5 Installation

Installation manual

10

FNA25~60A2VEB(9)

Split system air conditioners

4P456958-1J – 2020.12

Insulation

.  Insulate  the  refrigerant  piping  on  the  indoor  unit  as

follows:

A

B

a

d

c

e f

b

b

a

d

c

e f

b

b

2

4

3

g

1

2

3

4

g

A

B

1

A

Gas piping

B

Liquid piping

a

Insulation material (field supply)

b

Tie wrap (accessory)

c

Insulation pieces: Large (gas pipe), small (liquid pipe)
(accessories)

d

Flare nut (attached to the unit)

e

Refrigerant pipe connection (attached to the unit)

f

Unit

g

Sealing pads: Medium 1 (gas pipe), medium 2 (liquid
pipe) (accessories)

1

Turn up the seams of the insulation pieces.

2

Attach to the base of the unit.

3

Tighten the tie wraps on the insulation pieces.

4

Wrap the sealing pad from the base of the unit to the top
of the flare nut.

NOTICE

Make  sure  to  insulate  all  refrigerant  piping.  Any  exposed
piping might cause condensation.

5.2.2

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

ALWAYS  use  a  recommended  bubble  test  solution  from
your wholesaler.

NEVER use soap water:

▪ Soap  water  may  cause  cracking  of  components,  such

as flare nuts or stop valve caps.

▪ Soap  water  may  contain  salt,  which  absorbs  moisture

that will freeze when the piping gets cold.

▪ Soap  water  contains  ammonia  which  may  lead  to

corrosion  of  flared  joints  (between  the  brass  flare  nut
and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

5.3

Connecting the electrical wiring

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

5.3.1

Specifications of standard wiring
components

Component

Specification

Interconnection cable
(indoor↔outdoor)

Minimum cable section of

2.5 mm² and applicable for

230 V

H05RN-F (60245 IEC 57)

User interface cable

Vinyl cords with 0.75 to

1.25 mm² sheath or cables

(2‑core wires)

H03VV-F (60227 IEC 52)

Maximum 500 m

5.3.2

To connect the electrical wiring to the
indoor unit

It is important to keep the power supply and the transmission wiring
separated  from  each  other.  In  order  to  avoid  any  electrical
interference  the  distance  between  both  wirings  should  ALWAYS  be
at least 50 mm.

NOTICE

Be sure to keep the power line and transmission line apart
from  each  other.  Transmission  wiring  and  power  supply
wiring may cross, but may NOT run parallel.

1

Remove the service cover.

a

c

b

d

g

g

e

f

e

A B

A

Outside the unit

B

Inside the unit

a

Control box cover

b

Connection of interconnection cable (including earth)

c

Wiring diagram

d

Connection of user interface wiring

e

Sealing material (accessory)

f

Opening for cables

g

Wire

2

User  interface  cable

:  Route  the  cable  through  the  frame,

connect the cable to the terminal block, and fix the cable with a
cable tie.

3

Interconnection  cable

  (indoor↔outdoor):  Route  the  cable

through  the  frame,  connect  the  cable  to  the  terminal  block
(make  sure  the  numbers  match  with  the  numbers  on  the
outdoor unit, and connect the earth wire), and fix the cable with
a cable tie.

Summary of Contents for Bluevolution FNA35A

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FNA25A2VEB FNA35A2VEB FNA50A2VEB FNA60A2VEB FNA25A2VEB9 FNA35A2VEB9 FNA50A2VEB9 FNA60A2VEB9...

Page 2: ...acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 4: ...on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions...

Page 5: ...conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Use suspension bolts for installation Mind the followi...

Page 6: ...60 m kg Amin m2 1 842 No requirements 1 843 6 2 5 5 1 9 6 4 5 7 2 6 8 6 0 2 1 7 1 6 3 2 2 7 4 6 6 2 3 7 8 6 9 2 4 8 1 7 2 2 5 8 4 7 5 2 6 8 8 7 8 2 7 9 1 8 1 2 8 9 5 8 4 2 9 9 8 8 7 FNA25 35 FNA50 60...

Page 7: ...ng the suction cover B Reattaching the suction cover a Suction cover b Protective grille c Air inlet d Air outlet 7 Remove one leg on the opposite side of the electronic component box 8 Reattach the r...

Page 8: ...n the duct Use the function to adjust the fan rate setting automatically For setting refer to the installation manual of the used user interface The ducting is to be field supplied Air inlet side Atta...

Page 9: ...sory e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet only to discharge the water if the drain pump is not used or before maintenance Inse...

Page 10: ...applying the bubble test solution to all connections 3 Discharge all nitrogen gas 5 3 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply...

Page 11: ...em is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply volt...

Page 12: ...osed The air inlet or air outlet is blocked Error code Possible cause E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck...

Page 13: ...M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power...

Page 14: ......

Page 15: ......

Page 16: ...4P456958 1J 2020 12 Copyright 2017 Daikin Verantwortung f r Energie und Umwelt...