Service Diagnosis
51
U2
Description
DC VOLTAGE OUT OF RANGE
Supposed Cause
1. Power supply voltage is not as specifi ed.
2. Defective DC voltage detection circuit.
3. Defective over-voltage detection circuit.
4. Defective PAM control part.
5. Disconnection of compressor harness
6. Short circuit inside the fan motor winding.
7. Noise.
8. Momentary drop of voltage.
9. Momentary power failure.
10. Defective outdoor unit PCB.
Troubleshooting
Is the
voltage fluctuation
within ±10% from the
rated value?
No
Yes
Yes
Check the power supply voltage.
Turn on the power.
Check the connection of the
compressor harness.
Yes
Disturbance factors
* Noise
* Power supply distortion
Replace the outdoor fan motor
and the outdoor unit PCB.
Check for such factors for
a long term.
Loose or
disconnected?
Does the
outdoor fan rotate
smoothly?
System restarted?
(Repeat a few
times.)
Yes
No
Reconnect the harness.
No
Correct the power supply.
No
(Precaution before turning on the power again.)
Make sure the power has been off for at least
30 seconds.
Replace the outdoor unit PCB.
Summary of Contents for ARXN25MV1B
Page 1: ...SERVICE MANUAL Inverter DOO 0RXQWHG Single Split SM 5WMY A1 R410A ...
Page 60: ...Wiring Connection 54 4 0 Wiring Connection Model ATXN FTXN 25 35L M ARXN RXN 25 35L M ...
Page 61: ...Wiring Connection 55 Model ATXN FTXN 50 60L ARXN RXN 50 60L ...
Page 62: ...Wiring Connection 56 Model ATXN FTXN 50 60M ARXN RXN 50 60M ...