3/11
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
└─ Heating WD curve
3.5
[0-00]
R/W
[9-05]~min(45,[9-06])°C, step: 1°C
[2-0C]=0
25°C
[2-0C]=1
35°C
[2-0C]=2
35°C
3.5
[0-01]
R/W
[9-05]~[9-06]°C, step: 1°C
[2-0C]=0
35°C
[2-0C]=1
45°C
[2-0C]=2
65°C
3.5
[0-02]
R/W
10~25°C, step: 1°C
15°C
3.5
[0-03]
R/W
-40~5°C, step: 1°C
-15°C
└─ Cooling WD curve
3.6
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C(*3)
[2-0C]=1
7°C(*3)
[2-0C]=2
18°C(*3)
3.6
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
22°C(*3)
3.6
[0-06]
R/W
25~43°C, step: 1°C
35°C(*3)
3.6
[0-07]
R/W
10~25°C, step: 1°C
20°C(*3)
Additional zone
3.7
[2-0D]
R/W
0: Underfloor heating
1: Fancoil unit
2: Radiator
└─ Setpoint range
3.8.1
[9-05]
R/W
15~37°C, step: 1°C
25°C
3.8.2
[9-06]
R/W
[2-0D]=2:
37~70, step: 1°C
70
°C
[2-0D]≠2:
37~55, step: 1°C
55°C
3.8.3
[9-07]
R/W
5~18°C, step: 1°C
7°C(*3)
3.8.4
[9-08]
R/W
18~22°C, step: 1°C
22°C(*3)
Additional zone
3.A
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
└─ Delta T
3.B.1
[1-0C]
R/W
3~10°C, step: 1°C
10°C
3.B.2
[1-0E]
R/W
3~10°C, step: 1°C
5°C(*3)
Additional zone
3.C
R/O
0: 2-points
1: Slope-Offset
Space heating / cooling
└─ Operation range
4.3.1
[4-02]
R/W
14~35°C, step: 1°C
35°C
4.3.2
[F-01]
R/W
10~35°C, step: 1°C
20°C(*3)
Space heating / cooling
4.4
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
4.5
[F-0D]
R/W
0: Continuous
1: Sample
2: Request
4.6
[E-02]
R/W (*3)
R/O
0: Reversible (*3)
1: Heating only
└─ Pump limitation
4.8.1
[9-0E]
R/W
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
4.8.2
[9-0D]
R/W
0~8, step:1
0 : No limitation
1~4 : 50~80%
5~8 : 50~80% during sampling
6
Space heating / cooling
4.9
[F-00]
R/W
0: Restricted
1: Allowed
4.A
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
4.B
[9-04]
R/W
1~4°C, step: 1°C
1°C
4.C
[2-06]
R/W
0: Disabled
1: Enabled
Tank
5.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
Number of zones
Antifrost
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
Delta T heating
Leaving water value for low ambient temp. for LWT add zone heating WD curve.
Thermostat type
Main zone
Pump operation mode
Unit type
WD curve type
Leaving water value for high ambient temp. for LWT add zone heating WD curve.
Additional zone
Emitter type
Low ambient temp. for LWT add zone heating WD curve.
Comfort setpoint
Cooling maximum
Delta T cooling
Space cooling OFF temp
Space heating OFF temp
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Cooling minimum
Heating minimum
Heating maximum
High ambient temp. for LWT add zone heating WD curve.
Increase around 0°C
Overshoot
Pump outside range
(*1) *6V_
(*2) *9W_
(*3) + EKHVCONV2
(#) Only applicable in Swedish language.
4P586462-1 - 2019.07