background image

Commissioning Manual

intelligent Touch Manager

Model

DCM601A51

MONITOR

CPU ALIVE

SLAVE

MASTER

BACKUP

LAN SW

SERVICE LAN

FRONT BACK

D

 

MASTER

ON

OFF

RESET

LAN LINK D

 

MONITOR

Summary of Contents for DCM601A51

Page 1: ...Commissioning Manual intelligent Touch Manager Model DCM601A51 MONITOR CPU ALIVE SLAVE MASTER BACKUP LAN SW SERVICE LAN FRONT BACK D MASTER ON OFF RESET LAN LINK D MONITOR...

Page 2: ...Regist 13 Registering a management point with the iTM unit 14 Detailed Mgmt Point Attributes screen and button descriptions 21 Registering management points using a CSV file 33 4 2 Other Setting 38 4...

Page 3: ...e Leakage Check results to a CSV file 77 Conflict with other controls 79 Failure mode 81 Optional Functions 84 5 Service Settings 84 5 1 Activation 84 Acquiring the Activation key 84 Entering the Acti...

Page 4: ...ent 108 iTM integrator Explanation 109 7 iTM integrator 109 7 1 Basic Setup 109 7 2 iTM integrator Service Settings 114 Service Settings Tab Menu List Screen 115 Controller Access Setup 116 Appendix 1...

Page 5: ...p to 7 D3net port Up to 64 groups LAN port USB port D3net ROUTER Web Remote Management Web Remote Management Port 1 4 Port 1 Port 2 4 HUB SWITCH ROUTER Emergency Stop signal input Power meter pulse in...

Page 6: ...ation Check the equipment to connect to DIII NET Allocate the Group Address Acquire the upgrade data 4 8 Upgrade Acquiring the Activation key When necessary 5 1 Activation Acquiring the Activation key...

Page 7: ...4 7 Pre engineering Create the Layout View Layout View creation tool When necessary Commissioning Manual Supplementary Volume Layout View Creation Tool EM11A024 Acquiring the Activation key When nece...

Page 8: ...ttings tab which is normally hidden is displayed on the Menu List Also special buttons available only in SE Mode are displayed on the tabs The following describes how to log into the SE Mode 1 Display...

Page 9: ...gent Touch Manager 8 Furthermore if the screen is locked entering the service password instead of the administrator password after carrying out the special operation indicated below allows you to unlo...

Page 10: ...dinated and the local time This function allows you to con gure or cancel the cooling heating selection right This function allows you to delete the history data This tool allows you to precon gure ne...

Page 11: ...The air conditioner icons to be displayed on the Standard View screen are also set up automatically Automatic registration is supported only for indoor units and Ventilator NOTE 2 Mgmt Point Data Reg...

Page 12: ...es Disables Setpoint Restriction depending on whether an upper central unit is installed or not NOTE 9 Changeover Option Enables Disables the Changeover Option for an air conditioner 10 Layout Setup O...

Page 13: ...igent Touch Manager 12 3 3 System Settings Tab 2 1 3 1 Network Sets up the network IP addresses as well as the Web Servers 2 Web Access Users Sets up Web users for Web Remote Management 3 Backup Allow...

Page 14: ...after installing iTM When installing iTM after creating management point data When creating management point data using pre engineering tool and loading the management point data to an installed iTM...

Page 15: ...that can be registered but have not yet been registered with it Log into SE Mode from the Menu List screen and display the Service Settings tab see page 7 Touch the Mgmt Pnt Data Regist button on the...

Page 16: ...or air conditioners 7 8 6 Touching the Refresh button 6 updates the Search Result List 7 to its most recent status Selecting a management point to register and touching the Add button adds it to the R...

Page 17: ...ter screen The Add and Add ALL buttons are grayed out when the upper limit of registration has been reached and thus no more management points can be registered NOTE 2 Manually registering management...

Page 18: ...int type and touch the OK button to save and return to Management Point Types screen Remark External Ao or External Pi are not supported by this model When finished touch the OK button to display the...

Page 19: ...11 12 Touching the Delete button 10 deletes the management point selected in the list Touching the Edit button 11 displays the Mng Point Attributes screen for editing the management point selected in...

Page 20: ...of outdoor management points Outdoor Unit Mgmt points exceeded Excess of total number of Internal Pi management points Internal Pi Mgmt point exceeded DIII Duplicated D3 addresses D3 address duplicat...

