[ PRECAUTIONS ] 

1.

Use round crimp-style terminals for connecting wiring to the power supply terminal block. 
If unavailable, observe the following points when wiring.

Do not connect wiring of different gauge to the same power supply terminal.
(Looseness in the connection may cause overheating.)

Use the specified electric wiring. Connect the wiring securely to the terminal. Lock the wiring down with-
out applying excessive force to the terminal. (Tightening torque: 131N·cm ±10 %)

2. Tightening torque for the terminal screws.

Use the correct screwdriver for tightening the terminal screws. If the blade of screwdriver is too small, the 
head of the screw might be damaged, and the screw will not be properly tightened.

If the terminal screws are tightened too hard, screws might be damaged.

Refer to the table below for the tightening torque of the terminal screws.

3.

Do not connect wiring of different gauge to the same grounding terminal. Looseness in the connection 
may deteriorate protection.

4.

Outside of the unit, keep the weak wiring (gas piping thermistor lead wire, transmission wiring) at least 
50 mm away from strong wiring (power supply wiring, inter-unit wiring, ground wire, and other power 
wiring). The equipment may malfunction if subjected to electrical (external) noise.

5.

For remote controller wiring, refer to the “INSTALLATION MANUAL OF REMOTE CONTROLLER” 
attached to the remote controller. 

6. Never connect power supply wiring to the terminal block for remote controller wiring. A mistake of 

the sort could damage the entire system.

7.

Use only specified wiring and tightly connect wiring to terminals. Be careful wiring do not place external 
stress on terminals.  Keep wiring in neat order and so as not to obstruct other unit such as popping open 
the control box lid. Make sure the lid closes tight. Incomplete connections could result in overheating, and 
in worse case, electric shock or fire.

Terminal

Size

Tightening torque

Transmission terminal block  (2P)

M3.5

0.79 – 0.97N·m

Power supply and inter-unit wiring terminal block (6P)

M4

1.18 – 1.44N·m

Ground terminal

M4

1.44 – 1.94N·m

Electric wiring

Round crimp-style terminal

Attach insulation sleeve

3P084604-2A_Eng.fm  Page 13  Wednesday, March 3, 2004  10:01 AM

Summary of Contents for BEVQ100MVE

Page 1: ...A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGV...

Page 2: ...conformidade com a s seguinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retning...

Page 3: ...aler or qualified personnel to carry out installation work Do not try to install the machine yourself Improper installation may result in water leakage electric shocks or fire Perform installation wor...

Page 4: ...m televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Remote controller wireles...

Page 5: ...e exposed to combustible gas and where volatile flammable gas like thinner or gasoline is used Gas in the vicinity of the unit could ignite Where machines can generate electromagnetic waves Control sy...

Page 6: ...eight if it seems dangerous install it after reinforcing the location with boards crossbeams etc 3 Install the gas piping connection piping 7 no further than 250mm form the hole for the thermistor on...

Page 7: ...stall so that the control box lid is facing down Take the gas piping thermistor out from above Horizontal position Direction of the gas piping connection piping 100 Upper Lower 100 250 or more 500 or...

Page 8: ...stall the hanging bolts Use M8 hanging bolts If it is pre set use hole in anchors Otherwise use embedded inserts or embedded foundation bolts to make sure that the weight of the unit can be supported...

Page 9: ...h tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while working on the unit ventilate the room t...

Page 10: ...ecting section after checking gas leakage by thoroughly studying the following figure Wrap the insulation for fitting 3 4 around the insulation for the joints on the liquid piping side and the gas pip...

Page 11: ...carried out nitrogen substitution or while inserting nitrogen into the refrigerant piping Once this is done connect the indoor unit with a flared connection Nitrogen should be set to 0 02 MPa 0 2 kg...

Page 12: ...Additional filling amount a b c d e f g h i j k l m n p q Refer also to the installation manual included with the outdoor unit 7 ELECTRIC WIRING WORK 7 1 GENERAL INSTRUCTIONS All field supplied parts...

Page 13: ...x Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A NOTES The above Table of Electrical Characteristics refers to the BEV unit only See the technical documents for other details 7 3 SPECIF...

Page 14: ...e and the transmission wiring using the included clamp 1 CAUTIONS Do not under any circumstances connect the power supply wiring to the transmission terminal block F1 F2 as this may cause damage to th...

Page 15: ...the unit keep the weak wiring gas piping thermistor lead wire transmission wiring at least 50 mm away from strong wiring power supply wiring inter unit wiring ground wire and other power wiring The e...

Page 16: ...P1 P2 L N 1 2 3 F1 F2 L N P1 P2 P1 P2 L N T1 T2 P1 P2 F1 F2 L N P1 P2 IN D OUT D F1 F2 F1 F2 Control box Outdoor unit BEV Unit A Indoor Unit A Indoor Unit B Indoor Unit C Normal VRV Indoor Unit BEV Un...

Page 17: ...1 P2 P1 P2 L N OUT D BS IN D F1 F2 F1 F2 L N IN D OUT D F1 F2 F1 F2 Control box Outdoor unit Indoor Unit A F1 F2 F1 F2 1 2 TO indoor 3 F1 F2 L N BEV Unit A BS Unit A BS Unit B P1 P2 P1 P2 Indoor Unit...

Page 18: ...Once all piping work is done screw the control box lid shut using the mounting screws 9 HOW TO ATTACH THE NAMEPLATE Attach the included nameplate 9 next to the machine nameplate on the indoor unit 10...

Page 19: ...0404 HT 3P084604 2A EM03A115 FS 3P084604 2_cv fm Page 2 Thursday February 5 2004 2 41 PM...

Reviews: