Make sure the return water to the heat pump does NOT exceed 60°C. To do so:
-
Set the desired water temperature via the auxiliary boiler controller to
maximum 60°C.
-
Install an aquastat valve in the return water flow of the heat pump. Set the
aquastat valve to close above 60°C and to open below 60°C.
▪
Install non-return valves.
▪
An expansion vessel is already pre-mounted in the indoor unit. But for bivalent
operation, also make sure that there is an expansion vessel in the auxiliary boiler
loop. Otherwise when bivalent operation is running and if the Aquastat valve
would close, there would be no expansion vessel in the water circuit anymore.
▪
Install the digital I/O PCB (option EKRP1HBAA).
▪
Connect X1 and X2 (changeover to external heat source) on the digital I/O PCB to
the auxiliary boiler. See
"9.3.8 To connect the changeover to external heat
▪
To setup the heat emitters, see
"6.2 Setting up the space heating/cooling
Configuration
Via the user interface (configuration wizard):
▪
Set the use of a bivalent system as external heat source.
▪
Set the bivalent temperature and hysteresis.
▪
Set the operation mode to space heating only (no tank operation).
Changeover to external heat source decided by an auxiliary contact
▪
Only possible in external room thermostat control AND one leaving water
temperature zone (see
"6.2 Setting up the space heating/cooling system"
▪
The auxiliary contact can be:
-
An outdoor temperature thermostat
-
An electricity tariff contact
-
A manually operated contact
-
…
▪
Setup: Connect the following field wiring:
L
N
H
Com
A
K2A
K1A
X2M
BTI
K2A
K1A
Indoor/Auto/Boiler
35 30
X Y
Indoor
B
TI
Boiler thermostat input
A
Auxiliary contact (normally closed)
H
Heating demand room thermostat (optional)
K1A
Auxiliary relay for activation of indoor unit (field supply)
K2A
Auxiliary relay for activation of boiler (field supply)
Indoor
Indoor unit
Auto
Automatic
Boiler
Boiler