Page 21: ...estart iTM to reflect the settings 14 When finished touch the OK button 14 A settings data check is carried out and the Information check screen displayed if errors are found If no problems are found...

Page 22: ...ibutes screen vary depending on the selected management point type Set up by switching the displayed tabs as necessary Common 1 Tab Sets common items for a management point Displayed items vary depend...

Page 23: ...ield Address combo box Sets up the port number and address to which the management point belongs For the port number touch the Modify button and enter it in the Numerical Input dialog that appears For...

Page 24: ...t be used 16 Detailed Type field Displays the detailed management point type However you cannot modify it here 17 Mgmt Pt ID field Displays the management point ID automatically allocated by the syste...

Page 25: ...er D3Dio External Dio 22 21 21 Prohibit Manual Operation check box Select the check box when prohibiting manual operation from the iTM 22 Address ACNSS address text field Sets up the ACNSS address Tou...

Page 26: ...onitoring levels Monitor or Monitor History by using the radio button Ventilator Tab Sets up the Ventilator 23 24 25 23 Ventilation Mode check box Select the check box when setting up Fresh Up and or...

Page 27: ...rom Normal and Equipment error input 28 Error input masking time after start signal radio button Select an Error Mask Time after operation input from 10 and 30 seconds Start up error occurs if the ext...

Page 28: ...pulse value Displayed items vary depending on the management point type Pi 35 36 37 38 Internal Pi 37 38 39 40 35 Pulse Amount text field Sets up the pulse value Touch the Modify button and enter the...

Page 29: ...01 For the Internal Pi the power ratio is fixed to 0 1 39 Coeff a text field Sets up the coefficient a Touch the Modify button and enter the value in the Numerical Input dialog that appears You can e...

Page 30: ...d Sets up the unit Touch the Modify button and enter the value in the Text Input dialog that appears The number of characters you can enter is 0 to 8 irrespective of single or double byte 42 Hysteresi...

Page 31: ...istor or Other The unit type cannot be configured when Other is selected in Analog Type 45 Selecting Thermistor sets the Minimum value and Maximum value text fields 47 to 512 0 and 512 0 or 890 and 95...

Page 32: ...512 0 0 0 2 0 1 0 to 922 0 2 1 Lower limit 512 0 to 512 0 0 0 2 0 1 890 to 954 32 2 1 Upper limit 512 0 to 512 0 0 0 2 0 1 890 to 954 32 2 1 BACnet Ao Analog value Min of op 512 0 to 512 0 0 0 0 1 89...

Page 33: ...creen Sets up the reference for the Internal Ai Touch the Ref button on the Analog2 tab to display the Analog Point Selection screen 49 50 49 is the list of management points with analog value 50 is t...

Page 34: ...ft Excel and the like Log into SE Mode from the Menu List screen and display the Service Settings tab see page 7 Touch the Mgmt Point Data Register button on the Service Settings tab to display the ma...

Page 35: ...u List screen and display the Service Settings tab see page 7 Touch the Mgmt Point Data Register button on the Service Settings tab to display the main Mgmt Point Data Register screen 52 Connect the U...

Page 36: ...ng data has been loaded without any problem the merge results appear The Display Merge Results screen consists of the tabs Add Modify Modification Failed and No change After checking the list on each...

Page 37: ...nal 1 to 30 5 5 5 6 6 5 6 6 5 ADDRESS1 Upper level address group D3 1 to 4 External 1 to 120 Internal Pi 1 to 127 Outdoor unit 1 to 127 Main unit 1 to 4 2 to 4 for Port 1 6 6 6 7 7 6 7 7 6 ADDRESS2 Lo...

Page 38: ...r double byte For Internal Ai Set to C or F depending on the System Settings if any reference management point exists Set to if no reference management point exists For other management points Set to...

Page 39: ...hether to recognize the Warning from a management point as an error and indicate it via icon and history Also Enables Disables the Dry operation mode 1 Log into SE Mode from the Menu List screen and d...

Page 40: ...creen and display the Service Settings tab see page 7 Touch the DIII NET Engineering button on the Service Settings tab to display the DIII NET Engineering screen see page 10 1 2 3 4 5 2 Set Main or S...

