6.6 Rotation pulse check on outdoor unit PCB
6.6.1 Turning speed pulse input on outdoor unit PCB check for ARXN/RXN25/35MV1B9
a. Make sure control voltage of DC15V is being applied.
b. Make a turn of the fan motor with hand and make sure the pulse (0-15V) appears 4 times at pins
10 and 13.
S70
13
12
11
10
9
8
7
6
5
4
3
2
1
HV (Hall IC)
HU (Hall IC)
Phase W
15V
Free pin
Free pin
Phase V
Free pin
Free pin
Phase U
Free pin
Free pin
6.6.2 Rotation pulse check on outdoor unit PCB for ARXN/RXN50/60M,RXB50/60B.RX60CG
Make sure that the voltage of 320 ± 30 V is applied.
1. Set operation off and power off. Disconnect the connector S70.
2. Check that the voltage between the pins 4 & 7 is 320 VDC.
3. Check that the control voltage between the pins 3 & 4 is 15 VDC.
4. Check that the rotation command voltage between the pins 2 & 4 is 0 - 6.5 VDC.
5. Keep operation off and power off. Connect the connector S70.
6. Check whether 4 pulses (0 ~ 15 VDC) are output at the pins 1 - 4 when the fan motor is rotated 1
turn by hand.
When the fuse is melted, check the outdoor fan motor for proper function.
If NG in step 2
:
Defective PCB and replace the outdoor unit PCB.
If NG in step 4
:
Defective Hall IC and replace the outdoor fan motor.
If OK in both steps 2 and 4,replace the outdoor unit PCB.
1
2
3
4
5
6
7
PCB
S70
Actual rotation pulse input (0 ~ 15 VDC)
320 VDC
Control voltage 15 VDC
Rotation command voltage (0 ~ 6.5 VDC)
Summary of Contents for ARXN25MV1B
Page 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Page 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Page 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Page 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...