6 Commissioning

Installation manual

11

FNA25~60A2VEB(9)
Split system air conditioners
4P456958-1J – 2020.12

4

Wrap  the  cables  with  the  sealing  material  (accessory)  to
prevent  water  from  entering  the  unit.  Seal  all  gaps  to  prevent
small animals from entering the system.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

A

c

b

c

a

A

Indoor PCB (assembly)

a

Power supply and earth wiring

b

Transmission and user interface wiring

c

Clamps

X

Not allowed

O

Allowed

5

Reattach the service cover.

1~ 50 Hz

220-240 V

b

a

e

c

d

a

Interconnection cable

b

Power supply cable

c

Earth leakage circuit breaker

d

Fuse

e

User interface

6

Commissioning

NOTICE

ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.

6.1

Checklist before commissioning

After  the  installation  of  the  unit,  first  check  the  items  listed  below.
Once all checks are fulfilled, the unit must be closed. Power-up the
unit after it is closed.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

indoor units

 are properly mounted.

In case a wireless user interface is used: The 

indoor unit

decoration panel

 with infrared receiver is installed.

The 

outdoor unit

 is properly mounted.

There are NO 

missing phases

 or 

reversed phases

.

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

The 

insulation resistance

 of the compressor is OK.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the indoor and outdoor units.

There are NO 

refrigerant leaks

.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

The 

stop valves

 (gas and liquid) on the outdoor unit are

fully open.

6.2

To perform a test run

This  task  is  only  applicable  when  using  the  BRC1E52  or  BRC1E53
user  interface.  When  using  any  other  user  interface,  see  the
installation manual or service manual of the user interface.

NOTICE

Do NOT interrupt the test run.

INFORMATION

Backlight.

  To  perform  an  ON/OFF  action  on  the  user

interface,  the  backlight  does  not  need  to  be  lit.  For  any
other  action,  it  needs  to  be  lit  first.  The  backlight  is  lit  for
±30 seconds when you press a button.

1

Perform introductory steps.

#

Action

1

Open the liquid stop valve and gas stop valve by
removing the cap and turning counterclockwise with a
hex wrench until it stops.

2

Close the service cover to prevent electric shocks.

3

Turn ON power for at least 6 hours before starting
operation to protect the compressor.

4

On the user interface, set the unit to cooling operation
mode.

2

Start the test run

#

Action

Result

1

Go to the home menu.

Cool

Set to

28

°C

2

Press at least 4 seconds.

The Service Settings menu
is displayed.

Summary of Contents for Bluevolution FNA35A

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners FNA25A2VEB FNA35A2VEB FNA50A2VEB FNA60A2VEB FNA25A2VEB9 FNA35A2VEB9 FNA50A2VEB9 FNA60A2VEB9...

Page 2: ...acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 3: ...cestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e...

Page 4: ...on farms or for commercial and household use by lay persons Documentation set This document is part of a documentation set The complete set consists of General safety precautions Safety instructions...

Page 5: ...conditioner a fire may break out 4 1 1 Installation site requirements of the indoor unit INFORMATION The sound pressure level is less than 70 dBA Use suspension bolts for installation Mind the followi...

Page 6: ...60 m kg Amin m2 1 842 No requirements 1 843 6 2 5 5 1 9 6 4 5 7 2 6 8 6 0 2 1 7 1 6 3 2 2 7 4 6 6 2 3 7 8 6 9 2 4 8 1 7 2 2 5 8 4 7 5 2 6 8 8 7 8 2 7 9 1 8 1 2 8 9 5 8 4 2 9 9 8 8 7 FNA25 35 FNA50 60...

Page 7: ...ng the suction cover B Reattaching the suction cover a Suction cover b Protective grille c Air inlet d Air outlet 7 Remove one leg on the opposite side of the electronic component box 8 Reattach the r...

Page 8: ...n the duct Use the function to adjust the fan rate setting automatically For setting refer to the installation manual of the used user interface The ducting is to be field supplied Air inlet side Atta...

Page 9: ...sory e Drain piping field supply NOTICE Do NOT remove the drain pipe plug Water might leak out Use the drain outlet only to discharge the water if the drain pump is not used or before maintenance Inse...

Page 10: ...applying the bubble test solution to all connections 3 Discharge all nitrogen gas 5 3 Connecting the electrical wiring DANGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply...

Page 11: ...em is properly earthed and the earth terminals are tightened The fuses or locally installed protection devices are installed according to this document and have NOT been bypassed The power supply volt...

Page 12: ...osed The air inlet or air outlet is blocked Error code Possible cause E7 There is a missing phase in case of three phase power supply units Note Operation will be impossible Turn OFF the power recheck...