Step 1 – Network Connection 

Using an Ethernet cable, attach one end to the Ethernet port on the 
front of the ATS PDU, and the other end to a network port.

Step 2 – Establish the ATS PDU IP address 

Assigning an IP address to the CyberPower ATS PDU requires the 
user to have an available IP address that is valid on the respective 
network. If an available IP address is unknown, contact the network 
administrator to obtain one.

DHCP is enabled by factory default. If the ATS PDU does not receive an IP 
address from the network's DHCP server, it will default to 192.168.20.177.

There are multiple methods for setting up the IP address of the ATS PDU 
Please follow the instructions below for the method that is appropriate for your 
application.

Please make sure the ATS PDU is powered on during this process.

Option 1: Power Device Network Utility (recommended)
1.  Download and install the Power Device Network Utility software from              

www.cyberpower.com.

2. Open the Power Device Network Utility and select the ATS PDU device from 

the list and select Tools > Device Setup from the menu.

3. Configure the IP Address, Subnet Mask, and Gateway Address to match 

your network settings.

4. Enter the user name and password of the ATS PDU device at the Authentication 

menu. 

Note:

 The default username is “

cyber

” and the default password is “

cyber

”. For 

further information and installation instructions, see Appendix B.

Option 2: DHCP Server
1.  Ask your administrator if there is DHCP server on the LAN.
2. Make sure the DHCP is Enabled.
3. Make sure the network connection is ready and power on the ATS PDU.
4. The ATS PDU will obtain an IP address from the DHCP server automatically.

Option 3: Address Resolution Protocol (ARP) Command
1.  Obtain the MAC address from the sticker on the ATS PDU.
2. Open a command prompt as an administrator and type the following: 

“arp -s [available IP address] [MAC address of ATS PDU]”.

 Example:

 arp -s 192.168.20.240 

00-0C-15-00-00-01

   

 

         IP Address  

 

     MAC Address

3. Use the Ping command to assign a size of 123 bytes to the IP.

* Type in “

ping 192.168.20.240 -l 123

” then press 

Enter

.

* If the replies are received, your computer can communicate with the IP 

address.

Option 4: Hyper Terminal or Terminal Emulator
1.  Use the included RJ45/DB9 serial port connection cable, attach one end to 

the serial port on the front of the ATS PDU, and the other end to the PC/server.

2. Open the Hyper Terminal software on your PC and select a name and icon for 

the connection.

3. Setup the COM port settings using the values indicated in Appendix A.
4. Press 

Enter

 to enter the Authentication menu.

5. Enter the user name and password of the ATS PDU device at the Authentication 

menu.

6. Press 

4

 and 

Enter

 to access Network Settings to view the IP address.

Note:

 The default username is “

cyber

” and the default password is “

cyber

”. 

For further information and configuration via Hyper Terminal, see 
Appendix A-Hyper Terminal.

Network Installation

Installation Guide

Summary of Contents for PDU24001

Page 1: ...Automatic Transfer Switch USER S MANUAL Copyright 2021 Cyber Power Systems Inc All rights reserved K01 0000929 01...

Page 2: ......

Page 3: ...For 2U Models 12 Rear Mounting 13 For 1U Models 13 For 2U Models 15 Replacing LCD Panel 17 Electrical Installation 17 Locking Power Cord For IEC Type ATS PDU 18 Input Power Cord 18 Output Power Cord 1...

Page 4: ...PDU74002 PDU74004 PDU74005 PDU74006 PDU74301 PDU74003 PDU74007 PDU74302 Switched Series Monitored Series 1U 2U 1U 2U PDU44001 PDU44002 PDU44004 PDU44005 PDU44006 PDU44301 PDU44003 PDU44007 PDU44302 PD...

Page 5: ...0A Pour la s rie PDU 30A veuillez utiliser un disjoncteur de 30A La connexion tout autre type de prise de courant peut provoquer un choc lectrique N utilisez pas de rallonges ni d adaptateurs avec ces...

Page 6: ...y For 1U Models Product Contents ATS PDU Cable Ties Qty 18 NEMA Outlet Qty 30 IEC Outlet RJ45 DB9 Serial Port Connection Cable Mounting Bracket x 2 24 M4x8 Bracket Mounting Screws Includes eight spare...

Page 7: ...cludes two spares for each Cord Retention Tray X 2 12 M3x6 Cord Retention Tray Mounting Screws Includes two spares for each User s Manual and Software Download Card Users Manual PowerPanel Management...

Page 8: ...10 2 1 Critical Warning Normal USB Serial Enter Select SOURCE A SOURCE A 15A SOURCE B 15A SOURCE B 1 2 3 4 5 6 7 8 9 10 11 12 Critical Warning Normal Link Tx Rx In ENV USB Out Serial Enter Select A B...

Page 9: ...y Outlet Switched Monitor Series A B C D E F G H I J K L M N O P Source Status Indicator Indicates the status of Source A and B Source Selected Indicator Indicates Source A or B is in use Output Indic...

Page 10: ...Metered by Outlet Switched Monitor Series Source Status Indicator Indicates the status of Source A and B Source Selected Indicator Indicates Source A or B is in use Output Indicator Indicates the outp...

Page 11: ...PDU24007 Input Nominal Voltage 100 120V 200 240V 100 120V 200 240V Frequency 50 60Hz Derated Input Current 24A Plug Type 2 NEMA L5 30P 2 NEMA L6 30P 2 NEMA L5 30P 2 NEMA L6 30P Power Cord Type SR 10...

Page 12: ...ing Normal USB Serial Enter Select D E H A B A B C L I K M N O P Q BANK 1 20A BANK 2 20A 1 2 3 4 13 12 11 10 14 15 16 17 8 7 6 5 9 18 Source Status Indicator Indicates the status of Source A and B Sou...

Page 13: ...er sources are compatible with this ATS PDU Simulated sine wave AC power sources are NOT compatible CyberPower Sinewave UPS CyberPower Online UPS Utility Power Utility Power Utility Power CyberPower O...

Page 14: ...d ATS PDU are aligned Attach the Cord Retention Tray to the ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws Tighten the Cord Retention Tray with the screw on it Step 3 ATS PDU Mounting...

Page 15: ...16 to attach the Mounting Brackets 2 to the ATS PDU Step 2 Cord Retention Tray Installation optional Adjust the length of the Cord Retention Trays till the screw hole on the Trays and ATS PDU are ali...

Page 16: ...rew sets provided by the rack to secure the ATS PDU Step 4 Cable Ties Optional Use the provided Cable Ties to fasten each cord to the Cord Retention Tray Rear Mounting For 1U Models Step 1 Mounting Br...

Page 17: ...t the length of the Cord Retention Tray till the screw hole on the Tray and ATS PDU are aligned Attach the Cord Retention Tray to the ATS PDU with the 4 supplied Cord Retention Tray Mounting Screws Ti...

Page 18: ...Step 1 Mounting Bracket Installation Use the provided Mounting Bracket Screws 16 to attach the Mounting Brackets 2 to the ATS PDU If you plan on attaching the Cord Retention Tray to the ATS PDU use th...

Page 19: ...o the ATS PDU with the 8 supplied Cord Retention Tray Mounting Screws Tighten the Cord Retention Trays with the screw on it Step 3 ATS PDU Mounting Use the provided Washers 4 and Screws 4 to secure th...

Page 20: ...st also be connected to an appropriate branch circuit main with fuse or circuit breaker protection Connection to any other type of receptacle may result in an electrocution hazard Step 2 Plug the ATS...

Page 21: ...d Stand and fasten it as shown below Step 2 Align and insert the Cable Tie from the bottom side of the Fixed Stand and fasten it as shown below Output Power Cord Step 1 Align and insert the Cable Tie...

Page 22: ...ation instructions see Appendix B Option 2 DHCP Server 1 Ask your administrator if there is DHCP server on the LAN 2 Make sure the DHCP is Enabled 3 Make sure the network connection is ready and power...

Page 23: ...SNMP supported management software Default read write community is public private for SNMPv1 SNMPv3 provides a higher security level than SNMPv1 by encrypting the transmitted packet Configure the sett...

Page 24: ...ttended Automatic Shutdown PowerPanel Business Remote software automatically initiates a graceful shutdown on the connected computer s operating system PowerPanel must be installed on every computer o...

Page 25: ...t turn the ATS PDU off when performing the firmware upgrade ATS PDU outlets will remain powered on while the firmware update takes place Only the ATS PDU LCD screen will reboot 3 The ATS PDU LCD scree...

Page 26: ...the Upgrade and Configuration Utility from www cyberpower com 2 Open Upgrade and Configuration Utility from Start All Programs CyberPower Upgrade and Configuration Utility 3 Wait for search to finish...

Page 27: ...data file to be updated Shown in Figure 4 Figure 4 8 Click OK in the Upgrade Firmware confirmation window Shown in Figure 5 9 The upgrade progress bar will show in Last Action column Shown in Figure...

Page 28: ...n and Yes to start the upgrade process 6 The ATS PDU will reboot after the process is completed Note You can check to see if the firmware upgrade is successful by checking the Firmware version on the...

Page 29: ...psmpdumafw_XXX bin and cpsmpdumadata_XXX bin In order to upgrade the firmware version both files need to be uploaded Only one firmware file can be uploaded at a time it is recommended to upload the fi...

Page 30: ...appareil numerique de la class A respecte toutes les exigencies du Reglement sur le materiel brouilleur du Canada European Union This is a class A product In a domestic environment this product may c...

Page 31: ...for Shipping We pay when we send items to you you pay when you send items to us What Are Some Things This Warranty Does Not Cover 1 This Warranty does not cover any software that is damaged or needs...

Page 32: ...6 Account Settings 7 Configure System to Default 8 Logout Utility Configuration 1 Preferred Source A 2 Sensitivity High 3 Voltage Range Medium 4 Frequency Deviation 1 Hz 5 Nominal Voltage 230 V 6 Wide...

Page 33: ...ddresses on CyberPower ATS PDUs Installation Step 1 Download the Power Device Network Utility software from www cyberpower com Step 2 Select Next in the software wizard Shown in Figure 1 Step 3 Choose...

Page 34: ...h a specific IP address subnet mask and gateway address This allows the device s to function properly on the network and interface with CyberPower Management Console Step 1 Select the appropriate ATS...

Page 35: ...ord of the ATS PDU at the Authentication menu shown in Figure 9 Note The default username is cyber and the default password is cyber Figure 9 Authentication screen Advanced Settings Timeout Settings T...

Page 36: ...hain In ENV port on the Guest 1 ATS PDU to connect the ATS PDUs as shown below How to connect the PDUs together Use one Ethernet cable and connect one end of it to the daisy chain Out port on the Host...

Page 37: ...he Guest PDUs through the Host PDU Yes you can upgrade the firmware using the Upgrade and Configuration Utilit FTP network connection required or USB port Once the Host completes th PDU firmware upgra...

Page 38: ...d the Guest ATS PDUs are able to connect to the network directly Note that a Guest ATS PDU will require having its own Ethernet cable connected to the network What will happen if a 5th ATS PDU is adde...

Page 39: ......

Page 40: ...Cyber Power Systems Inc www cyberpower com Copyright 2021 Cyber Power Systems Inc All rights reserved K01 0000929 01...

Reviews: