9
|
Electrical installation
Installer reference guide
94
EPGA11~16DAV3(7) + EAVH/23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
Model (power supply)
Connections to backup heater power supply
*9W (3N~ 400 V)
3N~, 50 Hz
400 V AC
SWB
Q1DI
L1 L2 L3 N
1
2
3
4
5
6
7
8
F1B
I
I
I
I
X6M
2
1
K5M
4
3
6
5
14
13
BRN
GRY
BLK
BLU
F1B
Overcurrent fuse (field supply). Recommended fuse: 4‑pole; 20 A; curve 400 V;
tripping class C.
K5M
Safety contactor (in the lower switch box)
Q1DI
Earth leakage circuit breaker (field supply)
SWB
Switch box
X6M
Terminal (field supply)
NOTICE
Do NOT cut or remove the backup heater power supply cable.
9.3.3 To connect the shut-off valve
INFORMATION
Shut-off valve usage example.
In case of one LWT zone, and a combination of
underfloor heating and heat pump convectors, install a shut-off valve before the
underfloor heating to prevent condensation on the floor during cooling operation.
For more information, see the installer reference guide.
1
Connect the valve control cable to the appropriate terminals as shown in the
illustration below.
NOTICE
Wiring is different for a NC (normally closed) valve and a NO (normally open) valve.
X1M
X2M
X1M
X2M
NO
NC
M2S
M2S
21 28
21 29
2
Fix the cable with cable ties to the cable tie mountings.