Page 41: ...for use in LONWORKS Main CRC 1 Central Remote Controller iTM iTM plus adaptor Sub CRC 1 Main On Off 1 ON OFF Controller Sub On Off 1 Main On Off 2 ON OFF Controller Sub On Off 2 Main On Off 3 ON OFF...

Page 42: ...tab to display the Time Zone Setting screen see page 10 1 2 Select the time zone in the Time Zone area 1 Touching the OK button displays a confirmation dialog Touch the Yes button to commit and close...

Page 43: ...ntent displayed in the Changeover Option column and its meaning 2 Comm Err Group address of the connected unit with communication error N A A group address not registered as a management point Mainten...

Page 44: ...d enter the start date in the Time Input dialog box that appears Touch the OK button to commit the start date and close the dialog The start date is displayed in the From field 2 To set the end date t...

Page 45: ...t iTM system Settings Auto accumulated data 2 5 Data load to iTM USB memory 4 2 Layout settings output 4 1 Restore data output 4 Property data output Layout settings HW speci c info Installer program...

Page 46: ...operty Data edit Layout View edit Scenario 3 Restore with existing property s backup data Not applicable to iTM integrator Scenario 4 Implementation of new functions due to existing property s upgrade...

Page 47: ...ol OS Windows XP Professional SP3 32 bit Windows VISTA Business SP2 32 bit Windows 7 Professional SP1 32 bit 64bit CPU Equivalent to Intel Core 2 Duo 1 2 GHz or higher Memory 2 GB or more Free HDD spa...

Page 48: ...1 DCM601A51 intelligent Touch Manager 47 1 2 On the login screen that appears enter the password and click the Login button 1 The iTM Pre engineering tool main screen appears if the correct password h...

Page 49: ...ialog 3 4 5 Create New Folder dialog 2 Select the location to create the new property s folder in 3 Clicking the Make New Folder button 4 creates a new folder directly under the folder selected in 3 C...

Page 50: ...and files within the folder NOTE 6 Main screen 3 Click the Edit Data button 6 to start up the iTM demo version for PC 7 Screen of demo version for PC The demo version for PC allows you to make simila...

Page 51: ...ppears 10 9 Select the drive in the Drive combo box 9 Select the content to output using the Output Data radio button 10 Click the OK button A conformation dialog appears indicating that you are about...

Page 52: ...e USB memory to iTM to restore For details see 4 10 Installation Layout Setup data only is available when the Layout option is enabled and saves only the Layout Setup data to the USB memory For the me...

Page 53: ...the iTM unit to a USB memory For details see 4 9 Backup 2 Copy data backed up in the USB memory folder name Backup_MAC address_year month day_ hour minute second to a PC Start up the Pre engineering...

Page 54: ...n for PC to restore data output to USB and iTM restore are the same as steps 3 to 5 of the procedure for Scenario 1 Installation to new property The Layout Setup data backup and restore procedures are...

Page 55: ...ch you are creating the restore data and click the OK button to close the screen 2 The restore data in the selected folder is output to a USB memory The steps up to the output to USB and iTM restore a...

Page 56: ...een For details see page 46 3 Edit the settings data using the upgraded Pre engineering tool The steps up to the output of the edited data to USB and iTM restore are the same as steps 4 and 5 of the p...

Page 57: ...troubleshooting and the like Data to be backed up is as follows iTM system file Settings data of each function Automatically accumulated data such as Energy Navigator s time tone trend data and histor...

Page 58: ...mplete an information dialog appears Touch the Close button to close the screen and remove the USB memory All the folders and files in the USB memory will be deleted when the backup begin One folder w...

Page 59: ...e iTM unit while pressing the MONITOR button provided on it Keep the MONITOR button depressed until the following screen appears and then release it To restart press the RESET switch on the front pane...

Page 60: ...and MAC addresses in the USB memory are compared with the version and MAC addresses on the iTM The information displayed on the installation tool screen is as follows 2 Name 3 Version of the installe...

Page 61: ...tion tool screen is greyed out and cannot be clicked NOTE 4 11 Contact Info Sets up contact information for inquiries regarding the system 1 Log into SE Mode from the Menu List screen and display the...

Page 62: ...ual EM11A021 DCM601A51 intelligent Touch Manager 61 3 The registered contact information can be checked on the Contact tab of the Information screen accessible from the Standard View screen See User s...

Page 63: ...or Setup screen see page 10 1 2 Select the desired outdoor unit from the list and touch the 1 Type button When the input dialogue is displayed input the type The type depends on the model of the outdo...

Page 64: ...name Type 36 RXYQ32M7W1B 1 37 RXYQ34M7W1B 1 38 RXYQ36M7W1B 1 39 RXYQ38M7W1B 1 40 RXYQ40M7W1B 1 41 RXYQ42M7W1B 1 42 RXYQ44M7W1B 1 43 RXYQ46M7W1B 1 44 RXYQ48M7W1B 1 45 RX10MTL 1 46 RX10MTLE 1 47 RX10MY1...

Page 65: ...RXY40MY1E 1 271 RXY40MYL 1 272 RXY40MYLE 1 273 RXY42MTL 1 274 RXY42MTLE 1 No Model name Type 275 RXY42MY1 1 276 RXY42MY1E 1 277 RXY42MYL 1 278 RXY42MYLE 1 279 RXY44MTL 1 280 RXY44MTLE 1 281 RXY44MY1 1...

Page 66: ...Q5M9W1B 1 536 RXYQ8M9W1B 1 537 RXYQ10M9W1B 1 538 RXYQ12M9W1B 1 539 RXYQ14M9W1B 1 540 RXYQ16M9W1B 1 541 RXYQ18M9W1B 1 542 RXYQ20M9W1B 1 No Model name Type 543 RXYQ22M9W1B 1 544 RXYQ24M9W1B 1 545 RXYQ26...

Page 67: ...6 3 806 RXQ32PY16 3 807 RXQ34PY16 3 808 RXQ36PY16 3 809 RXQ38PY16 3 810 RXQ40PY16 3 No Model name Type 811 RXQ42PY16 3 812 RXQ44PY16 3 813 RXQ46PY16 3 814 RXQ48PY16 3 815 RXQ50PY16 3 816 RXQ52PY16 3 8...

Page 68: ...Q16P9W1B 3 1075 RXYHQ18P9W1B 3 1076 RXYHQ20P9W1B 3 1077 RXYHQ22P9W1B 3 1078 RXYHQ24P9W1B 3 No Model name Type 1079 RXYHQ26P9W1B 3 1080 RXYHQ28P9W1B 3 1081 RXYHQ30P9W1B 3 1082 RXYHQ32P9W1B 3 1083 RXYHQ...

Page 69: ...1 1225 RZQ18PVJU 3 1226 RZQ24PVJU 3 1227 RZQ30PVJU 3 1228 RQYQ140P 3 1229 RQYQ180P 3 1230 RQCYQ280P 3 1231 RQCYQ360P 3 1232 RQCYQ460P 3 1233 RQCYQ500P 3 1234 RQCYQ540P 3 No Model name Type 1235 RQYQ8P...

Page 70: ...d time You can also run Leakage Check manually on site Furthermore Leakage Check can also be run from the Web Remote Management See page 90 The Leakage Check takes approximately 180 minutes to complet...

Page 71: ...SV file output CSV file output enables monitoring of the outdoor unit s Leakage Check results Page 77 History History Settings modifications sent instructions and errors are recorded as history Prepar...

Page 72: ...for each outdoor unit Completed Refrigerant Charging Operation is complete Uncompleted Refrigerant Charging Operation is incomplete Unknown Refrigerant Charging Operation status is unknown due to com...

Page 73: ...o unregister select the indoor unit from 3 and touch the Remove button to move it to 4 The indoor unit becomes unregistered Touch the OK button to commit the indoor unit registration and close the scr...

Page 74: ...e smaller number has precedence When the system time is adjusted for clock drift the execution of a scheduled Leakage Check changes as follows for an adjustment that stretches over the program executi...

Page 75: ...n of copy in the Copy to list 13 The Available list 14 is a list of outdoor units that can be registered as copy destination Selecting an outdoor unit and touching the Add button registers it in the C...

Page 76: ...door units registered in the refrigeration system of the outdoor unit are suitable for starting Leakage Check If they are in normal status the Leakage Check starts 2 Statuses unsuitable for starting L...

Page 77: ...curred with outdoor units and if any error is found run Leakage Check again NOTE Stopping Leakage Check by manual operation Stop Leakage Check by manual operation 17 18 1 Select the target outdoor uni...

Page 78: ...s are saved by naming the file LeakageCheck sequential number 1 to 9 If there are no more sequential numbers that can be used an error dialog is displayed and the output to CSV file aborted When opera...

Page 79: ...he remote control continue operating Furthermore these indoor units may operate in a different mode from that before the leakage check For this reason set up a schedule to stop or start the indoor uni...

Page 80: ...tic Control Schedule Control Automatic Control is disabled during Leakage Check since indoor units are under maintenance Interlocking Control Emergency Stop Control Emergency Stop instructions are sen...

Page 81: ...kage check and power limit control cannot be conducted at the same time i If power limit control is set to Demand 3 Forced thermo OFF it will be conducted before leakage control ii If power limit cont...

Page 82: ...abled Incorrect Leakage Check results Indoor units in the refrigeration system are not placed under maintenance because refrigeration system information for the outdoor unit indoor units is unknown Du...

Page 83: ...nance status is canceled and Leakage Check results are made viewable Touch the Check Start button or set up the schedule again after recovery from the cause of failure iTM judged that it failed to sta...

Page 84: ...of power outage Error in the communication between iTM and outdoor unit during Leakage Check None When a communication error occurred Leakage Check failure is recorded in the history Maintenance statu...

Page 85: ...ess indicated on the iTM main unit and the software ID shown in the license form supplied with the main unit will be requested Check them in advance Be sure to have them handy 1 Access to Daikin Distr...

Page 86: ...r function touch the Add button 3 Enter the Activation key for the optional maker function using the text input keyboard that appears and touch the OK button If the key is correct the function is adde...

Page 87: ...10 1 2 Enable 1 is a list of enabled dealer options Disable 2 is a list of disabled dealer options 2 To enable a new optional function select it from 2 and touch the Add button It is added to 1 and en...

Page 88: ...y via the Internet or receive notification via E mail in the case of an error To use these functions you must set up the network on the iTM unit The following describes how to set this up 1 Touch the...

Page 89: ...nput dialog that appears For information necessary for the settings consult your network administrator 1 Controller name 2 Host name 3 IP address 4 Subnet mask 5 Default gateway address 6 Preferred DN...

Page 90: ...number 8080 Touching the Modify button allows you to modify the settings in the Numerical Input dialog that appears Touch the OK button to save and close the screen 4 When finished touch the OK button...

Page 91: ...software such as a Web browser The requirements for the PC are as indicated in the table below Function Requirement PC for Web Remote Management OS Windows XP Professional SP3 32 bit Windows VISTA Bus...

Page 92: ...and cross Connect the PC and iTM unit by referring to the connection diagrams below Straight cable connection diagram Cross cable connection diagram When connecting the PC and iTM directly Use a 100B...

Page 93: ...owser Internet Explorer and select About from the Help menu In the case of Firefox you can check by selecting Help About Mozilla Firefox NOTE Check that the version is 8 0 xxxx xxxxxxx or 9 0 xxxx xxx...

Page 94: ...ot be guaranteed if both the Web browser and Flash Player are not of the specified version Be sure to use the version described in the table Necessary software can be downloaded from Microsoft Adobe a...

Page 95: ...Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 94 3 Click Network Connections 4 Double click Local Area Connection...

Page 96: ...Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 95 5 Select Properties 6 Select Internet Protocol TCP IP and click Properties...

Page 97: ...55 0 iTM settings at shipment are as follows Item Settings at shipment Host name localhost IP address 192 168 0 1 Subnet mask 255 255 255 0 Default gateway 0 0 0 0 Preferred DNS 0 0 0 0 Alternate DNS...

Page 98: ...ssioning Manual EM11A021 DCM601A51 intelligent Touch Manager 97 Setting up the IP address Windows Vista Business 1 Select Start Control Panel 2 Click Network and Internet 3 Click Network and Sharing C...

Page 99: ...Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 98 4 Click Manage network connections 5 Double click Local Area Connection...

Page 100: ...Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 99 6 Click Properties 7 Select Internet Protocol Version 4 TCP IPv4 and click Properties...

Page 101: ...up as follows when connecting to the iTM via local network IP address 192 168 0 2 Subnet mask 255 255 255 0 For iTM settings at the time of shipment see page 96 NOTE 9 Check that the settings are corr...

Page 102: ...sioning Manual EM11A021 DCM601A51 intelligent Touch Manager 101 Setting up the IP address Windows 7 Professional 1 Select Start Control Panel 2 Click Network and Internet 3 Click Network and Sharing C...

Page 103: ...Commissioning Manual EM11A021 DCM601A51 intelligent Touch Manager 102 4 Double click Local Area Connection 5 Select Properties...

Page 104: ...DCM601A51 intelligent Touch Manager 103 6 Select Internet Protocol Version 4 TCP IPv4 and click Properties 7 To connect to the iTM via the Internet ask its IP address and subnet mask to your network...

Page 105: ...plorer on Windows Vista and Windows 7 In Windows Vista and Windows 7 some operations are restricted by the User Account Control UAC regardless of the user type administrator regular user For that reas...

Page 106: ...21 DCM601A51 intelligent Touch Manager 105 1 2 3 4 5 Network Connection Check Check whether the Ethernet connection between a PC and iTM is normal Carry out the following procedure from the PC Windows...

Page 107: ...1 DCM601A51 intelligent Touch Manager 106 1 From the Start menu of the PC select All Programs Accessories Command Prompt Alternatively select Run from the Start menu of the PC enter cmd in Open and cl...

Page 108: ...EM11A021 DCM601A51 intelligent Touch Manager 107 2 The command prompt starts up Type ping followed by one single byte space and then the iTM IP address and press the Enter key In this example the IP a...

Page 109: ...llowed by the port number after the IP address Example If port number is 8080 enter 192 168 0 1 8080 NOTE Logging into Service Mode via Web Remote Management The Service Mode is also available when ma...

Page 110: ...etup program that lets you complete the basic setup procedure You can complete the basic setup procedure by following the instructions displayed on the monitor display in steps The setting assignment...

Page 111: ...ppears on the screen 3 Powering on data backup battery To retain the settings even in the event of a power outage the iTM integrator has a built in battery Because this battery is disabled by default...

Page 112: ...creen The radio button next to the language you touched is now selected 2 Touch OK The Locale Settings screen appears If the message Turn ON Battery Backup switch appears instead of the Locale Setting...

Page 113: ...decimal point on the display Locale Settings screen 1 LOCALE Select the desired options on the Locale Settings screen Language Select the display language Date Select the date display format Time Sel...

Page 114: ...region from the Time Zone combo box 2 Touch OK The Time DST Setup screen appears 8 Setting current time and daylight saving time Adjust the clock and set up the daylight saving time schedule Time DST...

Page 115: ...V LAN port Web Remote Management Router Web Remote Management HUB 100Base TX compliant iTM iTM iTM iTM iTM Individually working as iTM 5 units connected Internet Internet Service settings described in...

Page 116: ...ne 2 History Mgmt Delete Deletes history records of a specified period from the iTM integrator s history The setup method is the same as that for the iTM See 4 6 History Mgmt Delete 3 Controller Acces...

Page 117: ...16 Controller Access Setup Set up the connection between the iTM to be controlled and the iTM integrator 1 Display the Service Settings tab on the iTM integrator Menu List screen 1 2 Touch the Control...

Page 118: ...ss in the IP Address Input dialog that appears Set up the iTM Web port number in 4 Select Default or User Setup using the radio button If you selected User Setup then touch the Modify button to enter...

Page 119: ...istered iTM s IP address Web server port number connection status and controller name are listed in 5 You can register up to five iTM The Delete button 6 allows you to delete the iTM selected in the l...

Page 120: ...he OK button to close the screen If there is an iTM whose connection status is Disconnected the following Confirm dialog appears To exit setup leaving the iTM disconnected touch the Yes button To retu...

Page 121: ...ire length exceeds 1500m The total wire length must not exceed 2000m 1500m for shielded cords Check the status of the management points against the wiring diagram Connection is done to the wrong DIII...

Page 122: ...security vulnerabilities The pulse port is not displayed on the PPD setup tool Check whether the Pi management point is registered in iTM Pi management point is not registered Register the Pi manageme...

Page 123: ...pecification 243mm 207mm 290mm 256 6mm Power AC100 240 V 50 60 Hz Power consumption 23 W Emergency stop input Always a contact Contact current approximately 10 mA Size 290 243 50 W H D Weight 2 4 kg T...

Page 124: ...ore 2 Duo 1 2 GHz or higher Memory 2 GB or more Free HDD space 10 GB or more Network 100Base TX or higher Display resolution 1024 x 768 or higher Network 100Base TX Real transfer rate 115 kbps or high...

Page 125: ...EM11A021 1208 HT...