Appendix A
62
6.5 Inverter analyzer check
If an abnormal stop occurs due to compressor start up failure or over current output when using an
Inverter unit, it is dif
fi
cult to judge whether the stop is caused by compressor failure or some other failure
(main PCB, power module and etc.). The inverter analyzer makes it possible to judge the cause of trouble
easily and securely. (Connect an inverter analyzer as quasi-compressor instead of compressor and check
the output of the inverter)
Operation Guide
a. Turn off the power
b. Install Inverter analyzer instead of compressor
c. Press cooling operation ON/OFF button for 5 seconds
Compressor
(1) Remove the terminals from
the compressor.
(2) Connect the terminals to the
terminals of the inverter analyzer.
Be careful not to let the terminals (U,
V, W) touch each other. Otherwise,
high voltage is applied.
Install an inverter analyzer instead of a compressor.
Inverter analyzer
Diagnosis Guide (according to 6 LEDs lighting status)
a. If all LEDs are lit uniformly, compressor is defective and need to replace.
b. If the LEDs are not lit uniformly, check the power module as below.
i. Disconnect compressor harness connector from outdoor PCB.
ii. Follow table below to measure resistance between (+) or (-) power module terminal or diode bridge
and the U, V, or W terminal of compressor with a multimeter. Evaluate the measurement results
referring to following table.
Negative (-) terminal of
multimeter
Power module (+)
or Diode bridge (+)
UVW
Power module (-)
or Diode bridge (-)
UVW
Positive (+) terminal of
multimeter
UVW
Power module (+)
or Diode bridge (+)
UVW
Power module (-)
or Diode bridge (-)
Resistance is OK
Several k
Ω
~ several M
Ω
Resistance is NG
0
Ω
or
∞
*Remark:
1. Make sure voltage between (+) and (-) of power module or the diode bridge is approximately 0V before checking
2. Use opposite sign of terminal for digital multimeter for measurement.
c. If NG in power module check, replace the main PCB.
d. If OK in power module check, observe any solder cracking on PCB.If there is any solder cracking
found, replace PCB or repair the soldered section. If there is no solder cracking, replace PCB.
Caution
a. When the output frequency is low, the LEDs blink slowly. As the output frequency increases, the
LEDs blink quicker. (The LEDs look like they are lit)
b. Upon completion of the inverter analyzer diagnosis, be sure to re-crimp the FASTON terminals.
Otherwise, terminals may be burned due to loosening.
Summary of Contents for ARXN25MV1B
Page 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Page 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Page 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Page 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...