possible to
operate without
remote controller.
(when the central
remote controller is
employed.)
Possible to control group operation
of up to 16 indoor units.
Group control is set by the
automatic address setting.
Combined control of
Heat reclaim
ventilator is possible
Independent operation
of Heat reclaim
ventilator is possible
Also possible to control
the operation of the air-
conditioner other than
VRV system.
(Wiring adaptor for
other air-conditioner is
required.)
Possible to control the
operation of the SkyAir
(Interface adaptor for
SkyAir series is required.)
SkyAir
Unified ON/OFF Controller
(DCS301BA61)
Up to 8 controllers can be
connected
intelligent Touch Manager
(DCM601A51)
When all the centralized
control equipment is located at
one place.
A
A
(
α
1)
(
α
2)
(
α
3)
System1
System2
System3
Summary of Contents for DCM601A51
Page 5: ...1 ED721208 1 Part 1 intelligent Touch Manager ...
Page 6: ...2 intelligent Touch Manager ED721208 ...
Page 7: ...3 ED721208 intelligent Touch Manager 1 ...
Page 8: ...4 intelligent Touch Manager ED721208 ...
Page 9: ...5 ED721208 intelligent Touch Manager 1 ...
Page 10: ...6 intelligent Touch Manager ED721208 ...
Page 11: ...7 ED721208 intelligent Touch Manager 1 ...
Page 12: ...8 intelligent Touch Manager ED721208 ...
Page 13: ...9 ED721208 intelligent Touch Manager 1 ...
Page 14: ...10 intelligent Touch Manager ED721208 ...
Page 15: ...11 ED721208 intelligent Touch Manager 1 ...
Page 16: ...12 intelligent Touch Manager ED721208 ...
Page 17: ...13 ED721208 intelligent Touch Manager 1 ...
Page 18: ...14 intelligent Touch Manager ED721208 ...
Page 40: ...36 7 2 Error Code on Initial Setting and Wiring Troubles Fundamental of DIII NET ED721208 ...