background image

12

English

8. WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTROLLER

8-1 HOW TO CONNECT WIRINGS 

Connect the piping only after finishing the refrigerant piping work.

Make sure all power supply is shut down to the unit first.

As shown in the Fig. 16, loosen the two screws in the control box lid, remove it, and do the wiring work.

Once all wiring is done, attach the control box lid and secure it with the screws.
If you are using “8-4 DEFAULT SETTINGS,” however, finish that and then attach the control box lid and 
secure it with the screws.

8-2 THE GAS PIPING THERMISTOR

Connect to (X5A) on A1P.

Bundle the gas piping thermistor lead wire and the branch wiring (transmission) using the included 
clamping material.

Tension is not added to the gas pipe thermistor lead wire coming out of the unit.

• Power supply wiring

• Ground wire

Connect the wiring to R (L) and S (N) on the power supply terminal block (X1M). Also, connect the ground 
wire to the ground terminal. Take the wiring and the ground wire into the unit through the wiring pass-through 
hole, and firmly secure them together using the included clamp (1).

• Indoor unit inter-unit wiring

Connect the wires to 1, 2, and 3 on the power supply terminal block (X1M). Take the wires into the unit 
through the wiring pass-through hole, and firmly secure them using the included clamp (1).

• Transmission wiring

Connect the wires to F1 and F2 on the transmission terminal block (X2M). Take them into the unit through 
the wiring pass-through hole, and firmly secure the gas piping thermister lead wire and the transmission 
wiring using the included clamp (1).

[ CAUTIONS ] 

Do not under any circumstances connect the power supply wiring to the transmission terminal block (F1, 
F2), as this may cause damage to the entire system.

CAUTION

When clamping wiring, use the included clamping material to prevent outside presure being exerted on the 
wiring connections and clamp firmly. When doing the wiring, make sure the wiring is neat and does not 
cause the control box lid to stick up, then close the cover firmly.

When attaching the control box lid, make sure you do not pinch any wires.

After all the wiring connections are done, fill in any gaps in the through holes with putty or insulation (pro-
cured locally) to prevent small animals and insects from entering the unit from outside. (If any do get in, they 
could cause short circuits in the control box.)

Outside the machine, separate the weak wiring (gas piping thermistor lead wire, transmission wiring) and 
strong wiring (power supply wiring, inter-unit wiring, ground wire, and other power wiring) at least 50mm so 
that they do not pass through the same place together. Proximity may cause electrical interference, mal-
functions, and breakage.

X5A

A1P

1

2

3

R

(

L

)

S

(

N

)

F1 F2

X1M

X2M

Fig. 16

Ground terminal

Gas piping 
thermistor lead wiring

Low 
voltage

High 
voltage

Transmission wiring

Ground wire

Power supply wiring

Indoor unit 
inter-unit wiring

Ground wire

Power supply wiring

Clamp (1)

 (accessory)

Clasp

Clamp (1) 

Clasp

Indoor unit inter-unit wiring

 (accessory)

Gas piping thermistor lead wire

Clasp

Transmission 
wiring

Clamp (1)

 (accessory)

Control box lid

The gas piping thermistor lead wire should 
be passed through the clamp (1).

3P084604-2A_Eng.fm  Page 12  Wednesday, March 3, 2004  10:01 AM

Summary of Contents for BEVQ100MVE

Page 1: ...A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGV...

Page 2: ...conformidade com a s seguinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retning...

Page 3: ...aler or qualified personnel to carry out installation work Do not try to install the machine yourself Improper installation may result in water leakage electric shocks or fire Perform installation wor...

Page 4: ...m televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Remote controller wireles...

Page 5: ...e exposed to combustible gas and where volatile flammable gas like thinner or gasoline is used Gas in the vicinity of the unit could ignite Where machines can generate electromagnetic waves Control sy...

Page 6: ...eight if it seems dangerous install it after reinforcing the location with boards crossbeams etc 3 Install the gas piping connection piping 7 no further than 250mm form the hole for the thermistor on...

Page 7: ...stall so that the control box lid is facing down Take the gas piping thermistor out from above Horizontal position Direction of the gas piping connection piping 100 Upper Lower 100 250 or more 500 or...

Page 8: ...stall the hanging bolts Use M8 hanging bolts If it is pre set use hole in anchors Otherwise use embedded inserts or embedded foundation bolts to make sure that the weight of the unit can be supported...

Page 9: ...h tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while working on the unit ventilate the room t...

Page 10: ...ecting section after checking gas leakage by thoroughly studying the following figure Wrap the insulation for fitting 3 4 around the insulation for the joints on the liquid piping side and the gas pip...

Page 11: ...carried out nitrogen substitution or while inserting nitrogen into the refrigerant piping Once this is done connect the indoor unit with a flared connection Nitrogen should be set to 0 02 MPa 0 2 kg...

Page 12: ...Additional filling amount a b c d e f g h i j k l m n p q Refer also to the installation manual included with the outdoor unit 7 ELECTRIC WIRING WORK 7 1 GENERAL INSTRUCTIONS All field supplied parts...

Page 13: ...x Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A NOTES The above Table of Electrical Characteristics refers to the BEV unit only See the technical documents for other details 7 3 SPECIF...

Page 14: ...e and the transmission wiring using the included clamp 1 CAUTIONS Do not under any circumstances connect the power supply wiring to the transmission terminal block F1 F2 as this may cause damage to th...

Page 15: ...the unit keep the weak wiring gas piping thermistor lead wire transmission wiring at least 50 mm away from strong wiring power supply wiring inter unit wiring ground wire and other power wiring The e...

Page 16: ...P1 P2 L N 1 2 3 F1 F2 L N P1 P2 P1 P2 L N T1 T2 P1 P2 F1 F2 L N P1 P2 IN D OUT D F1 F2 F1 F2 Control box Outdoor unit BEV Unit A Indoor Unit A Indoor Unit B Indoor Unit C Normal VRV Indoor Unit BEV Un...

Page 17: ...1 P2 P1 P2 L N OUT D BS IN D F1 F2 F1 F2 L N IN D OUT D F1 F2 F1 F2 Control box Outdoor unit Indoor Unit A F1 F2 F1 F2 1 2 TO indoor 3 F1 F2 L N BEV Unit A BS Unit A BS Unit B P1 P2 P1 P2 Indoor Unit...

Page 18: ...Once all piping work is done screw the control box lid shut using the mounting screws 9 HOW TO ATTACH THE NAMEPLATE Attach the included nameplate 9 next to the machine nameplate on the indoor unit 10...

Page 19: ...0404 HT 3P084604 2A EM03A115 FS 3P084604 2_cv fm Page 2 Thursday February 5 2004 2 41 PM...

Reviews: