Service Diagnosis
41
H0 (ARXN/RXN25/35L/M)
Description
COMPRESSOR SENSOR SYSTEM ABNORMAL
Supposed Cause
1. Broken and disconnected harness.
2. Outdoor unit PCB defective.
Troubleshooting
Is the harness
broken?
Get restarted
and error
displayed again?
Yes
No
Turn off the power and turn it on
again.
Yes
No problem.
Keep on running.
No
Replace the harness.
Replace the PCB.
Check the harness S30.
H0 (ARXN/RXN50/60L/M)
Description
COMPRESSOR SENSOR SYSTEM ABNORMAL
Supposed Cause
1. Broken and disconnected harness.
2. Outdoor unit PCB defective.
Troubleshooting
Is the harness
broken?
Restart operation
and error displayed
again?
Yes
No
Turn off the power and turn it on
again.
Check the relay harness for the
compressor.
Yes
No problem.
Keep on running.
Replace the outdoor unit
PCB.
No
Replace the harness.