Control Specification
SiBE04-809
40
Function and Control
3.11
Electronic Expansion Valve Control
Outline
The following items are included in the electronic expansion valve control.
Electronic expansion valve is fully closed
1. Electronic expansion valve is fully closed when turning on the power.
2. Pressure equalizing control
Open Control
1. Electronic expansion valve control when starting operation
2. Control when frequency changed
3. Control for defrosting
4. Control when a discharge pipe temperature is abnormally high
5. Control when the discharge pipe thermistor is disconnected
Feedback Control
1. Discharge pipe temperature control
Detail
The followings are the examples of control which function in each mode by the electronic
expansion valve control.
(R2833)
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
Fully closed when power is turned ON
Open control when starting
(Control of target discharge pipe temperature)
Pressure equalizing control
Open control when starting
(Control of target discharge pipe temperature)
(Defrost control FD=1)
Pressure equalizing control
Open control when starting
Continue
Pressure equalizing control
Control when frequency changed
Control for abnormally high discharge
pipe temperature
When power is turned ON
Cooling operation
Stop
Heating operation
Stop
Heating operation
Control of discharge pipe
thermistor disconnection
Stop
Operation pattern
: function
×
: not function
Summary of Contents for ARXG25E3V1B
Page 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series ...
Page 11: ...Introduction SiBE04 809 x ...
Page 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4 ...