Control Specification
SiBE04-809
44
Function and Control
3.13
Forced Operation Mode
Outline
Forced operating mode includes only forced cooling.
Detail
Forced Cooling
3.14 Additional Function
3.14.1
POWERFUL Operation Mode
Compressor operating frequency is increased to PI Max. (Max. Hz of operating room) and
outdoor unit airflow rate is increased.
3.14.2
Voltage Detection Function
Power supply voltage is detected each time equipment operation starts.
Item
Forced Cooling
Forced operation
allowing conditions
1) The outdoor unit is not abnormal and not in
the 3-minute standby mode.
2) The operating mode of the outdoor unit is
the stop mode.
3) The forced operation is ON.
The forced operation is allowed when the
above “and” conditions are met.
Starting/adjustment
If the forced operation switch is pressed as
the above conditions are met.
1) Command
frequency
68Hz
2) Electronic
expansion valve
opening
It depends on the capacity of the operating
indoor unit.
3) Outdoor unit
adjustment
Compressor is in operation
4) Indoor unit
adjustment
The command of forced operation is
transmitted to the indoor unit.
End
1) When the forced operation switch is
pressed again.
2) The operation is to end automatically after
15 min.
Others
The protect functions are prior to all others in
the forced operation.
Summary of Contents for ARXG25E3V1B
Page 1: ...SiBE04 809 Applied Models Inverter Pair Heat Pump Inverter Pair Wall Mounted Type E Series ...
Page 11: ...Introduction SiBE04 809 x ...
Page 12: ...SiBE04 809 List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 14: ...SiBE04 809 Specifications 3 Part 2 Specifications 1 Specifications 4 ...