Indoor Unit
SiBE04-809
158
Removal Procedure
1.11 Removal of
Heat Exchanger
Procedure
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Step
Procedure
Points
Remove the electrical
box.
You can detach the indoor
unit without removing the
assembly of the outlet grille.
Caution
If gas leaks, repair the spot of
leaking, then collect all
refrigerant from the unit. After
conducting vacuum drying,
recharge proper amount of
refrigerant.
Caution
Do not contaminate any gas
(including air) other than the
specified refrigerant (R410A),
into refrigerant cycle.
(Contaminating of air or other
gas causes abnormal high
pressure in refrigerating
cycle, and this results in pipe
breakage or personal
injuries.)
Pay attention so that the
residual water in the drain
will not make the floor wet.
In case that a drain hose is
buried inside a wall, remove
it after the drain hose in the
wall is pulled out.
Use two wrenches to
disconnect pipes.
When disconnecting pipes,
cover every nozzle with caps
so as not to let dust and
moisture in.
1. Disconnect the refrigerant
piping.
1
Loosen the screws
fixed to the installation
plate.
2
Hold the indoor unit up
by a block.
Unscrew the flare nut
for piping by two
wrenches.
2. Remove the indoor unit.
1
Detach the indoor unit
from the installation
plate.
Summary of Contents for ARXG25E3V1B
Page 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series ...
Page 11: ...Introduction SiBE04 809 x ...
Page 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4 ...