2) "r1" Error
① Occurring Condition: R-Sensor Disconnection / Short Circuit
② Control Method: F-Fan & Comp run as following in accordance with RT-S.
(But only when
Comp is On by F-S, On/Off occurs by the time per the following RT condition.
If RT-S error occurs at the same time, On/Off 3min/7min operation occurs only at Comp
On state)
③ Cancellation: Automatically cancelled if R-Sensor is normal.
3) "rt" Error
① Occurring Condition: RT-Sensor Disconnection / Short Circuit
② Control Method: Normal operation will occur, while ignoring controls by the RT-Sensor.
③ Cancellation: Automatically cancelled if RT-Sensor is normal.
④ Front PCB detects RT-Sensor. As communication is made with Main PCB, RT-Sensor is detected
every 10 min.
4) “d1" Error
① Occurring Condition: D-Sensor Disconnection / Short Circuit
② Control Method: D-HTR On for 30 min.
③ Cancellation: Automatically cancelled if D-Sensor is normal.
5 ) "dF", "dr", "dH“ Error (Detection of F/R/home-bar Door Switch Error, respectively)
① Occurring Condition: Door Open is detected for longer than one hr.
② Control Method: Functions related to a Door Switch detection is ignored.
③ Cancellation: Automatically cancelled if Door Switch Open/Close is detected.
6) "C1" Error
① Occurring Condition: With 3 hr of Comp operation, D-Sensor is -5℃ or higher.
② Control Method: Normal operation will occur.
③ Cancellation: When, at Comp Off, D-Sensor < -5℃
7) "F3" Error
① Occurring Condition: Returning by the Defrosting time limit of 60 min.
② Control Method: Normal operation will occur.
③ Cancellation: Automatically cancelled, if Defrosting is returned by the D-Sensor.
Contents
7. Control Method (At an Error Occurring)
1) "F1" Error
① Occurring Condition: F-Sensor Disconnection / Short Circuit
② Control Method: F-Fan & Comp run as following in accordance with RT-S.
(But if RT-S error occurs at the same time, On/Off 25min./25min. Operation will occur.)
③ Cancellation: Automatically cancelled if F-Sensor is normal.
RT-S Standard
~ 8
℃
~14
℃
~20
℃
~30
℃
~42
℃
42
℃~
On/Off (min)
14/50
16/41
27/45
26/22
35/20
35/20
RT-S Standard
~ 8
℃
~14
℃
~20
℃
~30
℃
~42
℃
42
℃~
On/Off (min)
Off
3/50
2/10
3/7
4/6
6/4
34
Summary of Contents for Q600 series
Page 7: ...3 1 Normal Compressor 3 Wiring Diagram 6...
Page 8: ...3 2 Inverter Compressor 7...
Page 9: ...4 1 FRQ 19D Dispenser only 4 External Size and Names of the Refrigerator 8...
Page 10: ...4 2 FRQ 19F Dispenser H bar 9...
Page 30: ...Contents 3 Ice Separation Mode 29...
Page 61: ...INVERTER BOX COMPRESSOR 60 INVERTER Compressor VESD11C INVERTER Compressor ENV4A5G L2B...
Page 101: ...10 4 How to install Water Line Dispenser Models only External Filter Type 100...
Page 102: ...101...