Troubleshooting
SiBE04-809
104
Service Diagnosis
Troubleshooting
Check No.06
Refer to P.118
P4
:
Radiation fin thermistor
J3
:
Discharge pipe thermistor
J6
:
Outdoor heat exchanger thermistor
H9
:
Outdoor air temperature thermistor
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
(R7346)
NO
YES
YES
YES
NO
NO
NO
YES
Turn on the power again.
Normal?
Reconnect.
Reconnect.
Replace defective one(s) of
the following thermistors.
Radiation fin thermistor
Discharge pipe thermistor
Outdoor heat exchanger
thermistor
Outdoor air thermistor
Indoor heat exchanger
thermistor
Replace the following
thermistor.
Replace the outdoor unit
PCB.
(Replace the indoor unit
PCB.)
Connector or thermistor
disconnected?
Error displayed
again on remote
controller?
Indoor heat
exchanger thermistor
functioning?
Check No. 06
Check the thermistor resistance
value.
Check No. 06
Check the indoor heat exchanger
thermistor resistance value in the
heating mode.