10
|
Configuration
Installer reference guide
146
EPGA11~16DAV3(7) + EAVH/23DA6V(7)+9W(7)
Daikin Altherma 3 H F
4P556070-1A – 2021.09
#
Code
Description
[5.6]
[6-0D]
Heat up mode
:
▪
0:
Reheat only
: Only reheat operation is
allowed.
▪
1:
Schedule + reheat
: The domestic hot
water tank is heated according to a schedule
and between the scheduled heat up cycles,
reheat operation is allowed.
▪
2:
Schedule only
: The domestic hot water
tank can ONLY be heated according to a
schedule.
See the operation manual for more details.
INFORMATION
Risk of space heating capacity shortage for domestic hot water tank without internal
booster heater: In case of frequent domestic hot water operation, frequent and long
space heating/cooling interruption will happen when selecting the following:
Tank
>
Heat up mode
>
Reheat only
.
10.5.7 User settings
Language
#
Code
Description
[7.1]
N/A
Language
Time/date
#
Code
Description
[7.2]
N/A
Set the local time and date
INFORMATION
By default, daylight savings time is enabled and clock format is set to 24 hours. If you
want to change these settings, you can do this in the menu structure (
User
settings
>
Time/date
) once the unit is initialised.
Holiday
About holiday mode
During your holiday, you can use the holiday mode to deviate from your normal
schedules without having to change them. While holiday mode is active, space
heating/cooling operation and domestic hot water operation will be turned off.
Room frost protection and anti-legionella operation will remain active.
Typical workflow
Using holiday mode typically consists of the following stages:
1
Setting the starting date and ending date of your holiday.
2
Activating the holiday mode.
To check if holiday mode is activated and/or running
If
is displayed on the home screen, holiday mode is active.