9
|
Configuration
Installer reference guide
158
EPRA14~W1 + ET9W
Daikin Altherma 3 H HT F
4P587503-1A – 2020.01
INFORMATION
During disinfection of the domestic hot water tank, the DHW temperature can
exceed this maximum temperature.
INFORMATION
Limit the maximum hot water temperature according to the applicable legislation.
#
Code
Description
[5.8]
[6-0E]
Maximum
:
The maximum temperature that users can select
for the domestic hot water. You can use this
setting to limit the temperature at the hot water
taps.
The maximum temperature is NOT applicable
during disinfection function. See disinfection
function.
Hysteresis
The following ON hysteresis can be set.
Heat pump ON hysteresis
Applicable when domestic hot water preparation is reheat only. When the tank
temperature drops below the reheat temperature minus the heat pump ON
hysteresis temperature, the tank heats up to the reheat temperature.
The minimum ON temperature is 20°C, even if setpoint hysteresis is smaller than
20°C.
#
Code
Description
[5.9]
[6-00]
Heat pump ON hysteresis
▪
2°C~40°C
Reheat hysteresis
Applicable when domestic hot water preparation is screheat. When the
tank temperature drops below the reheat temperature minus the reheat hysteresis
temperature, the tank heats up to the reheat temperature.
#
Code
Description
[5.A]
[6-08]
Reheat hysteresis
▪
2°C~20°C
Setpoint mode
#
Code
Description
[5.B]
N/A
Setpoint mode
:
▪
Fixed
▪
Weather dependent