background image

 

Technical Data

Air Conditioners

C o n t r o l   S y s t e m s

E E D E N 1 5 - 1 0 0 

Summary of Contents for brp069a42

Page 1: ...Technical Data Air Conditioners C o n t r o l S y s t e m s E E D E N 1 5 1 0 0 ...

Page 2: ...DTA113B51 40 42 4 Mini Building Management System 53 54 5 Standard protocol interfaces 132 Modbus interface 132 KNX Interface 134 BACNET Interface 135 LonWorks Interface 143 6 Remote monitoring and maintenance 148 I Net 148 7 Daikin configurator software 150 EKPCCAB3 150 8 Sensors and other devices 151 Wireless room temperature sensor 151 Wired room temperature sensor 151 Other intergration device...

Page 3: ...RP980B2 required FTXZ N FTXJ LW LS FTXG LW LS FTXM20 25K CTXS15 35K FTXS20 35K FTXM35 42 50K FTXS35 50K FTXS G FTX J3 Individual control Infrared remote control ARC477A1 x Infrared remote control ARC466A1 x x Infrared remote control ARC466A6 x x x x x Infrared remote control ARC433A8 x Infrared remote control ARC480A11 Infrared remote control ARC466A2 Infrared remote control ARC452A1 Infrared remo...

Page 4: ...or units FTXS G FTX J3 FTX GV FTX20 35K FTX50 60K FVXG K FVXS F FDXS F 9 FLXS B 9 FTXLS K FTXL JV ATXS20 25K ATXS35 50K ATX J3 ATX K ATXL JV N A N A x N A x x x x N A x x N A x x N A x N A N A x N A x N A x x N A x x 1 x 1 x x 2 x x 2 x 2 x x x 2 x 2 x x 2 x 2 x 2 x x 2 x x 2 x 2 x x x x x 2 x 2 x x 2 x 2 x 2 x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x...

Page 5: ... auto cooling heating change over mode kWh indication keeps track of your consumption The kWh indication shows an indicative electricity consumption of the last day month year Other functions Up to 3 independent schedules can be set so the user can easily change the schedule himself throughout the year e g Summer winter mid season Possibility to individually restrict menu functions Easy to use all...

Page 6: ...ctions marked with 1 are available on BRC 44B2 ARC4 BRC4 BRC7 Infrared remote control Operation buttons ON OFF timer mode start stop timer mode on off programme time temperature setting air flow direction 1 operating mode fan speed control filter sign reset 2 inspection 2 test indication 2 Display Operating mode battery change set temperature air flow direction 1 programmed time fan speed inspecti...

Page 7: ... indoor unit Heating ºC Depends on the indoor unit Ambient temperature Operation Min ºC 10 Max ºC 50 Storage Min ºC 20 Max ºC 70 Relative humidity 95 Electrical Specifications BRC1E52A BRC1E52B Wiring connections Type of wires Sheathed vinyl cord or cable Size mm 0 75 1 25 For connection with indoor Quantity 2 Remark P1 P2 wired connection from indoor unit Wiring length Max m 500 Back up for power...

Page 8: ... Size 0 75 1 25mm2 Total length 500m 2 If the hole size is too large or the location is not proper the hole may come out from the remote control C Embedded Cord Use Switch Box A Exposed Cord Upper outlet Upper center outlet Left outlet Lower case portion Lower case portion Note 2 through hole 5x15 oblong hole Lower case Operation lamp green Upper case 5x7 oblong hole Code outlet hole Switch box fo...

Page 9: ...emote control holder Service space for ceiling installation more than 90 service space Ceiling opening Ceiling opening Transmitting part 5 x 7 Round end slit Hole Ø5 6 5 x 9 Round end slit 5 x 10 Round end slit 3D007898B NOTE 1 Do not install more than 3 receivers in the vincity of one another 2 With 4 or more units there is always the possibility of malfunction BRC4C62 Heat pump FXDQ M9 FXDQ PB N...

Page 10: ...eiver installation procedure Transmitting part Transmitting part Receiver detail Receiver detail Decoration panel Receiver Receiver Drain piping side Refrigerant piping side BYFQ60BW1 BYFQ60B7W1 BYFQ60B8W1 Remote control holder installation procedure installation to wall surface Remote control holder installation procedure installation to wall surface Liquid crystal remote control Liquid crystal i...

Page 11: ...re Wireless remote controller kit Transmitting part Transmitting part Receiver detail Receiver detail Receiver Remote control holder installation procedure installation to wall surface Remote control holder installation procedure installation to wall surface Remote control holder Remote control holder Liquid crystal remote control Liquid crystal remote control wireless wireless Drain socket Refrig...

Page 12: ...r outlet Operation lamp green Lower case Upper center outlet Staple note 2 Through hole Switch box Field supply part Lower case portion Switch box for one switch ex KJB111A optional accessory Switch box for two switch ex KJB211A optional accessory Between remote control and control box Lower case portion Left outlet oblong hole oblong hole Embedded cord use switch box Embedded cord Exposed cord Co...

Page 13: ... Basic user interface 20 5 2 Operation userinterface 20 5 3 Clock function 21 5 4 Schedule timer function 21 5 5 Energy Saving features menu always available 22 5 6 Maintenance information 22 5 7 Others 22 6 Combination BRC073A1 KRP928 to connect to DIII central control equipment 23 6 1 Typical layout for indoor models with standard S21 connector integrated 23 6 2 Typical layout for indoor models ...

Page 14: ...models The wired userinterface can be connected to following model ranges description Brand model range Wall mounted Ururu Sarara Daikin FTXZ N Emura Daikin FTXG LW S Emura Daikin FTXJ LW S Wall mounted Daikin CTXS K Wall mounted Daikin FTXS K Wall mounted Daikin FTXM K Wall mounted Daikin FTXLS K Wall mounted Daikin FTXS G Wall mounted Daikin FTX J Wall mounted Daikin FTX GV Wall mounted Daikin F...

Page 15: ...odels without S21 connector 14 Control systems Individual control systems BRC073 Required wireharness option available in different lengths BRCW901A03 08 Required wireharness option available in different lengths BRCW901A03 08 Adapter KRP980 S2 1 S21 indoor indoor n S21 Adapter BRC073A1 Adapter BRC073A1 BRC073A 1 BRC073A 1 ...

Page 16: ... Adapter h x w x d mm 80 x 44 x 21 5 Weight of userinterface net weight g 290 gross weight g 348 Weight of packing material Carton weight g 50 Ambient temperature operation C 10 50 indoor use storage C 20 70 Humidity Below 95 RH Temperature setpoint range cooling C 18 32 Temperature setpoint range heating C 10 30 Temperature setpoint range auto mode C 18 30 Temperature setting resolution C 1 color...

Page 17: ...067A41 EKRP980B2 specific model depending on indoor model Combination with other options that are connected to S21 BRC073A1 wired user interface is connected to the S21 connector of the indoor unit Only one S21 option can be applied at the same time on an indoor units with S21 Not possible to combine with different other S21 options e g BRP069A42 WLAN adapter Exception Due to the fact that the BRC...

Page 18: ...rmation User reference guide Detailed step by step instructions and background information for basic and advanced usage For detailed instructions on how to connect the wireharness to the S21 connector for the different indoor units Refer to the available installation videos for each daikin unit range with similar S21 wireharness installation of Daikin online controller are available on http www da...

Page 19: ...interface BRC073A1 adapter 4 3 2 dimensions BRC073A1 user interface mm BRC073A1 adapter mm Operation lamp green Upper case 5x7 Oblong hole 5x15 Oblong hole Code outlet hole Lower case 18 Control systems Individual control systems BRC073 Remote control dimensions ...

