SiBE04-809
Main Functions
Function and Control
15
Inverter Features
The inverter provides the following features:
The regulating capacity can be changed according to the changes in the outside
temperature and cooling/heating load.
Quick heating and quick cooling
The compressor rotational speed is increased when starting the heating (or cooling). This
enables a quick set temperature.
Even during extreme cold weather, the high capacity is achieved. It is maintained even when
the outside temperature is 2°C.
Comfortable air conditioning
A detailed adjustment is integrated to ensure a fixed room temperature. It is possible to air
condition with a small room temperature variation.
Energy saving heating and cooling
Once the set temperature is reached, the energy saving operation enables to maintain the
room temperature at low power.
Frequency Limits
The following table shows the functions that define the minimum and maximum frequency:
Forced Cooling
Operation
For more information, refer to “Forced operation mode” on page
60
120
300
45˚C
Air discharge
temperature
inverter
normal heat pump
Start
seconds
(R1187)
Frequency limits
Limited during the activation of following functions
Low
Four way valve operation compensation. Refer to page 33.
High
Input current control. Refer to page 35.
Compressor protection function. Refer to page 34.
Heating peak-cut control. Refer to page 37.
Freeze-up protection control. Refer to page 36.
Defrost control. Refer to page 38.
Summary of Contents for ARXG25E3V1B
Page 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series ...
Page 11: ...Introduction SiBE04 809 x ...
Page 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4 ...