Overview

CyberPower Automatic Transfer Switches PDUs with dual input for power 
provide redundant and increased reliability for critical devices with a single 
power plug. Users can define the preferred input power source. When a 
selected source is unstable or unavailable, the ATS PDU will switch to the 
second power source to constantly provide power to connected devices. The 
entire ATS PDU series are designed with LED and LCD interfaces for users 
to easily observe power status and device load. On-site power management 
is accomplished as users can configure power settings, via LCD interface, 
according to local power condition. Available in both switched and metered/
monitored configurations, users have a broad base of options to select the 
ATS PDU that best fits their needs.

WARNING:

 This automatic transfer switch has dual power cords (A & B) to 

provide redundant power sources to devices with single power supplies and 
can be plugged into separate compatible sources* to ensure continuous 
access. Users select the preferred source as the primary input. CyberPower 
Smart App Online and Sinewave series UPS are highly recommended for use 
as the power source. 
*

Note:

 Only sine wave AC power sources are compatible with this ATS PDU. 

Simulated sine wave AC power sources are NOT compatible.

Model List

Switched Metered by 

Outlet Series

Metered by Outlet Series

1U

2U

1U

2U

PDU84001 
PDU84002 
PDU84004 
PDU84005 
PDU84006 
PDU84301

PDU84003 
PDU84007 
PDU84302

PDU74001
PDU74002
PDU74004
PDU74005
PDU74006 
PDU74301

PDU74003
PDU74007
PDU74302

Switched Series

Monitored Series

1U

2U

1U

2U

PDU44001
PDU44002
PDU44004
PDU44005
PDU44006
PDU44301

PDU44003
PDU44007
PDU44302

PDU34001
PDU34002
PDU34004
PDU34005
PDU34006
PDU34301

PDU34003
PDU34007
PDU34302

Metered Series

1U

2U

PDU24001
PDU24002
PDU24004
PDU24005
PDU24006 
PDU24301

PDU24003
PDU24007
PDU24302

*Selected models may not be available in certain regions. Please contact your 

CyberPower sales team for more information.

Safety Precautions

Read the following before installing or operating the Automatic Transfer 
Switches (ATS) PDU: 

• Use only the supplied hardware to attach the mounting brackets.
• The ATS PDU must be plugged into a single phase three-wire, grounded 

outlet on a circuit that is protected by a fuse or circuit breaker. For 15A 
PDU series, please use a 15A circuit protector. For 20A PDU series, please 
use a 20A circuit protector. For 30A PDU series, please use a 30A circuit 
protector. Connection to any other type of power outlet may result in a 
electrocution hazard.

• Do not use extension cords or adapters with these ATS PDUs.
• Never install an ATS PDU or associated wiring or equipment during a 

lightning storm.

• Ensure that the power cord, plug, and socket are in good condition.
• For the ATS PDU with attached input Power Cords, the socket must be 

installed near the equipment and must be easily accessible.

• Make sure to disconnect all power supply cords before attempting to 

service or remove this unit.

• As for overcurrent protection, please be noted that all ATS PDUs with an 

input current rating greater than 20A are equipped with two flush-mount 
branch circuit breakers.

Summary of Contents for PDU24001

Page 1: ...Automatic Transfer Switch USER S MANUAL Copyright 2021 Cyber Power Systems Inc All rights reserved K01 0000929 01...

Page 2: ......

Page 3: ...For 2U Models 12 Rear Mounting 13 For 1U Models 13 For 2U Models 15 Replacing LCD Panel 17 Electrical Installation 17 Locking Power Cord For IEC Type ATS PDU 18 Input Power Cord 18 Output Power Cord 1...

Page 4: ...PDU74002 PDU74004 PDU74005 PDU74006 PDU74301 PDU74003 PDU74007 PDU74302 Switched Series Monitored Series 1U 2U 1U 2U PDU44001 PDU44002 PDU44004 PDU44005 PDU44006 PDU44301 PDU44003 PDU44007 PDU44302 PD...

Page 5: ...0A Pour la s rie PDU 30A veuillez utiliser un disjoncteur de 30A La connexion tout autre type de prise de courant peut provoquer un choc lectrique N utilisez pas de rallonges ni d adaptateurs avec ces...

Page 6: ...y For 1U Models Product Contents ATS PDU Cable Ties Qty 18 NEMA Outlet Qty 30 IEC Outlet RJ45 DB9 Serial Port Connection Cable Mounting Bracket x 2 24 M4x8 Bracket Mounting Screws Includes eight spare...

Page 7: ...cludes two spares for each Cord Retention Tray X 2 12 M3x6 Cord Retention Tray Mounting Screws Includes two spares for each User s Manual and Software Download Card Users Manual PowerPanel Management...

Page 8: ...10 2 1 Critical Warning Normal USB Serial Enter Select SOURCE A SOURCE A 15A SOURCE B 15A SOURCE B 1 2 3 4 5 6 7 8 9 10 11 12 Critical Warning Normal Link Tx Rx In ENV USB Out Serial Enter Select A B...

Page 9: ...y Outlet Switched Monitor Series A B C D E F G H I J K L M N O P Source Status Indicator Indicates the status of Source A and B Source Selected Indicator Indicates Source A or B is in use Output Indic...

Page 10: ...Metered by Outlet Switched Monitor Series Source Status Indicator Indicates the status of Source A and B Source Selected Indicator Indicates Source A or B is in use Output Indicator Indicates the outp...

Page 11: ...PDU24007 Input Nominal Voltage 100 120V 200 240V 100 120V 200 240V Frequency 50 60Hz Derated Input Current 24A Plug Type 2 NEMA L5 30P 2 NEMA L6 30P 2 NEMA L5 30P 2 NEMA L6 30P Power Cord Type SR 10...

Page 12: ...ing Normal USB Serial Enter Select D E H A B A B C L I K M N O P Q BANK 1 20A BANK 2 20A 1 2 3 4 13 12 11 10 14 15 16 17 8 7 6 5 9 18 Source Status Indicator Indicates the status of Source A and B Sou...

Page 13: ...er sources are compatible with this ATS PDU Simulated sine wave AC power sources are NOT compatible CyberPower Sinewave UPS CyberPower Online UPS Utility Power Utility Power Utility Power CyberPower O...

Page 14: ...d ATS PDU are aligned Attach the Cord Retention Tray to the ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws Tighten the Cord Retention Tray with the screw on it Step 3 ATS PDU Mounting...

Page 15: ...16 to attach the Mounting Brackets 2 to the ATS PDU Step 2 Cord Retention Tray Installation optional Adjust the length of the Cord Retention Trays till the screw hole on the Trays and ATS PDU are ali...

Page 16: ...rew sets provided by the rack to secure the ATS PDU Step 4 Cable Ties Optional Use the provided Cable Ties to fasten each cord to the Cord Retention Tray Rear Mounting For 1U Models Step 1 Mounting Br...

Page 17: ...t the length of the Cord Retention Tray till the screw hole on the Tray and ATS PDU are aligned Attach the Cord Retention Tray to the ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws Ti...

Page 18: ...Step 1 Mounting Bracket Installation Use the provided Mounting Bracket Screws 16 to attach the Mounting Brackets 2 to the ATS PDU If you plan on attaching the Cord Retention Tray to the ATS PDU use th...

Page 19: ...o the ATS PDU with the 8 supplied Cord Retention Tray Mounting Screws Tighten the Cord Retention Trays with the screw on it Step 3 ATS PDU Mounting Use the provided Washers 4 and Screws 4 to secure th...

Page 20: ...st also be connected to an appropriate branch circuit main with fuse or circuit breaker protection Connection to any other type of receptacle may result in an electrocution hazard Step 2 Plug the ATS...