Page 20: ...x 4 4 2 Adapter Dimensions in mm Staple Upper outlet Condit Switch box for one switch Ex KJB111A Optional accessory Switch box for two switch Ex KJB211A Optional accessory Between remote control and control box Switch box Field supplied part Left outlet Lower case portion Lower case portion Note 2 Through hole Mounting with supplied wood screws Ø3 5x16 Mounting with supplied double face adhesive t...

Page 21: ...ckage 1 Language package 2 Language package 3 standard supplied 7 Languages 7 Languages 7 Languages 1 English 1 English 1 English 2 German 2 Czech 2 Russian 3 French 3 Croatian 3 Greek 4 Italian 4 Hungarian 4 Turkish 5 Spanish 5 Slovenian 5 Polish 6 Portuguese 6 Romanian 6 Serbian 7 Dutch 7 Bulgarian 7 Slovak Note With EKPCCAB3 PC USB cable in combination with updater PC software the language pack...

Page 22: ...Summer winter time automatic change over 5 4 Schedule timer function 3 independend schedules can be programmed nr 1 2 3 e g Nr 1 summer schedule nr 2 winter schedule nr 3 intermediate schedule A maximum of 5 actions can be programmed for each day of the week totalling 35 actions Schedule timer nr 1 nr 2 or nr 3 can be enabled disabled at any time but manual selection Each action linked to a Coolin...

Page 23: ... As there is no actual air flow the measured temperature inside the air conditioner unit can deviate up to 3 C with the actual room temperature Note Setback should not be enabled when a central controller is connected via the KRP928 interface adapter Setting temperature auto reset Even if the setting temperature is changed it returns to the preset temperature Off timer After you turn on the unit i...

Page 24: ...tion BRC073A1 KRP928 has influence on following functions Schedule timer function can be restricted in case central controller is installed via the KRP928 adapter Setback should not be enabled when a central controller is connected via the KRP928 interface adapter The additionall Mode conflict message on the BRC073A1 wired user interface will not be displayed when a central controller is connected...

Page 25: ...0B1 required CTXS35K2V1B KRP980B1 required CTXS15K3V1B KRP980B1 required CTXS35K3V1B KRP980B1 required Wall mounted Daikin FTXS K FTXS20K2V1B KRP980B1 required FTXS25K2V1B KRP980B1 required FTXS35K2V1B FTXS42K2V1B FTXS50K2V1B FTXS20K3V1B KRP980B1 required FTXS25K3V1B KRP980B1 required FTXS35K3V1B FTXS42K3V1B FTXS50K3V1B Wall mounted Daikin FTXM K FTXM20K3V1B KRP980B1 required FTXM25K3V1B KRP980B1 ...

Page 26: ... ATXS50K2V1B ATXS20K3V1B KRP980B1 required ATXS25K3V1B KRP980B1 required ATXS35K3V1B ATXS50K3V1B Siesta Daikin ATXS KV ATX20KV1B EKRP067A41 required ATX25KV1B EKRP067A41 required ATX35KV1B EKRP067A41 required Siesta Daikin ATXL JV ATXL25J2V1B KRP980B1 required ATXL35J2V1B KRP980B1 required Siesta Daikin ATX J ATX20J2V1B KRP980B1 required ATX25J2V1B KRP980B1 required ATX35J2V1B KRP980B1 required AT...

Page 27: ... your unit from anywhere offering optimal climate control while saving energy The Daikin Online Controller application can control and monitor the status of up to 50 units and allows you to Monitor the status of your heat pump unit Control the operation mode set temperature air flow rate and direction Schedule the set temperature and operation mode with up to 4 actions per day for 7 days 2 3 Table...

Page 28: ...Operation mode humidify û û û û û û û û û û û Temperature set point adjustment Humidification setpoint û û û û û û û û û û û Weekly schedule timer On off mode temperature 4actions day 28 actions total Mode batting for Multi û Air flow adjustment Fan speed Auto 5 steps Air flow adjustment Fan speed Quiet û û û û û û û û û Air flow direction adjustment Vertical swing Air flow direction adjustment Ho...

Page 29: ...ation mode automatic cooling heating dry fan only Operation mode humidify û û û û û û û û û û û û Temperature set point adjustment Humidification setpoint û û û û û û û û û û û û Weekly schedule timer On off mode temperature 4actions day 28 actions total Mode batting for Multi û û Air flow adjustment Fan speed Auto 5 steps Air flow adjustment Fan speed Quiet û û û û û û û û û Air flow direction ad...

Page 30: ...imum of 64 groups 128 indoor units max 10 outdoor units can be controlled ʯ a maximum of 128 groups 128 indoor units max 10 outdoor units can be controlled via 2 centralised remote controls in separate locations ʯ zone control ʯ group control ʯ malfunction code display ʯ maximum wiring length of 1 000m total 2 000m ʯ air flow direction and air flow rate of HRV can be controlled ʯ expanded timer fu...

Page 31: ... control Unified ON OFF Schedule timer DCS302C51 Centralised remote control Dimensional drawing DCS301B51 Unified on off control Dimensional drawing Unit mm Unit mm 3D004872 3D004872 Switch box Optional switch box Door closed Door open Ø 5 hole 2 5 x 7 Round end slit ...

Page 32: ...tems Centralised control systems Centralised remote control Unified ON OFF Schedule timer DST301B51 Schedule timer Dimensional drawing Unit mm 3D049544 Optional switch box Door closed Door open 2 5 x 7 Round end slit ...

Page 33: ...door unit ON OFF control Individual unified operation Remote control operation rejected command Centralised remote control given priority when used in combination with centralised remote control Sequential start function Controls up to 16 groups of indoor units with one unified ON OFF control Max 128 units Schedule timer Centralised remote control Unified ON OFF control Respective functions of sch...

Page 34: ... one place Unified On Off Control DCS301B51 Up to 4 control can be connected Unified On Off Control DCS301B51 Up to 4 controllers can be connected Unified adapter for computerised control DCS302A52 6 Max 7 The schedule timer unified adapter for computerised control etc can be connected to the same as in pattern 1 Never connect the wire between the contollers which are connected to different circui...

Page 35: ...trol is employed Also possible to control the operation of the airconditioner other than VRV system Wiring adapter for other airconditioner is required Possible to control the operation of room airconditioner Adapter for general use and the adapter PCB for room airconditioner are required Possible to control the operation of Sky Air Interface adapter for Sky Air series is required for certain unit...

Page 36: ... length is 1 100 m that is the total of 900 m between A and C and 200 m between B and C which also satisfies the limit of 2 000 m The central controller functions properly only when both the longest extension and the total length of wiring satisfies the limitation as shown above Notes When designing the system be sure to check both the longest extension and the total wiring length If it exceeds th...

Page 37: ...g between the outdoor units Line Main line Line Branch line Line Sub branch line How to count the branch wiring No sub branch line The control wiring between outdoor units and the control wiring between indoor unit and outdoor unit should be considered as main line We count this as no 1 branch and we count the branch line to no 2 12 which is diverged from the main line The terminal for Out Out and...

Page 38: ...ontrols are connected to the control wiring between the outdoor unit and indoor unit Line Main line Line Branch line Line Sub branch line How to count the branch wiring No sub branch line The control wiring between outdoor units and the control wiring between indoor unit and outdoor unit shall be considered as main line We count this as no 1 branch and we count the branch line to no 2 12 which is ...

Page 39: ... required to satisfy the following conditions The following conditions are not required to be considered when the number of controller is 7 or less Central control equipment Indoor units Outdoor units other adapters 160 units Central Conversion number of central control equipment Indoor units outdoor units other adapters 200 units NOTE is converted one central control equipment except unified ON O...

Page 40: ...S unit is used the indoor units used in its downstream are not counted 4 One port of one Interface for use in BACnet can have up to 64 groups 64 master indoor units with address In case of adopting group controlling the circuit covered by the data station can have up to 128 indoor units including main and sub units 1 x 10 x 10 x 1 A x 10 x 10 x 10 2 2 8 1 1 1 4 7 128 10 B 10 200 8 39 Control syste...

Page 41: ...n Cool Heat o o Temperature setting Cool Heat o o Error code o x O Possible X Impossible Specifications DTA113B51 Supply Voltage DC 16V supplied from R C line Maximum number of connectable indoor units 4 units per adapter PCB via GSM Forced ON OFF input Non voltage normal a contact x each point Dimensions mm 100x100x35 Installation method Built into the indoor unit or placed inside a box especiall...

Page 42: ... is the same as with the remote control operation The contact is to be purchased locally The current applied when the contact is ON is approx DC16V 10mA Input is via momentary A contact Minimum 1 second is required for turning ON Please don t clamp with high voltage cable 41 Control systems Centralised control systems DTA113B51 Relay harness 3 Relay harness 2 Analog Modem Transmission wiring termi...

Page 43: ... scheduling function 8 schedules 17 patterns ʯ ʯ Flexible grouping in zones ʯ ʯ Yearly schedule ʯ ʯ Fire emergency stop control ʯ ʯ Interlocking control ʯ ʯ Increased HRV monitoring and control function ʯ ʯ Automatic cooling heating change over ʯ ʯ Heating optimization ʯ ʯ Temperature limit ʯ ʯ Password security 3 levels general administration service ʯ ʯ Quick selection and full control ʯ ʯ Simpl...

Page 44: ...ironment to the web available security is only the username password control via the iTC web function I f information data such as passwords are leaked it is possible that an intruder could operation the A C Proposals for better security U sers can be limited by allowing only limited PCs to be able to acces the web via the use of firewalls and the like I ntroduction of security for constant connec...

Page 45: ...act 9 Power proportional distribution of the air conditioners With the optional software DCS002C51 10 Control and Monitoring of air conditioner with personal computer by the Controller with the optional software DCS004A51 A group of indoor units include 1 One indoor unit without a remote control 2 One indoor unit controlled with one or two remote controls 3 Up to 16 indoor units controlled with on...

Page 46: ...al size of the terminal block for communication with indoor units is M3 5 When monitoring and operating the indoor units using the optional Web and E mail function software sold separately connect to LAN via Ethernet cable This is used when distributing the power supply to indoor units using optional Power Proportional Distribution software sold separately and when stopping the indoor units compul...

Page 47: ...card Input terminals Digital input Di x 1 forced shutdown Pulse input Pi x 3 power measuring pulse power measuring pulse Overseas certification Safety of information Technology Equipment IEC60730 including IEC60335 IEC60730 including IEC60335 Interference EMC EN55022 Class A EN55024 EN55022 Class A EN55024 Project data Engineering Configuration and engineering for each project are necessary For fu...

Page 48: ...ure 1 F1 F2 wiring between this equipment and centralized control equipment is required 2 The connection to the facility equipment and setting of various switches are required See the Wiring with Facility equipment paragraph 3 Connect the power supply and earth See the Power Supply Earth wiring paragraph 3 For the wiring connection and clamping method refer to the Wiring lead in paragraph Wiring w...

Page 49: ...ther equipment within 80mm from the lower surface of this equipment Install this equipment in a place in which only authorized personnel can touch it 2 Installation Direction Install this equipment vertically to the floor surface It should be noted that if it is installed in horizontal direction a malfunction or failure may result 3 Installation Method Ensure that this equipment is installed with ...

Page 50: ...A51 F1 F2 DEC102A51 No Wiring procedure 1 F1 F2 wiring between this equipment and centralized control equipment is required 2 The connection to the facility equipment and setting of various switches are required See the Wiring with Facility equipment paragraph 3 Connect the power supply and earth See the Power Supply Earth wiring paragraph 3 For the wiring connection and clamping method refer to t...

Page 51: ... 50 60 Hz Grounding work Up to 16 units maximum Up to 16 units maximum Up to 64 groups maximum The number of connectable indoor units is up to 64 units maximum where the Power Proportional Distribution Card as option is used Up to 64 groups maximum The number of connectable indoor units is up to 64 units maximum where the Power Proportional Distribution Card as option is used Monitoring from PC is...

Page 52: ...general purpose table calculation software package may be available separately Precautions This system calculates electricity consumptions by size of indoor units run time expansion vales open gap suction rate and the number of pulses from the power meters installed at the Outdoor Units This method is not calculated by direct measurement alone 123 123 123 DAIKIN INDUSTRIES LTD DCS002A51 DCS601C51 ...

Page 53: ...tion file This file contains Power Proportional Distribution Report and information of air conditioners 1 File name YYYYMMDD YYYYMMDD Month and date of calculation completion Year month and date of calculation start 2 File format Example Index Start day number of days air conditioner type 0 normal type Undistributed Power Amount period designation type 0 period designation 1 month designation 2005...

Page 54: ...s and switches 60 3 1 3 Required space 63 3 1 4 Connections 64 3 2 iTM plus adaptor 71 3 2 1 Main specifications 71 3 2 1 1 Dimensions 72 3 2 2 Location of terminals and switches 72 3 2 3 Connections 75 3 3 iTM integrator 81 3 3 1 Main specifications 81 3 3 2 Location of terminals and switches 82 3 3 3 Required space 85 3 3 4 Connections 86 4 Accessoires 89 4 1 Di unit DEC101A51 89 4 2 Dio unit DE...

Page 55: ...geration Internet Extranet LAN 3G http interface Price competitive mini BMS Cross pillar integration of Daikin products Integration of third party equipment Split I O module I O module WAGO interface BACnet protocol Integration of third party equiqment Full control of Daikin HVAC R portfolio DCM601A51 Multi state objects Alarm Elevator Air handling unit ITM plus adaptor line Max 7 adapters DCM601A...

Page 56: ...issioning tool Auto registration of indoor units Functions overview Languages English French German Italian Spanish Dutch Portuguese Management Web access Power Proportional Distribution option Operational history malfunctions operation hours Smart energy management monitor if energy use is according to plan detect origins of energy waste Setback function Sliding temperature System layout Up to 2 ...

Page 57: ...ge 16 32 C Heating Mode Optimisation HMO Unneeded heating is prevented Timer extension Operation stop is selectable from 30 60 90 120 and 180 minutes Setback Setback setpoint can be set for 2 patterns Temperature range 1 7 C 1 7 C setpoint shift amount Data control Power Proportional Distribution Hourly Power Proportional Distribution results up to 13 months are recorded The system supports data o...

Page 58: ...lers ZUW Maximum 320 2 DIII compatible inverter chillers EWAQ BAWN BAWP EWAQ ADVP ACV3 ACW1 EWYQ BAWN BAWP EWYQ ADVP ACV3 ACW1 Di Di port of intelligent Touch Manager Maximum 32 3 Di port of iTM plus adapter D3 Di DIII Di Unit DEC101A51 Maximum 512 1 External Di Wago Di Maximum 512 4 D3 Dio D III Dio unit DEC102A51 Maximum 512 3 General purpose adaptor DTA103A51 Maximum 512 4 External Dio Wago Di ...

Page 59: ... 32bit Windows 7 Professional SP1 32bit 64bit Monitor 1024x768 or more Web browser Internet Explorer 8 9 Firefox 10 0 Flash Player Ver11 1 WAGO I O system Modbus communication unit 750 315 000 002 K190 6442 DC24V power supply unit 787 712 DC24V power supply module 750 613 Connector 750 960 Terminator module 750 600 Di module 750 400 750 432 Do module 750 513 000 001 Di module 750 430 Do module 750...

Page 60: ...dule Di Dio Ai Di Pi 4ch Emergency stop input Di1 Pulse input contact signal input plus ADP IF 1ch iTM plus adaptor Up to 7 adaptors internal modem option 1ch Air Conditioning Network Service System POWER SUPPLY DCM601A51 AC100 240V 10 50 60Hz INPUT 23W MASS 2 4kg FUSE AMP 3 15A Operating temperature limit 0 C 40 C Operating humidity limit MAX 15 C 85 Storage temperature range 15 C 60 C Installati...

Page 61: ... used for securing the power supply cables with cable ties B DIII The communication line connection terminals for DIII NET which enables communications with DAIKIN s air conditioning equipment C LINE PHONE The sockets used when subscribing to the DAIKIN Air Conditioning Network Service System online monitoring service for air conditioning systems To use the Air Conditioning Network Service System ...

Page 62: ... The switch used when there are two or more DIII NET centralized controllers to select the MASTER or SLAVE controllers E CPU ALIVE LED Green The LED that indicates that the CPU is operating normally The CPU is operating normally when this LED is blinking and malfunctioning when it is on or off It takes about 10 seconds for detection of the abnormality On Installation failure Off A hardware failure...

Page 63: ...ion or during maintenance You also see an attached label bearing the model weight power ratings and the serial number of the intelligent Touch Manager Side face of intelligent Touch Manager Pulling up the rubber cover reveals a USB socket This socket can be raised 90 degrees so you can plug in a USB device to it from the front direction when there is no clearance from the side edge of the unit ...

Page 64: ... sure that there is a minimum clearance of 30 mm from the top edge 100 mm from the left side edge 30 mm from the right side edge and 60 mm from the bottom edge of the unit Installation space required for intelligent Touch Manager Required installation space MONI TOR MONI TOR MONI TOR MONI TOR 30mm 100mm 290mm 100mm 60mm 60mm 30mm 243mm A B A Top B Wall ...

Page 65: ...e that the wires you are connecting to the F1 and F2 terminals are not power wires Inadvertently connecting power wires to these terminals results in a failure of the air conditioner or intelligent Touch Manager Conceptual connection diagram with air conditioning equipment A Outdoor unit B OUT OUT C IN OUT D Indoor unit E A maximum of 16 indoor units can be connected per remote controller group F ...

Page 66: ...must be limited to 2000 meters except when using a shielded cable whose total wire length must be kept to 1500 meters or less Precautions for using multiple centralized controllers Equipment that controls multiple air conditioners is referred to as centralized controller DAIKIN s product portfolio includes a wide range of centralized controllers suited to different applications or target sizes whi...

Page 67: ...adaptor Sub 6 Central Remote Controller Sub 7 ON OFF Controller Main 8 ON OFF Controller Sub Priority Low Centralized controllers that cannot be installed in parallel with intelligent Touch Manager CALCULATE UNIT intelligent Processing Unit Parallel Interface Intelligent Touch Controller DIII NET Plus Adapter Residential Central Remote Controller Schedule Timer Wiring Adaptor for Electrical Append...

Page 68: ... Applicable cable standard 100Base TX or 10Base T Connector standard RJ 45 SERVICE LAN socket and LAN SW switch NOTE If you are connecting to a LAN temporarily during installation or maintenance use the SERVICE LAN terminal located on the front face Changing the position of the LAN SW switch to FRONT causes the SERVICE LAN socket to activate enabled for use You cannot close the cover when the swit...

Page 69: ...nceptual connection diagram Conceptual drawing of I O module connection MONIT OR RS 485 A A Max 30 nodes Connect the I O module to the RS 485 terminals located on the rear face Be sure to connect the positive core to the positive terminal and the negative core to the negative terminal respectively If you are using shielded stranded wire cables twist and connect the strands of wire to the G Ground ...

Page 70: ...y meters for calculating the electricity usage of individual air conditioners when power distribution is enabled WARNING Be sure to perform this procedure with the power supply turned off Not doing so may cause an electric shock Do not clamp the cables with high current lines such as a power cable NOTE Power distribution is available for a maximum of 64 air conditioners indoor units per DIII NET p...

Page 71: ...rnally So you can use either of them However youcanconnectuptotwowiressimultaneously to each COM terminal Di1 COM Di2 COM Di3 COM Di4 COM Requirements that must be met Cable type CPEV cable Core thickness φ0 65 0 9 mm Cable length 200 meters or less Pulse width Pulse width 20 to 400 ms Pulse interval 100 ms or more A B A Pulse width 20 to 400 ms B Pulse interval 100 ms or more CAUTION The contact ...

Page 72: ... adaptor Up to 7 adaptors D III 1ch D III NET Up to 64 groups Di Pi 4ch Pulse input contact signal input POWER SUPPLY DCM601A52 AC100 240V 10 50 60Hz INPUT 6W MASS 0 5kg FUSE AMP 3 15A Operating temperature limit 10 C 50 C Operating humidity limit MAX 15 C 85 Storage temperature range 15 C 60 C Installation direction Vertical direction only ...

Page 73: ... up an efficient work plan For connection details including the cable type terminal size and wiring precautions refer to 2 Connection Front face of iTM plus adaptor All the terminals used during installation are located on the front face of the iTM plus adaptor Note that only the power terminals are covered with a terminal cover for safety You can remove this cover by loosening a single screw In a...

Page 74: ...lus adaptor set a unique number between 2 to 8 G TERM The switch used when multiple iTM plus adaptors are connected in parallel for enabling the termination resistor on the furthest iTM plus adaptor from the intelligent Touch Manager H DIII MASTER The switch used when there are two or more DIII NET centralized controllers such as intelligentTouch Managers are connected for distinguishing between t...

Page 75: ...led in a place and in a mounting direction as described below Installation place Indoor inside control enclosure which must be lockable or designed to be opened only with a special tool Mounting direction Vertical only Required space To install the iTM plus adaptor the following space is required Also note the following Make sure that there is a minimum clearance of 20 mm between each unit and wir...

Page 76: ...the cables with high current lines such as a power cable Terminals location and conceptual connection diagram Connect an iTM plus adaptor to the plus ADP IF terminals located on the rear face Be sure to connect the positive wire the terminal and the negative wire to the terminal respectively as these terminals have polarity Terminals location and conceptual connection diagram A intelligent Touch M...

Page 77: ...ion on the rear face of your intelligentTouch Manager Note that these terminals have polarity Be sure to connect the positive wire to the terminal and the negative wire to the terminal respectively In addition the intelligent Touch Manager must be connected as a terminal to the wiring Terminals location and conceptual connection diagram A intelligent Touch Manager Rear face B iTM plus adaptor C pl...

Page 78: ...res Inadvertently connecting power wires to these terminals results in a failure of the air conditioner or iTM plus adaptor Conceptual connection diagram with air conditioning equipment F2 F1 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 F1 F2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 F1 F2 E F A B C D D D D D A B C D D D D D A Outdoor unit B OUT OUT C I...

Page 79: ...otal wire length must be limited to 2000 meters except when using a shielded cable whose total wire length must be kept to 1500 meters or less Precautions for using multiple centralized controllers Equipment that controls multiple air conditioners is referred to as centralized controller DAIKIN s product portfolio includes a wide range of centralized controllers suited to different applications or...

Page 80: ...rs that cannot be installed in parallel with iTM plus adaptor CALCULATE UNIT intelligent Processing Unit Parallel Interface Intelligent Touch Controller DIII NET Plus Adapter Residential Central Remote Controller Schedule Timer Wiring Adaptor for Electrical Appendices 1 KRP2 Connecting contact or pulse input equipment such as electric energy meters The iTM plus adaptor can be connected with an ext...

Page 81: ...em However youcanconnectuptotwowiressimultaneously to each COM terminal Di1 Di2 COM Di3 Di4 COM Requirements that must be met Cable type CPEV cable Core thickness φ0 65 0 9 mm Cable length 200 meters or less Pulse width Pulse width 20 to 400 ms Pulse interval 100 ms or more A B A Pulse width 20 to 400 ms B Pulse interval 100 ms or more CAUTION The contact connected to the contact input terminal mu...

Page 82: ...ager ED721208 iTM integrator body 243mm 151 5mm 207mm 290mm 4 5mm 4 5mm 4 5mm 4 5mm 25mm 25mm 8mm 8mm 8mm 8mm 256 6mm 272mm 29 5mm Wall mounting metal plate 191mm 234 2mm 60mm 40mm 3 3 iTM Integrator 3 3 1 Main specifications Thickness 0 8mm ...

Page 83: ... rear face of the iTM integrator However they are covered with a terminal cover for safety reasons Removing 2 screws to detach this cover reveals various types of terminals as shown below Rear face of iTM integrator A POWER The power line connection terminals A power supply voltage of 100 to 240 VAC at 50 60 Hz is required Near this terminal block there is a blue resin cable mount used for securin...

Page 84: ...y for retaining the current settings D DIII MASTER No Use E CPU ALIVE LED Green The LED that indicates that the CPU is operating normally The CPU is operating normally when this LED is blinking and malfunctioning when it is on or off It takes about 10 seconds for detection of the abnormality On Installation failure Off A hardware failure occurred F LAN LINK LED Green The LED that indicates whether...

Page 85: ...nt direction when there is no clearance from the side edge of the unit Determining installation place Be sure to install the iTM integrator in a place that meets the conditions described in 1 4 1 through 1 4 3 below Installation place and mounting direction Below are the description of the installation place and mounting direction Be sure to confirm Installation place Indoor free from dust and wat...

Page 86: ... sure that there is a minimum clearance of 30 mm from the top edge 100 mm from the left side edge 30 mm from the right side edge and 60 mm from the bottom edge of the unit Installation space required for iTM integrator Required installation space MONI TOR MONI TOR MONI TOR MONI TOR 30mm 100mm 290mm 100mm 60mm 60mm 30mm 243mm A B A Top B Wall ...

Page 87: ... circuit breaker if available is turned off Not doing so may cause an electric shock After completing connections check again that all wires are connected correctly before turning on the power supply All field supplied parts and materials electric works must conform to local codes All wiring must be performed by an authorized electrician Removing terminal cover from rear face Removing terminal cov...

Page 88: ...iTM integrator can operate a maximum of 5 intelligent Touch Manager A B D D B D B D B D B C A iTM integrator B intelligent Touch Manager C Hub D Air conditioners or other devices that the intelligent Touch Manager is monitoring WARNING Do not clamp the cables with high current lines such as a power cable NOTE For how to connect the iTM integrator to a PC network contact your network administrator ...

Page 89: ...ust be met Applicable cable standard 100Base TX or 10Base T Connector standard RJ 45 SERVICE LAN socket and LAN SW switch NOTE If you are connecting to a LAN temporarily during installation or maintenance use the SERVICE LAN terminal located on the front face Changing the position of the LAN SW switch to FRONT causes the SERVICE LAN socket to activate enabled for use You cannot close the cover whe...

Page 90: ...n Possible Operation Error display only by lamps Unit DEC101A51 L N F1 F2 M CM A CA 9 9 Operating and error input When the contact is Open or Closed Error is produced For changeover refer to 2 Initial Setting Input specifications No voltage a contact The welding current is approx 10mA when the applied voltage is 20 to 30VDC and the contact is Closed For input use the contact for micro current 12VD...

Page 91: ...90 Control systems intelligent Touch Manager ED721208 Part Names and Functions Appearance Di Unit DEC101A51 PCB in DEC101A51 ...

Page 92: ...itor LED10 Red Micro computer OK monitor LED A Green Quantity change shortcircuit pin TP1 When the micro computer is in normal operation the lamp flickers Shortcircuit during control quantity setting Transformer connecting connector CN1 CN2 For the power supply use 1 200 240V When the transmission is abnormal the lamp lights up disabling remote control The lamp goes out in the normal condition The...

Page 93: ...It is therefore necessary to make arrangements so as not to attach other equipment within 80mm from the lower surface ot this equipment Install this equipment in a place in wich only the authorized personnel can touch it Installation Direction Install this equipment vertically to the floor surface It should be noted that if it is installed in the horizontal direction a malfunction or failure may r...

Page 94: ...shown below 40 80 325 40 140 40 40 DEC101A51 DEC101A51 DEC101A51 DEC101A51 To Remove Front Panel 1 5 4 Electric Wiring Work and Initial Setting should be performed with the front panel removed The front panel can be removed by detaching 2 front panel screws shown in the figure above and sliding it lightly to the upper side Upon completion of all wiring connections and setting operations close the ...

Page 95: ...PUT H5P 6 7 H3P H13P 3 1 8 5 X2A F2 F1 N L X3M RED H17P X1M YE RED AC200V 240V GRN HAP X2M X1A H4P 4 3 2 1 1 Wire connections and wire clamping should be as shown in the figure above 2 No simultaneous clamping is allowed for high voltage wiring power supply wiring L N earth wiring low voltage wiring Communication wiring F1 F2 operation input wiring CM M1 to 8 and abnormal input wiring CA A1 to 8 s...

Page 96: ...ent from factory 07 D 5 04 13 3 4 7 09 11 08 10 2 9 C A 0 05 E 6 06 12 01 B 8 03 14 00 15 02 F 1 2 00 2 15 1 00 1 15 RS2 DS1 8 3 00 3 15 4 00 4 15 Set the top address of this equipment with the DIII NET setting switch DS1 RS1 Using the DIII NET setting switch DS1 set the range of Address No that is set in this equipment Address Nos 1 00 to 1 15 are factory controlled before shipment Control range ...

Page 97: ...ondition The relationship between each switch and abnormal input is as described below Input A1 DS2 3 1 Input A2 DS2 3 2 Input A3 DS2 3 3 Input A4 DS2 3 4 Input A5 DS2 3 5 Input A6 DS2 3 6 Input A7 DS2 3 7 Input A8 DS2 3 8 TP1 Setting Facility equipment quantity change This function is used to set the number of facility equipment controllable with this equipment The number of controllable facility...

Page 98: ...equired The connection to the facility equipment and setting of various switches are required See the Wiring with Facility Equipment paragraph Connect the power supply and earth See the Power Supply Earth Wiring paragraph For the wiring connection and clamping method refer to the Wiring Lead in paragraph Wiring with Facility Equipment CAUTION The length of wiring between this equipment and facilit...

Page 99: ...ossible Possible Temp setting Possible Impossible Airflow rate setting Possible Impossible Airflow direction setting Possible Impossible Timer setting twice a day Possible Impossible Mode setting Possible Impossible Filter sign reset Possible Impossible Inspection Test operation Possible Operation Error display only by lamps Dio Unit DEC102A51 L N F1 F2 D CD M CM A CA Centralized control equipment...

Page 100: ...us Output Up to 2 facility equipments can be connected Output wiring for facility equipment 1 Facility Equipment Operation Circuit Example Output wiring for facility equipment 2 Termal size M3 5 Facility equipment protecting service Output SPEC No voltage a contact Voltage SPEC Maximum Current Minimum Current 200 240V 1 5A Resistive Load 10mA DC5 24V 2A Resistive Load 10mA Local operation Facility...

Page 101: ...al used in the case of setting to Continuous Output Run Stop output terminal Operation input terminal Abnormal input terminal 1st equipment CD D1 CM M1 CA A1 2nd equipment CD D2 CM M2 CA A2 3rd equipment CD D3 CM M3 CA A3 4th equipment CD D4 CM M4 CA A4 Facility equipment Up to 2 units can be connected to single DEC102A51 Terminal used in the case of setting to Instantaneous Output Operation outpu...

Page 102: ...101 Control systems intelligent Touch Manager ED721208 Part Names and Functions Appearance Dio Unit DEC102A51 PCB in DEC102A51 ...

Page 103: ...trol quantity setting It is possible to select whether the error at startup is masked for 10 or 30 seconds It is possible to select whether the equipment connection error is a non latch or latch error The start stop signal is outputted to the equipment to be connected The facility equipment status is monitored This switch makes it possible to select continuous 1 output or instantaneous 2 output Wh...

Page 104: ...external contacts are possible through DIII NET communication Installation method Indoor installation Power supply To be supplied from outside Rating AC200 240V 50 60Hz Applied Standard Safety standard IEC730 EMC standard CISPR22 A EMI CISPR24 EMS Environment for use Outdoor air temperature 15 to 60 C Ambient humidity 95 RH or less no condensation Environment for storage Outdoor air temperature 20...

Page 105: ...essary to make arrangements so as not to attach other equipment within 80mm from the lower surface of this equipment Install this equipment in a place in which only the authorized personnel can touch it Installation Direction Install this equipment vertically to the floor surface It should be noted that if it is installed in the horizontal direction a malfunction or failure may result Installation...

Page 106: ...t as shown below DEC102A51 DEC102A51 DEC102A51 DEC102A51 40 40 325 40 40 80 140 To Remove front Panel 1 4 4 Electric Wiring Work and Initial Setting should be performed with the front panel removed The front panel can be removed by detaching 2 front panel screws shown in the figure above and sliding it lightly to the upper side Upon completion of all wiring connections and setting operations close...

Page 107: ...Detecting start stop failure 1 No Yes DS5 Abnormal output shutoff retain Shut off control output upon detecting failure Yes No DS6 1 Startup failure Masking time after detecting operation input 10 seconds 30 seconds DS6 2 Failure detection Operation upon recovery from failure Automatic reset Retained DS6 3 Monitor input Detecting failure under halting status Yes No DS6 4 Forced termination Ignorin...

Page 108: ...iority or C C only Last command priority DS4 4 Operation commands from C C reach to C D but no operation No abnormality signal to C C DS5 Of abnormal in C D CD D1 4 is turned off DS6 1 Mask time for abnormal input after operation command from C C 10 seconds DS6 2 After error of C D is recovered Automatic reset DS6 3 Abnormal input stop state of C D Error display on C C DS6 4 Forced stop command fr...

Page 109: ...y equipment cannot be set to 4 In this case set it to 1 or 2 DS2 Setting This switch selects whether the input is abnormal with the abnormal input contact A1 to A4 oper or closed OFF factory preset before shipment Abnormal in the open condition ON Abnormal in the closed condition The relationship between each switch and abnormal input is as described below Input A1 DS2 1 Input A2 DS2 2 Input A3 DS...

Page 110: ...pment connected to this equipment 6 Finally open the TP1 The number of connectable facility equipment is 4 max at continuous output and 2 max at instantaneous output Electric wiring connection Wiring Procedure F1 F2 wiring between this equipment and centralized control equipment is required The connection to the facility equipment and setting of various switches are required See the Wiring with Fa...

Page 111: ...utput and it to be no voltage output If the specifications are not coincident there is a possibility that the following imperfections are caused If the pulse width is not within 20 400 msec If it is less than 20 msec the pulse input cannot be detected and the result of calculation is smaller than the real value In addition if more than 400 msec more than 2 pulses is detected for 1 pulse input and ...

Page 112: ...luded It is necessary to connect the watthour meter to the power supply line of the indoor unit and input its pulse to iTM In this case included power of Fan has to be set to Yes in the PPD setup tool 3 Calculation of electric power Crankcase heater PCB power consumption at stopping 1 In case of calculation for crankcase heater and PCB when not in operation 1 The electric power consumed by crankca...

Page 113: ...h Electric Power Group Watthour meters have to be installed for Heat Pump type VRV and Heat Recovery type VRV respectively as shown below figure and make power groups respectively iTM Watthour meter Watthour meter DIII NET Group 1 Group 2 VRV Heat Pump VRV Heat recovery ...

Page 114: ...must be different from others To be set at test operation WHM iTM Fig 1 Not Recommended Watthour meter is shared WHM WHM iTM Fig 2 Recommended Heat Recovery and other system watthour meter are separated Caution It is possible to register to the same electric power group for the following combination 1 VRV VRVII Heat Pump R 22 R 407C 2 VRV Heat Recovery R 22 R 407C 3 VRVII VRVIII Heat Pump R 410A 4...

Page 115: ... is not which complies with the Weight and Measure Act as shown in the catalogue The details of the cause to count error is described at chapter 1 3 2 1 Count method for a conventional VRV system 1 The following proportional division calculation is carried out every one hour and assigns the power consumption of air conditioning system to each indoor unit Heat load depending on the operation condit...

Page 116: ...crankcase heater to iTM it adds one 1 to the power counter inside iTM at no operation of the air conditioner when the crankcase heater is ON When this counter reaches 180 it judges that the crankcase heater was ON for one hour and in case of the above mentioned indoor unit the counter goes back to zero after 25 Wh is added to the counting result This calculation process is conducted separately fro...

Page 117: ...ter leaving off a 1 W figure to avoid the risk for the owners As a result the error by the leaving off occurs by 0 5W hour in average value as per each indoor unit Calculation example 1 Count for errors in 8 day Tenant A B 0 5 Wh 24 hr 8 days 5 units 0 48 kWh Tenant C 0 5 Wh 24 hr 8 days 3 units 0 288 kWh total 0 768 kWh 2 Assuming that the reads on watthour meters are as follows W1 read on wattho...

Page 118: ...8 4 5 W1 W2 iTM W1 Count conclusive total for indoor unit 1 5 W2 Count conclusive total for indoor unit 6 8 Caution If management staff checks the watts in the procedure mentioned below they would find the calculation to be incorrect due to an uncompleted cycle Example 1 May 24th read watthour meter and records the watts at 10 00 am 2 June 24th read watthour meter and records the watts at 10 00 am...

Page 119: ...ermo step which is a parameter necessary for power consumption apportionment For the VRV the indoor unit calculates thermo step Whereas for the Sky Air the outdoor unit calculates thermo step Although FXUQ is a Sky Air based indoor unit it cannot gather thermo step information from the outdoor unit because of an intervening BEV unit Therefore power consumption apportionment is not possible FXUQ BE...

Page 120: ...oor unit system 1 4 indoor units does not correspond to the value on wattmeter B Reason An intersystem difference causes this problem The PPD function does not recognize how many outdoor units exist in an electric power group It regards outdoor units as one big unit to perform PPD calculation Countermeasure If each outdoor unit system has a watthour meter make a power group for each outdoor unit s...

Page 121: ...e required for PPD If a group address is not set electric power is not distributed to the indoor unit Electric power is distributed among indoor units whose group addresses are registered iTM A B C D E F G H 1 00 1 01 1 02 1 03 Set a group address to B D G and H for PPD This setting can be configured in the field setting No 30 by remote controller The setting method is described in Page 332 Slave ...

Page 122: ...e the compressor is turned ON and the crankcase heater is turned OFF If accidentally keeping an air conditioner ON at a certain tenant the power consumption will increase iTM A B C D E F G H 4 When setting the Excluded Time is there a way to get to know a PPD result of the time A power pulse and a thermo step are not counted during the excluded time There is no way to get to know a PPD result or a...

Page 123: ...n polar 2 wire system reduces the number of required cables inside a building It also reduces mis connection facilitating the connection operation Post installation can be done easily Wiring up to 2km in total extension is available Various control devices can be freely connected and hierarchical risk diversification system can be established as well Comprehensive management of our Heat Reclaim Ve...

Page 124: ...nd that of refrigerant system coincide Crossed wiring will cause malfunctioning Connect indoor units and outdoor units without branch connection Connect outdoor units without branch connection Connect the centralized control equipment to the outdoor outdoor connection Indoor outdoor connection Outdoor outdoor connection Centralized Control Equipment VRV Outdoor unit VRV Indoor unit IN OUT IN OUT I...

Page 125: ...sk to loose control over all systems Ex If intelligent Touch Manager iTM is connected on a1 and System1 shut down control over System2 and System3 units is lost When all the centralized control equipment is located at one place Control wiring between indoor unit and outdoor unit Unified ON OFF controller DCS3301BA61 Up to 8 controllers can be connected intelligent Touch Manager DCM601A51 Combined ...

Page 126: ...entralized control equipment is located at one place Control wiring between indoor unit and outdoor unit Unified ON OFF controller DCS3301BA61 Up to 8 controllers can be connected Combined control of Heat reclaim ventilator is possible Independent operation of Heat reclaim ventilator is possible Control wiring between outdoor units It is possible to operate without remote controller When the centr...

Page 127: ...observed Wiring Specifications of DIII NET Be sure to use either 2 core sheathed vinyl cord or cable as mentioned below Vinyl cab tire round cord VCTF JISC3306 Example Section of cord Vinyl insulated vinyl sheathed cable for control CVV JISC3401 Round vinyl sheathed cable for control CVS JISC3401 Round vinyl insulated vinyl sheathed cable VVR JISC3342 600V vinyl cab tire cable VCT JISC3312 Polyeth...

Page 128: ...conditioners 220V or less 10A or less 50mm or more H 300mm or more 50A or less 500mm or more 100A or less 1000mm or more 100A or more 1500mm or more Note 1 1 VRV system SkyAir series and other air conditioner 2 2 VRV system or other Daikin air conditioner produces less electrical noise so that the distance of 50mm or more is sufficient For control wiring never use the shield wire together with oth...

Page 129: ...Outdoor Unit No of Outdoor Unit 10HP I U O U I U I U F1 F2 1 18HP I U O U I U I U F1 F2 1 28HP I U I U I U O U O U Q1 Q2 F1 F2 1 28HP I U I U I U I U I U I U O U O U O U O U Q1 Q2 F1 F2 F1 F2 Q1 Q2 F1 F2 2 I U Indoor unit O U Outdoor unit R C Remote controller Indoor Unit Indoor Unit Refrigerant Refrigerant Refrigerant Refrigerant Refrigerant Centralized Control Equipment ...

Page 130: ...or unit groups can be connected to DIII NET If you create remote control groups of indoor units up to 128 units can be connected Max number of groups is 64 In case of power proportional distribution the number of indoor units that can be connected is 64 units at the maximum even if you create remote control groups Example Each module is counted as 1 unit 2 unit module 3 unit module All the units c...

Page 131: ...lligentTouch Manager Following centralized control equipments can connect to the same DIII NET with an intelligentTouch Manager Centralized control equipment Description DMS502B51 Interface for use in BACnet or DMS504B51 Interface for use in LONWORKS One of these interfaces can connect to the same DIII NET DIII MASTER switch of intelligent Touch Manager should be set to SLAVE DMS601A51 intelligent...

Page 132: ......

Page 133: ... for monitoring and control of Daikin Altherma low temperature EHVH X C EHBH X C Voltage and resistance control Photovoltaic operation signal for energy saving RTD 20 Advanced control of Sky Air VRV VAM VKM and air curtains Clone or independent zone control Increased comfort with integration of CO2 sensor for fresh air volume control Save on runningcosts via pre post and trade mode set point limit...

Page 134: ...l Smart Grid control Control functions On Off Space heating cooling M C M C V Set point leaving water temperature heating cooling M V M R V Room temperature setpoint M M Operation mode M M Domestic Hot water ON M C V Domestic Hot Water reheat M C M C Domestic Hot Water reheat setpoint M R V Domestic Hot Water storage M Domestic Hot Water Booster setpoint M Quiet mode M C M C Weather dependent setp...

Page 135: ...ol house Concept Concept Domotica Controller Connect Sky Air VRV indoor units to KNX interface for BMS integration KNX interface line up The integration of Daikin indoor units through the KNX interface allows monitoring and control of several devices such as lights and shutters from one central controller One particularly important feature is the ability to programme a scenario light light shutter...

Page 136: ... Unlimited sitesize ʯ Easy and fast installation ʯ PPD data is available on BMS system only for VRV BACNET ETHERNET Fire alarm Security Local Control DIII NET VRV Outdoor unit Remote Control Power supply facility Pump Lighting Elevator HRV DMS502A51 up to 256 units connectable per interface Building control network BMS EKACBACMSTP Serial sequencing panel EKDSSP S EKCMBACIP EKCMBACMSTP Air handling...

Page 137: ...manufacturers concerning compatibility Specifications BACnet Interface DMS502A51 Description Rated Electrical conditions Rated Voltage and Frequency Single Phase AC 200 240 50 60 Hz Rated Power Maximum 20 W Conditions for Use Power Supply Fluctuation 10 of the Rated Value Ambient Temperature 10 50 C Ambient Humidity 0 98 Sweating is not acceptable Preservation Temperature 20 60 C Performance Insul...

Page 138: ...n not be solely used Option Digital Input Output DAM412B51 DAIKIN D BACS 24 M2 5 4 M3 5 4 M3 5 3 M3 5 10 M2 5 4 M3 5 Line Phone BACKUP POWER OFF ON PCMCIA RS232C 2 100BASE TX 10BASE T RS232C 1 AC100 240V 50 60Hz 3D056945 C 1P191166C C 1P191165B Board 104 5 27 12 7 140 1 2 30 3 Outside dimensions of PCB Outside dimensions of PCB BACnet Interface outside drawing DMS502A51 D SUB 9Pin male D SUB 9Pin ...

Page 139: ...Forced thermostat disble setting ForcedThermoOFFCommand_XXX BO Clearance Set 25 Forced thermostat disable status ForcedThermoOFFStatus_XXX BI Clearance Set 26 Energy saving setting Energy EfficiencyCommand_XXX BO Clearance Set 27 Energy saving status EnergyEfficiencyStatus_XXX BI Clearance Set 28 Thermostat status ThermoStatus_XXX BI OFF ON 29 Compressor status CompressorStatus_XXX BI Stop Operati...

Page 140: ... to BACnet client Ether link It lights when the 10BASE T acable or 100BASE TX cable RS485 TxD This LED display cannot be used with this unit RS485 RxD This LED display cannot be used with this unit RS232C 1 TxD It flashen when it tramits data to PC RS232C0 1 RxD It flashen when it receives data from PC RRS232C 2 TxD It flashes when it tranmits data to the central minitoring board RS232C 2 RxD It f...

