5 Installation

Installation manual

8

FNA25~60A2VEB(9)

Split system air conditioners

4P456958-1J – 2020.12

5.1.2

Guidelines when installing the ducting

WARNING

If  one  or  more  rooms  are  connected  to  the  unit  using  a
duct system, make sure:

▪ there are no operating ignition sources (example: open

flames,  an  operating  gas  appliance  or  an  operating
electric  heater)  in  case  the  floor  area  is  less  than  A

min

specified in the General safety precautions;

▪ no  auxiliary  devices,  which  may  be  a  potential  ignition

source,  are  installed  in  the  duct  work  (example:  hot
surfaces  with  a  temperature  exceeding  700°C  and
electric switching device);

▪ only  auxiliary  devices  approved  by  the  manufacturer

are used in the duct work;

▪ an air inlet or outlet is connected directly with a room by

ducting. Do NOT use spaces such as a false ceiling as
a duct for the air inlet or outlet.

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

CAUTION

▪ Make sure the installation of the duct does NOT exceed

the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.

▪ Make  sure  to  install  the  canvas  duct  so  vibrations  are

NOT  transmitted  to  the  duct  or  ceiling.  Use  a  sound-
absorbing material (insulation material) for the lining of
the  duct  and  apply  vibration  insulation  rubber  to  the
hanging bolts.

▪ When  welding,  make  sure  NOT  to  spatter  onto  the

drain pan or the air filter.

▪ If the metal duct passes through a metal lath, wire lath

or  metal  plate  of  the  wooden  structure,  separate  the
duct and wall electrically.

▪ Install the outlet grille in a position where the airflow will

not come into direct contact with people.

▪ Do NOT use booster fans in the duct. Use the function

to  adjust  the  fan  rate  setting  automatically.  For  setting
refer  to  the  installation  manual  of  the  used  user
interface.

The ducting is to be field supplied.

Air  inlet  side.

  Attach  the  duct  and  intake-side  flange  (field

supply). For connecting the flange, use 7 accessory screws.

a b

b a

e

e

d

d

c

a

Connection screw (accessory)

b

Flange (field supply)

c

Main unit

d

Insulation (field supply)

e

Aluminium tape (field supply)

Fixing  screws

.  When  installing  an  air  inlet  duct,  select  fixing

screws  that  stick  out  5  mm  on  the  inside  of  the  flange  to  protect
the air filter from damage during maintenance of the filter.

a

b

c

5 mm

a

Air inlet duct

b

Inside of the flange

c

Fixing screw

Filter. 

Be sure to attach an air filter inside the air passage on the

intake  side.  Use  an  air  filter  with  dust  collecting  efficiency  ≥50%
(gravimetric  method).  The  included  filter  is  not  used  when  the
intake duct is attached.

Air  outlet  side.

  Connect  the  duct  according  to  the  inside

dimension of the outlet-side flange.

Air leaks.

 Wind aluminium tape around the intake side flange and

duct  connection.  Make  sure  there  are  no  air  leaks  at  any  other
connection.

Insulation.

  Insulate  the  duct  to  prevent  condensation  from

forming. Use glass wool or polyethylene foam 25 mm thick.

5.1.3

Guidelines when installing the drain
piping

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

▪ Checking for water leaks

General guidelines

Pipe length.

 Keep drain piping as short as possible.

Pipe size.

 Keep the pipe size equal to or greater than that of the

connecting  pipe  (vinyl  pipe  of  20  mm  nominal  diameter  and
26 mm outer diameter).

Slope.

 Make sure the drain piping slopes down (at least 1/100) to

prevent air from being trapped in the piping. Use hanging bars as
shown.

1~1.5 m

a

a

Hanging bar

O

Allowed

X

Not allowed

Condensation.

  Take  measures  against  condensation.  Insulate

the complete drain piping in the building.

Summary of Contents for Bluevolution FNA35A

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FNA25A2VEB FNA35A2VEB FNA50A2VEB FNA60A2VEB FNA25A2VEB9 FNA35A2VEB9 FNA50A2VEB9 FNA60A2VEB9...

Page 2: ...acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 4: ...on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions...

Page 5: ...conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Use suspension bolts for installation Mind the followi...

Page 6: ...60 m kg Amin m2 1 842 No requirements 1 843 6 2 5 5 1 9 6 4 5 7 2 6 8 6 0 2 1 7 1 6 3 2 2 7 4 6 6 2 3 7 8 6 9 2 4 8 1 7 2 2 5 8 4 7 5 2 6 8 8 7 8 2 7 9 1 8 1 2 8 9 5 8 4 2 9 9 8 8 7 FNA25 35 FNA50 60...

Page 7: ...ng the suction cover B Reattaching the suction cover a Suction cover b Protective grille c Air inlet d Air outlet 7 Remove one leg on the opposite side of the electronic component box 8 Reattach the r...

Page 8: ...n the duct Use the function to adjust the fan rate setting automatically For setting refer to the installation manual of the used user interface The ducting is to be field supplied Air inlet side Atta...

Page 9: ...sory e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet only to discharge the water if the drain pump is not used or before maintenance Inse...

Page 10: ...applying the bubble test solution to all connections 3 Discharge all nitrogen gas 5 3 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply...

Page 11: ...em is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply volt...

Page 12: ...osed The air inlet or air outlet is blocked Error code Possible cause E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck...

Page 13: ...M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power...