Service Diagnosis
40
H0 (ARXN/RXN50/60L)
Description
COMPRESSOR SENSOR SYSTEM ABNORMAL
Supposed Cause
1. Broken and disconnected harness.
2. Outdoor unit PCB defective.
3. Defective
compressor.
Troubleshooting
# Disconnect the reactor wire and measure
resistance between terminal.
Any abnormal?
"
Yes
No
Check reactor connection.
Check reactor resistance.
Check compressor resistance.
Change outdoor PCB.
Yes
No
Change reactor.
"
Yes
No
Change Compressor.
Connect back reactor.