Page 141: ...ing 0 0 X X Filter sign monitoring and reset 0 X X X Cumulative power value monitoring 0 X X 0 Thermostat status monitoring 0 X X X Compressor operation status monitoring 0 X X X Indoor fan operation status monitoring 0 X X X Heater operation status monitoring 0 X X X Air direction setting and monitoring 0 X X X Air flow rate setting and monitoring 0 X X X Forced thermostat off setting and monitor...

Page 142: ... G Line Phone RS232C 2 100BASE TX 10BASE T RS232C 1 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 Power DIII 1 DIII 2 Di RS485 Do 1 Do 2 AC100 240V 50 60Hz DAIKIN D BACS Telephone ACNSS For maintenance Central monitoring board BACnet client Ethernet Telephone line maximum of 64 groups maximum of 64 groups Earth leakage breaker install for safety Terminal contact size M3 5...

Page 143: ... Power consumption Max 20 W Weight 4 0 Kg DMS502A51 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 DMS502A51 DMS502A51 Outdoor unit BACnet client Field supplied Ethernet 10BASE T 10BASE T straight cable Polarity No Terminal contact size M3 5 DAM411B51 Option Terminal contact size M3 5 Recommended wire size 0 75 1 25mm2 Recommended wire size 0 75 1 2...

Page 144: ... protocol twisted pair wire ʯ Unlimited sitesize ʯ Quick and easy installation LON BMS DMS504B51 up to 64 units connectable per interface Local Control DIII NET VRV Outdoor unit HRV Remote Control Building control network ETHERNET TCP IP adapter LonTalk LonTalk Fire alarm System Security LonPoint LonPoint adapter adapter LonTalk Applied systems network EKACLONP Serial sequencing panel EKDSSP S Ser...

Page 145: ...Temperature Setting Report Monitors the set room temperature Room Temperature Report Monitors the room temperature Airflow Rate Setting Report Monitors the set airflow rate Filter Sign Report Checks limit of filter use and monitors if it has reached the limit Error Status Report Monitors error status of the air conditioners Error Code Report Displays the manufacturer specified error codes if any e...

Page 146: ... system and therefore this setting cannot be monitored by the upper system 2 The triangle G denotes a function that is only available for some models 3 Operation mode can be changed only on indoor units that allow a selection between heating and cooling Specifications Item Specifications Model DMS504B51 Dimensions mm 168 W x 260 H x 50 D mm Weight kg 1 5 kg Power supply Single phase AC100 240V 50 ...

Page 147: ...aximu 5W 2 Conditions Power Supply fluctuation 10 of the rated value Ambient temperature 10 50 C Ambient humidity 0 95 Sweating is not acceptable Preservation 20 60 C 3 Performance Insulation resistance 50MW or more by DC500 megohmeter 4 Weight 1 5 kg Detailed drawing of fixing hole Alive wink Service Service switch 100 240V 50 60Hz Power Manufacturer s label Make sure the power supply is off when...

Page 148: ...0 mA 13 Do not use multicore cables with three or more cores 14 Wirings must be isolated from the power lines 15 Terminal contact Size 3 5 Definition of LED and switch LED ALIVE WINK CPU normal monitor Green Normal Blinking every 0 4 sec Red WINK command reception Blinking every 0 2 sec SERVICE LON status Yellow Normal Light off Unconfigurate state Blinking every 0 5 sec SERVICE SW on Light on Err...

Page 149: ...ing the energy bill What is I Net A service based on our global remote monitoring technology keeping your system trouble free and working with top efficiency I Net Services i Net consists of 2 main services the VRV Cloud and I Net performance monitoring and analysis VRV Cloud The VRV Cloud puts you in the driving seat of your energy management The easy to use energy data trending and analytic tool...

Page 150: ... company Monitor your energy managment Performance supervision and analysis Data server Internet Prediction analysis Data trend logging Connection with I Net via ITM PCASO CLOUD Performance Supervision by Daikin experts enhances a maintenance plan This service aims to enhance the service level to respond fast and accurate to save on unexpected repair costs and assure the peace of mind Repetitive i...

Page 151: ...Simplified commissioning The Daikin configurator for Daikin Altherma and VRV is an advanced software solution that allows for easy system configuration and commissioning Less time is required on the roof configuring the outdoor unit Multiple systems at different sites can be managed in exactly the same way thus offering simplified commissioning for key accounts Initial settings on the outdoor unit...

Page 152: ...ger Wireless room temperature sensor kit K RSS Wireless room temperature receiver Wireless room temperature sensor Dimensions mm 5 x 5 ø 5 Weight g 4 6 Power supply 16VDC max 2 mA N A Battery life N A 3 years Battery type N A 3 Volt Lithium battery Maximum range m 1 Operation range C 5 Communication Type RF Frequency MHz 868 3 Specifications Wired room temperature sensor Accurate temperature measu...

Page 153: ...aneous control of VRV system operating mode Demand control of individual or multiple systems Low noise option for individual or multiple systems KRP928 Interface adapter for DIII net Allows integration of split units to Daikin central controls KRP413 Wiring adapter normal open contact normal open pulse contact Switch off auto restart after power failure Indication of operation mode error Remotely ...

Page 154: ......

Page 155: ...rt mode Powerful mode Auto cooling heating changeover Whisper quiet down to 19dBA Radiant heat Indoor unit silent operation Comfortable sleeping mode Outdoor unit silent operation 3 D Air flow 35 42 50 class 35 42 50 class Vertical auto swing Horizontal auto swing 35 42 50 class 35 42 50 class Auto fan speed Fan speed steps 5 5 5 5 5 5 5 5 5 5 5 Ururu humidification Sarara dehumidification Dry pro...

Page 156: ...ed FTXL JV FTX GV FTX K FTXK AW S FTXB C FVXG K FVXS F FDXS F 9 FDBQ B FLXS B 9 ATXS K ATXL JV ATX J3 ATX K ATXB C ATXN NB 35 50 class 20 25 class 35 50 class 35 50 class 5 5 5 3 3 5 5 3 2 5 5 5 5 3 3 5 depending on controller depending on controller optional 155 Control systems Benefits overview ...

Page 157: ...long in horizontal position to prevent ceiling stains Vertical auto swing Possibility to select automatic vertical moving of the air discharge louvre for uniform air flow and temperature distribution Fan speed steps Allows to select up to the given number of fan speed 3 Individual flap control Individual flap control via the wired remote controller makes it simple to fix the position of each flap ...

Page 158: ... 2 3 3 2 3 3 3 3 3 2 3 y optional optional optional standard optional optional standard optional optional optional optional optional optional optional optional optional optional optional standard optional optional optional optional optional optional optional optional optional optional optional optional optional optional optional optional optional standard standard standard standard standard standa...

Page 159: ...e thermostat is off the air discharge direction is set horizontally and the fan to low speed to prevent draught After warming up air discharge and fan speed are set as desired Auto cooling heating changeover Automatically selects cooling or heating mode to achieve the set temperature heat pump types only Indoor unit silent operation To ensure a quiet environment for studying or sleeping the user c...

Page 160: ...thin the same mode Multi tenant The indoor unit s main power supply can be turned off when leaving the hotel or office building 24 Hour timer Timer can be set to start cooling heating anytime during a 24 hour period Self diagnosis Simplifies maintenance by indicating system faults or operating anomalies Infrared remote control Infrared remote control with LCD to start stop and regulate your indoor...

Page 161: ...cular purpose of its content and the products and services presented therein Specifications are subject to change without prior notice Daikin Europe N V explicitly rejects any liability for any direct or indirect damage in the broadest sense arising from or related to the use and or interpretation of this leaflet All content is copyrighted by Daikin Europe N V Daikin products are distributed by EE...