3 About the units and options

Installation manual

5

FNA25~60A2VEB(9)
Split system air conditioners
4P456958-1J – 2020.12

3

About the units and options

3.1

System layout

INFORMATION

The  following  illustration  is  an  example  and  might  NOT
match your system layout.

a

b

c

f

d

e

a

Indoor unit

b

Outdoor unit

c

User interface

d

Refrigerant interconnection cable

e

Drain pipe

f

Earth wiring

4

Preparation

4.1

Preparing the installation site

▪ Provide  sufficient  space  around  the  unit  for  servicing  and  air

circulation.

▪ Choose  the  installation  location  with  sufficient  space  for  carrying

the unit in and out of the site.

CAUTION

Do  NOT  install  or  use  in  places  filled  with  smoke,  gas,
chemicals  etc.  Sensors  inside  the  indoor  unit  may  detect
these  substances,  and  display  a  refrigerant  leak
abnormality.

(1)

CAUTION

Do  NOT  install  or  use  in  highly  airtight  spaces,  e.g.
soundproof chambers or rooms with sealed doors.

(1)

CAUTION

This  unit  is  equipped  with  electrically  powered  safety
measures,  such  as  a  refrigerant  leak  detector.  In  order  to
be  effective,  the  unit  must  be  electrically  powered  at  all
times after installation, except for short service periods.

(1)

WARNING

Do  NOT  install  the  air  conditioner  at  any  place  where
flammable gas may leak out. If the gas leaks out and stays
around the air conditioner, a fire may break out.

4.1.1

Installation site requirements of the
indoor unit

INFORMATION

The sound pressure level is less than 70 dBA.

▪ Use

 suspension bolts

 for installation.

▪ Mind the following requirements:

a

a

1750

A

B

A

Wall-mounted type

B

Floor-standing type

a

Minimum clearance

Top view:

≥300

≥300

≥1000

(mm)

20

a

a

Indoor unit

▪ Install the unit with a prebuilt fully enclosed casing with removable

access  panel,  suction  air  grille  and  discharge  grille.  These
removable parts shall prevent access to the unit and can ONLY be
removed using a removal tool.

▪ In case of installation under a window sill, make sure that there is

no short-circuit of air.

5

Installation

5.1

Mounting the indoor unit

5.1.1

Guidelines when installing the indoor unit

INFORMATION

Optional  equipment.

  When  installing  optional  equipment,

also read the installation manual of the optional equipment.
Depending  on  the  field  conditions,  it  might  be  easier  to
install the optional equipment first.

Wall  or  floor  strength.

  Check  whether  the  wall  or  the  floor  is

strong enough to support the weight of the unit. If there is a risk,
reinforce the wall or the floor before installing the unit.

Suspension  bolts.

  Use  W3/8  M10  suspension  bolts  for

installation. Attach the hanger bracket to the suspension bolt. Fix it
securely  using  a  nut  and  washer  from  the  upper  and  lower  sides
of the hanger bracket.

(1)

Only for units using R32 refrigerant. Refer to the outdoor unit specifications for the type of refrigerant to be used.

Summary of Contents for Bluevolution FNA35A

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FNA25A2VEB FNA35A2VEB FNA50A2VEB FNA60A2VEB FNA25A2VEB9 FNA35A2VEB9 FNA50A2VEB9 FNA60A2VEB9...

Page 2: ...acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 4: ...on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions...

Page 5: ...conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Use suspension bolts for installation Mind the followi...

Page 6: ...60 m kg Amin m2 1 842 No requirements 1 843 6 2 5 5 1 9 6 4 5 7 2 6 8 6 0 2 1 7 1 6 3 2 2 7 4 6 6 2 3 7 8 6 9 2 4 8 1 7 2 2 5 8 4 7 5 2 6 8 8 7 8 2 7 9 1 8 1 2 8 9 5 8 4 2 9 9 8 8 7 FNA25 35 FNA50 60...

Page 7: ...ng the suction cover B Reattaching the suction cover a Suction cover b Protective grille c Air inlet d Air outlet 7 Remove one leg on the opposite side of the electronic component box 8 Reattach the r...

Page 8: ...n the duct Use the function to adjust the fan rate setting automatically For setting refer to the installation manual of the used user interface The ducting is to be field supplied Air inlet side Atta...

Page 9: ...sory e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet only to discharge the water if the drain pump is not used or before maintenance Inse...

Page 10: ...applying the bubble test solution to all connections 3 Discharge all nitrogen gas 5 3 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply...

Page 11: ...em is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply volt...

Page 12: ...osed The air inlet or air outlet is blocked Error code Possible cause E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck...

Page 13: ...M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes through ferrite core PAM Pulse amplitude modulation PCB Printed circuit board PM Power...

Page 14: ......

Page 15: ......

Page 16: ...4P456958 1J 2020 12 Copyright 2017 Daikin Verantwortung f r Energie und Umwelt...