Service Diagnosis
25
When there is no error, compressor running frequency is displayed.
When there is error, it fl ashes the error code as below:
Normal operation
Flashing Error Code
In addition, 7 segment also can be use to retrieve unit operating condition such as running current, DC
voltage, ambient temperature, indoor air temperature, etc.
By pressing the tact switch, the 7 segment will start to fl ash from “
”. Press again, it will show “
” and
subsequent running number shows the parameter number.
Then, the 7 segment will fl ash again showing the parameter measurement.
When the 7 segment display is left untouched for 5 min, the display will light off (Dim).
Parameter
Number
Parameter Description
Unit/Range
00
Compressor Actual Rotation
r/s
01
Compressor Target Rotation
r/s
02
DC Bus Voltage
VDC
03
Total Current (x10)
A
04
Outdoor Air Temperature
°C
05
Outdoor Heat Exchanger Temperature
°C
06
Compressor Discharge Temperature
°C
07
Outdoor Heatsink Temperature
°C
08
Indoor Air Temperature
°C
09
Indoor Heat Exchanger Temperature
°C
10
Electronic Expansion Valve Opening
Pulse
41
Target Discharge Temperature
°C
Summary of Contents for ARXN25MV1B
Page 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Page 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Page 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Page 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...