18
2.3 Connection Method
Fundamental of DIII-NET
ED721208
2.3
Connection Method
2.3.1 Correct Wiring
Series wiring method only should be used.
[Example]
Caution:
Be sure to have indoor-outdoor control wiring and that of refrigerant system coincide.
Crossed wiring will cause malfunctioning.
Centralized
Control
Equipment
VRV Outdoor unit
VRV Indoor unit
Connect the centralized control equipment to the outdoor-outdoor connection.
Connect outdoor units without branch connection.
Indoor-outdoor
connection
Connect indoor units and outdoor units without branch connection.
Outdoor-outdoor
connection
IN/OUT
F1 F2
OUT/OUT
F1 F2
IN/OUT
F1 F2
IN/OUT
F1 F2
OUT/OUT
F1 F2
OUT/OUT
F1 F2
Summary of Contents for DCM601A51
Page 5: ...1 ED721208 1 Part 1 intelligent Touch Manager ...
Page 6: ...2 intelligent Touch Manager ED721208 ...
Page 7: ...3 ED721208 intelligent Touch Manager 1 ...
Page 8: ...4 intelligent Touch Manager ED721208 ...
Page 9: ...5 ED721208 intelligent Touch Manager 1 ...
Page 10: ...6 intelligent Touch Manager ED721208 ...
Page 11: ...7 ED721208 intelligent Touch Manager 1 ...
Page 12: ...8 intelligent Touch Manager ED721208 ...
Page 13: ...9 ED721208 intelligent Touch Manager 1 ...
Page 14: ...10 intelligent Touch Manager ED721208 ...
Page 15: ...11 ED721208 intelligent Touch Manager 1 ...
Page 16: ...12 intelligent Touch Manager ED721208 ...
Page 17: ...13 ED721208 intelligent Touch Manager 1 ...
Page 18: ...14 intelligent Touch Manager ED721208 ...
Page 40: ...36 7 2 Error Code on Initial Setting and Wiring Troubles Fundamental of DIII NET ED721208 ...
Page 403: ......