9
|
Configuration
Installer reference guide
131
EPRA14~W1 + ET9W
Daikin Altherma 3 H HT F
4P587503-1A – 2020.01
#
Code
Description
[1.6]
[2-0A]
Room sensor offset
(Human Comfort
Interface (BRC1HHDA used as room thermostat)):
Offset on the actual room temperature measured
by the Human Comfort Interface.
▪
–5°C~5°C, step 0.5°C
[1.7]
[2-09]
Room sensor offset
(external room sensor
option): Only applicable if the external room
sensor option is installed and configured.
▪
–5°C~5°C, step 0.5°C
9.5.3 Main zone
Overview
The following items are listed in the submenu:
2
Main zone
Additional zone
Room
Malfunctioning
Space heating/cooling
[2]
Main zone
Setpoint screen
[2.1]
Schedule
[2.2]
Heating schedule
[2.3]
Cooling schedule
[2.4]
Setpoint mode
[2.5]
Heating WD curve
[2.6]
Cooling WD curve
[2.7]
Emitter type
[2.8]
Setpoint range
[2.9]
Control
[2.A]
Thermostat type
[2.B]
Delta T
[2.C]
Modulation
[2.D]
Shut off valve
[2.E]
WD curve type
Setpoint screen
Control the leaving water temperature for the main zone via setpoint screen [2]
Main zone
.
See
Schedule
Indicate if the temperature of the leaving water is defined according to a schedule
or not.
Influence of the LWT setpoint mode [2.4] is as follows:
▪
In
Fixed
LWT setpoint mode, the scheduled actions consist of desired leaving
water temperatures, either preset or custom.
▪
In
Weather dependent
LWT setpoint mode, the scheduled actions consist of
desired shift actions, either preset or custom.
Summary of Contents for Altherma 3 H HT EPRA18DAW1
Page 250: ......
Page 251: ......
Page 252: ...4P587503 1A 2020 01 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...