5. BEV UNIT INSTALLATION

6. REFRIGERANT PIPING WORK

〈〈〈〈

This shows the piping method between the outdoor unit and the BEV unit and the indoor unit. Select 

the pipe size and refrigerant branch kit depending on how the piping will be laid.

〉〉〉〉

〈〈〈〈

For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.

〉〉〉〉

〈〈〈〈

Execute heat insulation work completely on both sides of the gas piping and the liquid piping. Oth-

erwise, a water leakage can result sometimes.

〉〉〉〉

〈〈〈〈

When using a heat pump, the temperature of the gas piping can reach up to approximately 120

°

C, 

so

 

use

 

insulation which is sufficiently resistant

.

〉〉〉〉

〈〈〈〈

Improve the insulation on the refrigerant piping depending on the installation environment.

If the insulation is not sufficient, condensation may form on the surface of the insulation.

〉〉〉〉

〈〈〈〈

Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not pos-

sible if the types of refrigerant are not the same.

〉〉〉〉

CAUTION

• Use a pipe cutter and flare suitable for the type of refrigerant.
• Apply ester oil or ether oil around the flare section before connecting.
• To prevent dust, moisuture or other foreign matter from infiltrating the tube, either pinch the end or 

cover it with tape.

• Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit, 

such as air, etc. If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly 
right away.

The outdoor unit is charged with refrigerant.

For the refrigerant piping and branching, follow the 

“piping connection procedure”

.

Be sure to use both a spanner and torque wrench together, as shown in the drawing, when connecting or 
disconnecting piping to/from the unit.

Refer to the Table 1 for the dimensions of flare nut spaces.

Nut (field supplied)

Washer 

(field supplied)

10-15mm

Hanging fitting

BEV main unit

Hanging bolt 

(field supplied)

Fig. 6

 

When hanging the unit from the ceiling

(1) Temporarily install the BEV unit.

(2) Adjust the height of the main unit with the nut.
(3) Check that the main unit is installed on the level.
(4) Tighten the nut on both the top and the bottom 

to fix securely.

Use only accessories and parts which are of the designated specification when installing.

● 

Mount the hanging fittings to 
hanging bolts. Secure the hanging fittings on 
the top and the bottom with nuts (M8, field 
supplied) and washers (M8: Outside diameter 
size 24 to 28 mm) (field supplied).

Mounting screws 

(field supplied)

Hanging fitting

BEV unit

 

When installing the unit on a wall

(1) Mount the hanging fittings with the 

mounting screws (4 pieces).

(2) Use M4 screws.

Fig. 7

3P084604-2A_Eng.fm  Page 7  Wednesday, March 3, 2004  10:01 AM

Summary of Contents for BEVQ100MVE

Page 1: ...A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI LEES DEZE INSTRUCTIES ZORGV...

Page 2: ...conformidade com a s seguinte s norma s ou outro s documento s normativo s desde que estes sejam utilizados de acordo com as nossas instru es overholder f lgende standard er eller andet andre retning...

Page 3: ...aler or qualified personnel to carry out installation work Do not try to install the machine yourself Improper installation may result in water leakage electric shocks or fire Perform installation wor...

Page 4: ...m televisions or radios in order to prevent image interference or noise Depending on the radio waves a distance of 1 meter may not be sufficient enough to eliminate the noise Remote controller wireles...

Page 5: ...e exposed to combustible gas and where volatile flammable gas like thinner or gasoline is used Gas in the vicinity of the unit could ignite Where machines can generate electromagnetic waves Control sy...

Page 6: ...eight if it seems dangerous install it after reinforcing the location with boards crossbeams etc 3 Install the gas piping connection piping 7 no further than 250mm form the hole for the thermistor on...

Page 7: ...stall so that the control box lid is facing down Take the gas piping thermistor out from above Horizontal position Direction of the gas piping connection piping 100 Upper Lower 100 250 or more 500 or...

Page 8: ...stall the hanging bolts Use M8 hanging bolts If it is pre set use hole in anchors Otherwise use embedded inserts or embedded foundation bolts to make sure that the weight of the unit can be supported...

Page 9: ...h tape Do not allow anything other than the designated refrigerant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while working on the unit ventilate the room t...

Page 10: ...ecting section after checking gas leakage by thoroughly studying the following figure Wrap the insulation for fitting 3 4 around the insulation for the joints on the liquid piping side and the gas pip...

Page 11: ...carried out nitrogen substitution or while inserting nitrogen into the refrigerant piping Once this is done connect the indoor unit with a flared connection Nitrogen should be set to 0 02 MPa 0 2 kg...

Page 12: ...Additional filling amount a b c d e f g h i j k l m n p q Refer also to the installation manual included with the outdoor unit 7 ELECTRIC WIRING WORK 7 1 GENERAL INSTRUCTIONS All field supplied parts...

Page 13: ...x Fuse Amps A KW Fan Motor Rated Output kW FLA Full Load Amps A NOTES The above Table of Electrical Characteristics refers to the BEV unit only See the technical documents for other details 7 3 SPECIF...

Page 14: ...e and the transmission wiring using the included clamp 1 CAUTIONS Do not under any circumstances connect the power supply wiring to the transmission terminal block F1 F2 as this may cause damage to th...

Page 15: ...the unit keep the weak wiring gas piping thermistor lead wire transmission wiring at least 50 mm away from strong wiring power supply wiring inter unit wiring ground wire and other power wiring The e...

Page 16: ...P1 P2 L N 1 2 3 F1 F2 L N P1 P2 P1 P2 L N T1 T2 P1 P2 F1 F2 L N P1 P2 IN D OUT D F1 F2 F1 F2 Control box Outdoor unit BEV Unit A Indoor Unit A Indoor Unit B Indoor Unit C Normal VRV Indoor Unit BEV Un...

Page 17: ...1 P2 P1 P2 L N OUT D BS IN D F1 F2 F1 F2 L N IN D OUT D F1 F2 F1 F2 Control box Outdoor unit Indoor Unit A F1 F2 F1 F2 1 2 TO indoor 3 F1 F2 L N BEV Unit A BS Unit A BS Unit B P1 P2 P1 P2 Indoor Unit...

Page 18: ...Once all piping work is done screw the control box lid shut using the mounting screws 9 HOW TO ATTACH THE NAMEPLATE Attach the included nameplate 9 next to the machine nameplate on the indoor unit 10...

Page 19: ...0404 HT 3P084604 2A EM03A115 FS 3P084604 2_cv fm Page 2 Thursday February 5 2004 2 41 PM...

Reviews: