5 Installation

Installation manual

9

FNA25~60A2VEB(9)
Split system air conditioners
4P456958-1J – 2020.12

Rising  piping

.  If  necessary  to  make  the  slope  possible,  you  can

install rising piping.

▪ Drain  hose  inclination:  0~75  mm  to  avoid  stress  on  the  piping

and to avoid air bubbles.

▪ Rising  piping:  ≤300  mm  from  the  unit,  ≤625  mm  perpendicular

to the unit.

Combining  drain  pipes.

  You  can  combine  drain  pipes.  Make

sure to use drain pipes and T-joints with the correct gauge for the
operating capacity of the units.

≥100

≤600

(mm)

a

a

T-joint

To connect the drain piping to the indoor unit

NOTICE

Incorrect  connection  of  the  drain  hose  might  cause  leaks,
and damage the installation space and surroundings.

1

Push  the  drain  hose  as  far  as  possible  over  the  drain  pipe
connection.

2

Tighten the metal clamp until the screw head is less than 4 mm
from the metal clamp part.

3

Check for water leaks (see 

"To check for water leaks"

 [

4

 9]).

4

Wind  the  large  sealing  pad  (=  insulation)  around  the  metal
clamp and drain hose, and fix it with tie wraps.

5

Connect the drain piping to the drain hose.

≤4 mm

A-A'

b

a

d

c

3

1

2~6

1

4

d

A

A'

A

A'

e

5

2

c

b

a

a

Drain pipe connection (attached to the unit)

b

Drain hose (accessory)

c

Metal clamp (accessory)

d

Large sealing pad (accessory)

e

Drain piping (field supply)

NOTICE

▪ Do NOT remove the drain pipe plug. Water might leak

out.

▪ Use  the  drain  outlet  only  to  discharge  the  water  if  the

drain pump is not used or before maintenance.

▪ Insert  and  remove  the  drain  plug  gently.  Excessive

force may deform the drain socket of the drain pan.

Pull out the plug.

▪ Do NOT wiggle the plug up and down.

a

Push in the plug.

▪ Set the plug and push it in using a Phillips screwdriver.

a

b

a

Drain plug

b

Philips screwdriver

To check for water leaks

Gradually  pour  approximately  1  l  of  water  in  the  drain  pan,  and
check for water leaks.

b

a

a

d

c

e

b

c

a

Air outlet

b

Portable pump

c

Bucket

d

Refrigerant pipes

e

Drain outlet

5.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

5.2.1

To connect the refrigerant piping to the
indoor unit

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

WARNING: FLAMMABLE MATERIAL

The  R32  refrigerant  (if  applicable)  in  this  unit  is  mildly
flammable.  Refer  to  the  outdoor  unit  specifications  for  the
type of refrigerant to be used.

Pipe length

. Keep refrigerant piping as short as possible.

Flare  connections

.  Connect  refrigerant  piping  to  the  unit  using

flare connections.

Summary of Contents for Bluevolution FNA35A

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FNA25A2VEB FNA35A2VEB FNA50A2VEB FNA60A2VEB FNA25A2VEB9 FNA35A2VEB9 FNA50A2VEB9 FNA60A2VEB9...

Page 2: ...acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 4: ...on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions...

Page 5: ...conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Use suspension bolts for installation Mind the followi...

Page 6: ...60 m kg Amin m2 1 842 No requirements 1 843 6 2 5 5 1 9 6 4 5 7 2 6 8 6 0 2 1 7 1 6 3 2 2 7 4 6 6 2 3 7 8 6 9 2 4 8 1 7 2 2 5 8 4 7 5 2 6 8 8 7 8 2 7 9 1 8 1 2 8 9 5 8 4 2 9 9 8 8 7 FNA25 35 FNA50 60...

Page 7: ...ng the suction cover B Reattaching the suction cover a Suction cover b Protective grille c Air inlet d Air outlet 7 Remove one leg on the opposite side of the electronic component box 8 Reattach the r...

Page 8: ...n the duct Use the function to adjust the fan rate setting automatically For setting refer to the installation manual of the used user interface The ducting is to be field supplied Air inlet side Atta...

Page 9: ...sory e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet only to discharge the water if the drain pump is not used or before maintenance Inse...

Page 10: ...applying the bubble test solution to all connections 3 Discharge all nitrogen gas 5 3 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply...

Page 11: ...em is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply volt...

Page 12: ...osed The air inlet or air outlet is blocked Error code Possible cause E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck...

Page 13: ...M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power...

Page 14: ......