Service Diagnosis
38
F3
Description
DISCHARGE PIPE OVERHEAT
Supposed Cause
1. Refrigerant
shortage.
2. Four way valve malfunctioning.
3. Discharge pipe thermistor defective.
4. Outdoor PCB defective.
5. Water mixed in the local piping.
6. EXV
defective.
7. Stop Valve defective.
Troubleshooting
Check the
thermistors.
Check the
electronic expansion
valve.
Malfunction
* Discharge pipe thermistor
* Outdoor heat exchanger thermistor
* Outdoor temperature thermistor
Functioning
Functioning
Replace the defective
thermistor(s).
Check the
refrigerant line.
Malfunction
* Refrigerant shortage
* Four way valve
* Water mixed
* Stop valve
Functioning
Refer to the refrigerant
line check procedure.
Replace the electronic
expansion valve or the coil.
Malfunction
Replace the outdoor unit PCB.
*Remark:
Refer to Appendix A for thermistor resistance checking procedures.(Page 59, item 6.1)
Refer to Appendix A for Electronic Expansion Valve (EXV) checking procedures. (Page 60, item 6.2)
Refer to Appendix A for Inverter unit refrigerant check procedures. (Page 62, item 6.4)