4
|
About the box
Installer reference guide
23
EPGA11~16DAV3(7) + EAVH/23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
1×
2×
2×
1×
1×
ENERG
IJA
Y
IA
IE
ENERG
IJA
Y
IA
IE
1×
RXXX
1×
1×
a
d
e
b
c
a
Outdoor unit installation manual
b
Fluorinated greenhouse gases label
c
Multilingual fluorinated greenhouse gases label
d
Shut-off valve (with integrated filter)
e
Energy label
4.2.4 To remove the transportation stay
NOTICE
If the unit is operated with the transportation stay attached, abnormal vibration or
noise may be generated.
The compressor transportation stay must be removed. It is installed under the
compressor leg in order to protect the unit during transport. Proceed as shown in
the figure and procedure below.
1
Remove the nut (a) of the compressor mounting bolt.
2
Remove and discard the transportation stay (b).
3
Re-install the nut (a) of the compressor mounting bolt and tighten to
10.1 N•m of torque.