14
|
Troubleshooting
Installer reference guide
188
EPGA11~16DAV3(7) + EAVH/23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
14.3 Solving problems based on symptoms
14.3.1 Symptom: The unit is NOT heating or cooling as expected
Possible causes
Corrective action
The temperature setting is NOT correct Check the temperature setting on the
remote controller. Refer to the
operation manual.
The water flow is too low
Check and make sure that:
▪
All shut-off valves of the water circuit
are completely open.
▪
The water filter is clean. Clean if
necessary.
▪
There is no air in the system. Purge air
if necessary. You can purge air
manually (see
173]) or use the
automatic air purge function (see
▪
The water pressure is >1 bar.
▪
The expansion vessel is NOT broken.
▪
The valve (if equipped) of the water
circuit towards the expansion vessel is
open.
▪
The resistance in the water circuit is
NOT too high for the pump (see the
ESP curve in the "Technical data"
chapter).
If the problem persists after you have
conducted all of the above checks,
contact your dealer. In some cases, it is
normal that the unit decides to use a
low water flow.
The water volume in the installation is
too low
Make sure that the water volume in the
installation is above the minimum
required value (see
74]).
14.3.2 Symptom: Hot water does NOT reach the desired temperature
Possible causes
Corrective action
One of the tank temperature sensors is
broken.
See the service manual of the unit for
the corresponding corrective action.
Summary of Contents for Altherma EAVH16S23DA6V
Page 228: ...11 11...
Page 229: ......
Page 230: ......
Page 231: ......
Page 232: ...4P556070 1A 2021 09 Copyright 2018 Daikin Verantwortung f r Energie und Umwelt...