Page 21: ...d Stand and fasten it as shown below Step 2 Align and insert the Cable Tie from the bottom side of the Fixed Stand and fasten it as shown below Output Power Cord Step 1 Align and insert the Cable Tie...

Page 22: ...ation instructions see Appendix B Option 2 DHCP Server 1 Ask your administrator if there is DHCP server on the LAN 2 Make sure the DHCP is Enabled 3 Make sure the network connection is ready and power...

Page 23: ...SNMP supported management software Default read write community is public private for SNMPv1 SNMPv3 provides a higher security level than SNMPv1 by encrypting the transmitted packet Configure the sett...

Page 24: ...ttended Automatic Shutdown PowerPanel Business Remote software automatically initiates a graceful shutdown on the connected computer s operating system PowerPanel must be installed on every computer o...

Page 25: ...t turn the ATS PDU off when performing the firmware upgrade ATS PDU outlets will remain powered on while the firmware update takes place Only the ATS PDU LCD screen will reboot 3 The ATS PDU LCD scree...

Page 26: ...the Upgrade and Configuration Utility from www cyberpower com 2 Open Upgrade and Configuration Utility from Start All Programs CyberPower Upgrade and Configuration Utility 3 Wait for search to finish...

Page 27: ...data file to be updated Shown in Figure 4 Figure 4 8 Click OK in the Upgrade Firmware confirmation window Shown in Figure 5 9 The upgrade progress bar will show in Last Action column Shown in Figure...

Page 28: ...n and Yes to start the upgrade process 6 The ATS PDU will reboot after the process is completed Note You can check to see if the firmware upgrade is successful by checking the Firmware version on the...

Page 29: ...psmpdumafw_XXX bin and cpsmpdumadata_XXX bin In order to upgrade the firmware version both files need to be uploaded Only one firmware file can be uploaded at a time it is recommended to upload the fi...

Page 30: ...appareil numerique de la class A respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada European Union This is a class A product In a domestic environment this product may c...

Page 31: ...for Shipping We pay when we send items to you you pay when you send items to us What Are Some Things This Warranty Does Not Cover 1 This Warranty does not cover any software that is damaged or needs...

Page 32: ...6 Account Settings 7 Configure System to Default 8 Logout Utility Configuration 1 Preferred Source A 2 Sensitivity High 3 Voltage Range Medium 4 Frequency Deviation 1 Hz 5 Nominal Voltage 230 V 6 Wide...

Page 33: ...ddresses on CyberPower ATS PDUs Installation Step 1 Download the Power Device Network Utility software from www cyberpower com Step 2 Select Next in the software wizard Shown in Figure 1 Step 3 Choose...

Page 34: ...h a specific IP address subnet mask and gateway address This allows the device s to function properly on the network and interface with CyberPower Management Console Step 1 Select the appropriate ATS...

Page 35: ...ord of the ATS PDU at the Authentication menu shown in Figure 9 Note The default username is cyber and the default password is cyber Figure 9 Authentication screen Advanced Settings Timeout Settings T...

Page 36: ...hain In ENV port on the Guest 1 ATS PDU to connect the ATS PDUs as shown below How to connect the PDUs together Use one Ethernet cable and connect one end of it to the daisy chain Out port on the Host...

Page 37: ...he Guest PDUs through the Host PDU Yes you can upgrade the firmware using the Upgrade and Configuration Utilit FTP network connection required or USB port Once the Host completes th PDU firmware upgra...

Page 38: ...d the Guest ATS PDUs are able to connect to the network directly Note that a Guest ATS PDU will require having its own Ethernet cable connected to the network What will happen if a 5th ATS PDU is adde...

Page 39: ......

Page 40: ...Cyber Power Systems Inc www cyberpower com Copyright 2021 Cyber Power Systems Inc All rights reserved K01 0000929 01...

Reviews: