2.3 Connection Method
21
ED721208
Fundamental of DIII-NET
2
[Incorrect Wiring 4]
[Incorrect Wiring 5]
[Incorrect Wiring 6]
IN/OUT
F1 F2
OUT/OUT
F1 F2
IN/OUT
F1 F2
OUT/OUT
F1 F2
Centralized
Control
Equipment
VRV Outdoor unit
VRV Indoor unit
F1 F2
F1 F2
Connect the centralized
control equipment
to the outdoor-outdoor
connection.
Connecting directly in the middle of indoor F1 or F2
line, without using F1 or F2 terminal, is prohibited.
Connect outdoor units without branch connection.
Indoor-outdoor
connection
Connect indoor units and outdoor units without branch connection.
Outdoor-outdoor
connection
Centralized
Control
Equipment
missmatch
VRV Outdoor unit
Refrigerant piping
VRV Indoor unit
IN/OUT
F1 F2
OUT/OUT
F1 F2
IN/OUT
F1 F2
OUT/OUT
F1 F2
F1 F2
F1 F2
Main
System A
2-00
~
2-03
2-00
2-01
2-02
2-03
1-00
1-01
1-02
1-03
Sub
Sub
NO!
Wiring this part is prohibited.
2-00
~
2-03
1-00
~
1-03
System B
Conflict
IN/OUT
F1 F2
OUT/OUT
F1 F2
IN/OUT
F1 F2
OUT/OUT
F1 F2
Summary of Contents for DCM601A51
Page 5: ...1 ED721208 1 Part 1 intelligent Touch Manager ...
Page 6: ...2 intelligent Touch Manager ED721208 ...
Page 7: ...3 ED721208 intelligent Touch Manager 1 ...
Page 8: ...4 intelligent Touch Manager ED721208 ...
Page 9: ...5 ED721208 intelligent Touch Manager 1 ...
Page 10: ...6 intelligent Touch Manager ED721208 ...
Page 11: ...7 ED721208 intelligent Touch Manager 1 ...
Page 12: ...8 intelligent Touch Manager ED721208 ...
Page 13: ...9 ED721208 intelligent Touch Manager 1 ...
Page 14: ...10 intelligent Touch Manager ED721208 ...
Page 15: ...11 ED721208 intelligent Touch Manager 1 ...
Page 16: ...12 intelligent Touch Manager ED721208 ...
Page 17: ...13 ED721208 intelligent Touch Manager 1 ...
Page 18: ...14 intelligent Touch Manager ED721208 ...
Page 40: ...36 7 2 Error Code on Initial Setting and Wiring Troubles Fundamental of DIII NET ED721208 ...
Page 403: ......