INFORMATION
The setting [F‑0B] is only valid when there is a thermostat or external room
thermostat request setting (NOT in case of leaving water temperature setting).
During cooling
: If [F‑0B] is enabled, the shut off valve closes when the unit is
running in cooling operation mode. Enable this setting to avoid cold leaving water
through the heat emitter and the forming of condensation (e.g. under floor heating
loops or radiators).
#
Code
Description
[2.D.2]
[F-0C]
The shut off valve:
▪
0
No
: is NOT influenced by changing the space
operation mode to cooling.
▪
1
Yes
: closes when the space operation mode
is cooling.
9.5.4 Additional zone
Overview
The following items are listed in the submenu:
3
Additional zone
Space heating/cooling
Main zone
Room
Tank
[3]
Additional zone
Setpoint screen
[3.1]
Schedule
[3.2]
Heating schedule
[3.3]
Cooling schedule
[3.4]
Setpoint mode
[3.5]
Heating WD curve
[3.6]
Cooling WD curve
[3.7]
Emitter type
[3.8]
Setpoint range
[3.9]
Control
[3.A]
Thermostat type
[3.B]
Delta T
[3.C]
WD curve type
Setpoint screen
Control the leaving water temperature for the additional zone via setpoint screen
[3]
Additional zone
.
See
Schedule
Indicates if the desired leaving water temperature is according to a schedule.
See